background image

To empty the refrigerant pipe from air and humidity, the use of the vacuum pump is recommended.

PIPING CONNECTION

5

ATTENTION: ONLY ACR 

copper pipes for air conditioners are allowed

YES

NO

Connecting the pipes

Do  not  remove  the  cap  from  the  pipe  until  connecting
it, to avoid dampness or dirt from entering.
If  the  pipe  is  bent  or  pulled  too  often,  it  will  become
stiff. Do not bend the pipe more than three times at one
place.
When extending the rolled pipe, straighten the pipe by
unwinding it gently as shown in the figure below

To avoid leakage, pay particular attention to the following points:
Tighten the flare nuts using two wrenches. Pay attention not to damage the pipes.
If the tightening torque is not sufficient, there will probably be some leakage. With excessive tightening torque there will also be
some leakage, as the flange could be damaged.
The surest system consists in tightening the connection by using a fix wrench and a torque wrench: in this case use the following
table.

CONNECTIONS TO THE INDOOR UNIT

Shape the connection pipe following the diagram.
Remove the indoor unit pipe cap (check that there is no
debris inside).
Insert  the  flare  nut  and  create  a  flange  at  the  extreme
end of the connection pipe.
Connect the pipes by using two wrenches.

CONNECTIONS TO THE OUTDOOR

UNIT

Screw  the  flare  nuts  to  the  outdoor  unit  coupling  with
the same tightening procedures described for the indoor
unit.

flare nuts

connection pipes

gas tap

liquid tap

indoor unit

FLANGE CONNECTION TIGHTENING TORQUE 

Pipe

Tightening torque 

Corresponding stress

[N x m]

(using a 20 cm wrench)

6,35  mm (

1

/

4

”)

15 - 20

wrist strength

9,52 mm (

3

/

8

”)

31 - 35

arm strength

12,70 mm (

1

/

2

”)

5

0

  -

5

5

arm strength

15,88 mm (

5

/

8

”)

6

5 - 

7

0

arm strength

TIGHTENING TORQUE FOR PROTECTION CAPS

Tightening torque

[N x m]

Service port nut

7 - 9

Protection caps

25 - 30

Service port nut

torque wrench

IMPORTANT ! REFRIGERANT LEAKAGE INSPECTION

After connecting the piping, check the joints for refrigerant leakage with leak detector carefully.

Содержание MDUN 10H

Страница 1: ...INSTALLATION MANUAL MANUALE DI INSTALLAZIONE MDUN 10H MDUN 13H MDUN 18H MDUN 24H INVERTER SPLIT AIR CONDITIONER CLIMATIZZATORI D ARIA A PARETE INVERTER...

Страница 2: ...ER PIPING MOVING A SPLIT AIR CONDITIONER TO ANOTHER LOCATION REQUIRES SPECIAL TECHNIQUE IF NECESSARY CONSULT WITH THE SELLER wall type air conditioners inverter INSTALLATION MANUAL INSTALLATION ACCESS...

Страница 3: ...SELECTING THE INSTALLATION PLACE 1 insulating covering sleeve condensed water drain pipe electrical connections Do not install the outdoor unit near sources of heat steam or flammable gases Do not in...

Страница 4: ...d horizontally 2 Fix the bracket first with 5 screws 3 Use several more tapping screws to secure the bracket onto the wall with even pressure on the screws 4 Cut a hole in the wall for the piping and...

Страница 5: ...n pipes refrigerant pipe power cable 1 2 3 1 2 INDOOR UNIT CONDENSED WATER DRAINAGE 3 YES NO NO The indoor unit condensed water drainage is fundamental for the success of the installation Install the...

Страница 6: ...g the connection by using a fix wrench and a torque wrench in this case use the following table CONNECTIONS TO THE INDOOR UNIT Shape the connection pipe following the diagram Remove the indoor unit pi...

Страница 7: ...4 1 ATTENTION In case the outdoor unit has been installed higher than the indoor unit it is necessary to provide S oil traps or liquid separator to both refrigerant pipes overy 3 m of difference in l...

Страница 8: ...OOR UNIT TEST Do the ON OFF and FAN keys operate normally Does the MODE key operate normally Do the set point and TIMER keys function properly Does each lamp light normally Do the louvers for air flow...

Страница 9: ...1 ATTENTION In case the outdoor unit has been installed higher than the indoor unit it is necessary to provide S oil traps or liquid separator to both refrigerant pipes overy 2 m of difference in leve...

Страница 10: ...he ON OFF and FAN keys operate normally Does the MODE key operate normally Do the set point and TIMER keys function properly Does each lamp light normally Do the louvers for air flow direction operate...

Страница 11: ...UN CLIMATIZZATORE SPLIT DOPO CHE E STATO INSTALLATO E UN OPERAZIONE CHE RICHIEDE UNA SPECIFICA PREPARAZIONE NEL CASO SIA NECESSARIO CONSULTARE IL VOSTRO RIVENDITORE MANUALE INSTALLAZIONE ACCESSORI PE...

Страница 12: ...tro sia facilmente accessibile UNITA ESTERNA Non installare l unit esterna vicino a fonti di calore vapore o gas infiammabili Non installare l unit in luogo particolarmente ventoso o polveroso Non pos...

Страница 13: ...ti perfettamente in asse sia verticalmente che orizzontalmente 2 Fissare la dima inizialmente con 5 viti 3 Usare poi altre viti per fissare la dima al muro in modo uniforme su tutta la superficie 4 Fo...

Страница 14: ...solamento tubazioni tubazione frigorifera cavo di potenza 1 2 3 1 2 SCARICO DELLA CONDENSA DELL UNIT INTERNA 3 SI NO NO Lo scarico della condensa dell unit interna un punto fondamentale per la buona r...

Страница 15: ...lizzare la seguente tabella CONNESSIONI ALL UNIT INTERNA Sagomare i tubi di collegamento secondo il tracciato Togliere la calottina di chiusura dei tubi dell unit interna verificare che all interno no...

Страница 16: ...na sia stata installata ad un altezza superiore rispetto all unit interna necessario praticare dei sifoni o applicare dei separatori di liquido su entrambe le tubazioni ogni 3 metri di dislivello MODE...

Страница 17: ...TERNA I tasti ON OFF e FAN funzionano regolarmente Il tasto MODE funziona regolarmente I tasti per l impostazione del set point e del TIMER funzionano correttamente Si accendono tutte le spie Le alett...

Страница 18: ...stata installata ad un altezza superiore rispetto all unit interna necessario praticare dei sifoni o applicare dei separatori di liquido su entrambe le tubazioni ogni 2 metri di dislivello MODELLO Dia...

Страница 19: ...ionano regolarmente Il tasto MODE funziona regolarmente I tasti per l impostazione del set point e del TIMER funzionano correttamente Si accendono tutte le spie Le alette per l orientamento dell aria...

Страница 20: ...per le possibili inesattezze se dovute ad errori di trascrizione o di stampa Si riserva altres il diritto di apportare ai propri prodotti quelle modifiche che riterr necessarie o utili senza pregiudi...

Отзывы: