hnical f
eatures and dimensions
3.6 - POSITIONING IN BOILER ROOM
TERNOX 2S boilers must be installed in rooms for exclusive
use complying with Technical Standards and Legislation in
force and with sufficiently sized air vents.
The ventilation openings must be permanent, communicating
directly with the outside and must be positioned high or low
according to standards in force.
The location of the ventilation openings, the fuel supply trains,
electric energy supply and lighting must comply with current
legal provisions in relation to the type of fuel used.
To make it easier to clean the smoke circuit, a free space must
be left in front of the boiler no less than the length of the boiler
body and, in any case, never less than 1300 mm. It must be
checked that with the door/s open 90°, the distance between
the door and the adjacent wall X is at least equal to the length
of the burner.
The boiler must rest on a perfectly level surface.
It is advisable to provide a flat, level cement basement capable
of bearing the weight of the boiler full of water. For the dimen-
sions of the basement, see the dimensions R x B (dimensions
table).
If the burner is fed with fuel gas weighing more than air, the
electrical parts must be placed higher than 500 mm above the
ground.
The appliance cannot be installed outdoors as it was not so
designed and does not have automatic antifreeze systems.