2.4 wATER SIDE PRESSURE DROPS DIAGRAM
Pressure drop (m/H2
o
)
Flow rate (m
3
/h)
2.4.1 - DETERMINATION OF THE PRIMARY CIRCUIT PUMP OR BOILER PUMP
The pumps must be determined by the installer
or designer according to the boiler and sys-
tem data.
The boiler pump must have head that is able to ensure the pump's
flow rates according to the circuit's
∆
t.
The pump is not an integral part of the boiler.
It is recommended to select a pump with a flow rate and
head of approximately 2/3 of its characteristic curve.
SPK 150
Maximum flow rate in l/h (
∆
t=8K)
14,655
Maximum flow rate in l/h (
∆
t=15K)
7,816
Requested rated output in l/h (
∆
t=20K)
5,862
SPK 300
Maximum flow rate in l/h (
∆
t=8K)
29,426
Maximum flow rate in l/h (
∆
t=15K)
15,695
Requested rated output in l/h (
∆
t=20K)
11,772
SPK 230
Maximum flow rate in l/h (
∆
t=8K)
22,495
Maximum flow rate in l/h (
∆
t=15K)
11,997
Requested rated output in l/h (
∆
t=20K)
8,998
SPK 400
Maximum flow rate in l/h (
∆
t=8K)
39,883
Maximum flow rate in l/h (
∆
t=15K)
21,303
Requested rated output in l/h (
∆
t=20K)
15,977
SPK 500
Maximum flow rate in l/h (
∆
t=8K)
47,300
Maximum flow rate in l/h (
∆
t=15K)
25,606
Requested rated output in l/h (
∆
t=20K)
19,203
SPK 600
Maximum flow rate in l/h (
∆
t=8K)
57,405
Maximum flow rate in l/h (
∆
t=15K)
30,616
Requested rated output in l/h (
∆
t=20K)
22,962