To determine the combustion efficiency
one must make the following measurements:
- measurement of the combustion air temperature
taken in the relevant hole
1
.
- measurement of the flue gas temperature and
content of CO
2
taken in the relevant hole
2
.
Take the measurements with the generator in
steady state conditions (see par. 3.11.1).
3.11.2 - POSITIONING THE PROBES
C
PIPES Ø 80 TYPE B23
1
2
1
B
SEPARATE PIPES
2
1
2
A
COAXIAL PIPES
1
Air
probe
2
N.B.: Insert the smoke probe only
afterwards ignition of the burner,
this in order to avoid saturation of the
analyzer cells.
Flue gas
probe
Air
probe
Air
probe
Flue gas
probe
Flue gas
probe