28
CALDAIA PELLEXIA
VASO
ESPANSIONE
POMPA 4
RICIRCOLO
POMPA 3
IMPIANTO
RISCALDAMENTO
IMPIANTO
RISCALDAMENTO
POMPA 2
BOLLITORE
PRODUTTORE ACQUA
CALDA SANITARIA
S 4
S 3
S 5
3.11.2 - PELLEXIA BOILER SYSTEM FOR HEATING AND FOR THE PRODUCTION OF
DOMESTIC HOT WATER, WITH SINGLE-COIL TYPE STORAGE TANK
In this diagram, the boiler is connected to both the heating sys-
tem and to a domestic hot water storage tank; there are the
P3
heating system pump, the
P2
storage tank pump, and the
recirculation pump.
NB: The P4 recirculation and balancing pump is essential;
it serves the purpose of balancing the flow and return tem-
perature of the boiler and adds cold water when necessary
to prevent the risk of condensation.
The
S3
probe is required to install and run the storage tank be-
cause it controls the temperature and the priority of either heat-
ing or hot water.
When the temperature of the storage tank falls below the mini-
mum threshold, the control unit prioritises domestic hot water.
The storage tank pump is enabled when the boiler temperature
(the
S4
probe) is above the minimum boiler temperature (nor-
mally 60°C); the storage tank pump is also enabled when the
S4
boiler flow probe detects a temperature above that of the
S3
probe plus a heat differential (normally 6°C).
Sensor legend:
S3: temperature sensor at the top of the storage tank
S4: flow temperature sensor of the boiler
S5: return temperature sensor of the boiler
ATTENTION:
In the case of a system with closed expan-
sion vessel, the installer must assemble a
minimum/maximum water pressure switch
and the safety heat exchanger.
PELLEXIA BOILER
EXPANSION
VESSEL
HEATING
SYSTEM PUMP 3
BOILER
PUMP 2
RECIRCULATION
PUMP 4
HEATING SYSTEM
DOMESTIC HOT WATER
PRODUCER