42
Bcm Parameters
code
Symbol
description
unit
min.
max.
Imp. fab.
803
Srv
enabled Services
16
27
483
rP
Gen: Temp. Max Differential
°K
0.0
50.0
34
hY
Burner hysteresis
°K
5.0
20.0
31
hl
ch#1: minimum Set-point
°c
20.0
40.0
39
hh
ch#1: maximum Set-point
°c
45.0
85.0
799
Ac
Input 0/10V
0
3
376
dI1
Programmable Input #1
0
2
322
Po
Pump: Post-circulation
min.
1
10
341
Pl
Pump: minimum control
V
0
10
313
Pr
Pump: maximum control
V
0
10
792
chP
ch: max. modulation
%
0
100
611
PoT
Gen: err. max. Parallel
°K
0
30
612
Pol
Gen: mod. max. Parallel
%
0
100
650
dl
dhW: minimum Set-point
°c
25.0
45.0
385
dh
dhW: maximum Set-point
50.0
65.0
360
dt
Heater Adjustment
0
15
656
drT
DHW: Temp. Requested Differential
°K
-20
20
657
drh
dhW: requested Temp. hysteresis
°K
1
20
310
dpT
dhW Pump: Postcirc.
sec.
5
600
660
dbT
dhW: Temp. maximum Boiler
°c
50.0
85.0
48
chSet
ch#1: Set-point
°c
20.0
85.0
64
chPo1
ch#1: Parallel Supply
0
1
346
fl
minimum modulation
%
0
100.0
600
mB
Burners: min. Inserted
1
8
616
BSt
Gen: Insertion Time
sec.
30
900
613
Brt
Gen: removal Time
sec.
30
900
336
hS
Temperature Gradient
°c/min
1
30
353
hP
ch PId: Proportional
°K
0
50
354
hI
ch PId: Integrative
°K
0
50
478
hd
ch PId: derivative
°K
0
50
816
mI
modbus Address
1
127
817
mT
modbus Time-out
sec.
0
240
896
Tu
°fahrenheit
0
1
309
St
Application code
0
1
368
VA1
Programmable relay #1
0
1
369
VA2
Programmable relay #2
0
1
771
PS
Water Pressure Sensor
0
1
768
lG
Sens. min. Gas Pressure
0
1
793
coc
chimney obstruction Sensor
0
2
622
fS
minimum flow Sensor
0
1
Содержание MODULEX EXT Series
Страница 1: ...e n G l I S h INsTALLATION AND MAINTENANCE INsTRUCTIONs 348 440 550 660 770 900 moduleX eXT...
Страница 25: ...25 Installation instructions E N G L I S H PAGE LEF T INTEN TION ALL Y BLANK...
Страница 30: ...30 PAGE LEF T INTEN TION ALL Y BLANK...
Страница 34: ...34 ON ON OFF 10V ON 10V Wilo Stratos modulating pump setting ext input enabling 0 10 V...
Страница 51: ...51 Installation instructions E N G L I S H PAGE LEF T INTEN TION ALL Y BLANK...