Instructions for the installer
INJECTORS – PRESSURES
SWEEPER MODE
The function is active for a time
of 15 min, after that the planned
parameters are restored.
MODULEX EXT: 100 - 150 - 200 - 250 - 300 - 350
Gas Type
Supply
pressure
Ø
Injectors
Diaphragm
Fan Speed
CO
2
levels
Starting
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FU
[Hz]
min
max
IG
Gas nat. (G20)
20
7
-
31
98
9,1
9,1
80
Gas nat. (G25)
25
9
-
31
98
9,1
9,1
80
Propan (G31)
37
7
-
30
91
10,8
10,8
80