Unical KONe R 18 Скачать руководство пользователя страница 41

41

Maintenance instructions

ENGLISH

4.6  -  ERROR CODES

The symbol flashes on the display monitor when the boiler detects an anomaly.
1) In the event of an anomaly that does not stop boiler operation, press key ‘‘D’’ to 

display the error code; in the event the boiler is in stand-by, the error code appears 

and remains fixed on the display.
2) In the event of an anomaly that causes boiler down time, the error code flashes 

directly on the display. 

Each fault is characterised by a priority level: if two faults are detected at the same 

time, the code with the highest priority is displayed. The fault codes are listed below:
F) Fault code displayed with code number:  

The display flashes alternating the F (FAULT - ANOMALY) with error code (eg 23).

( Num ) = 

see key Par. 2.2

SYMBOL

 

PRIO-

RITY

DESCRIPTION 

SOLUTIONS 

09

0

EXTERNAL PROBE

interrupted

Check the wiring, if needed 

replace the external probe

14

1

RETURN PROBE

Auxiliary 

(SRR)

 sensor inter-

rupted

Check the wiring, if needed re-

place the auxiliary sensor 

(22)

45

2

wATER OVERPRESSURE

detected if the H

2

O pressure 

Transducer is present with 

pressure > 2.5 bar; it is reset 

automatically when H

2

O pres-

sure < 2 bar

Wait for the values to return to 

default limits / 

Replace the Transducer 

30

3

SERVICE PARAMETERS 

Service parameters altered due 

to possible electromagnetic 

interferences.

Reset the altered parameters 

via  the  panel  and/or  regola

-

facile

21

4

POOR wATER CIRCULATION 

Poor circulation in primary 

circuit

Check pump operation 

(12) 

and speed, if there are any 

obstructions or system closure. 

17

5

FLAME CONTROL FRE-

QUENCY BEYOND LIMIT

Depends on the power supply 

mains (Frequency and voltage 

beyond default limits)

Wait for the values to return to 

the default limits 

15

6

wATER CIRCULATION IN-

SUFFICIENT

Primary circuit water circulation 

insufficient (∆t > 35° C)

Check pump operation 

(12)

 

and speed - remove any heat

-

ing system obstructions - clean 

the scaled domestic hot water 

exchanger

22

7

INCORRECT SENSOR PO-

SITIONING 

Flow and return 

sensors inverted

Check the wiring 

(21) (22)

24

8

SPEED OUT OF 

CONTROL

Alteration of the fan speed; the 

speed is not reached.

Check fan operation 

(18)

 and 

the connections

COD. REGO-

LA FACILE/

FAULT

HISTORY

Содержание KONe R 18

Страница 1: ...E N G L I S H INSTALLATION AND SERVICING MANUAL R 18 C 18 R 24 C 24 R 28 C 28 R 35 C 35...

Страница 2: ...It can be taken to a special recycling centre managed by the local authorities or to a dealer who offers this service Separate disposal of a domestic appliance avoids possible negative consequences fo...

Страница 3: ...ted from the control panel 33 4 3 Adaptation of the power to the heating system 37 4 3 1 GAC adjustment 38 4 4 Important notes 39 4 5 Wiring diagram 40 4 6 Error codes 41 3 INSTALLATION INSTRUCTIONS 1...

Страница 4: ...t was expressly designed Any other use is to be considered improper and therefore dangerous 1 1 general warnings The instruction booklet is an integral and essential part of the product and must be ke...

Страница 5: ...ser as well as other documents concerning the appliance inserted in the envelope inside the packaging The user must keep this documentation safe for future consultation Inform the user about the impor...

Страница 6: ...h affect the operating safety of the appliance Attention To tighten or loosen the screwed fittings use only appropriate fixed spanners Incompliant use and or inappropriate tools can cause damage e g w...

Страница 7: ...T max Max domestic hot water temperature C Electrical characteristics 21 Electrical power supply 22 Consumption 23 Protection rating D Countries of destination 24 Direct and indirect countries of dest...

Страница 8: ...fac es must be clean see system protection ACCESSO RIES sect in domestic price list This protection can intervene only if the electricity and gas supplies are connected If one of the two is not availa...

Страница 9: ...CATION OF THE MAIN COMPONENTS AND DIMENSIONS View from above View from below NOTE Further details in the section Technical Information on the boiler page of the www unicalag it website KONe 18 24 R KO...

Страница 10: ...10 View from above View from below KONe 28 35 R KONe 28 35 C 15 26 20 17 22 11 24 18 4 25 10 1 2 5 8 12 16 13 23 3 27 22 11 24 18 4 25 10 3 5 8 12 13 15 26 20 23 27...

Страница 11: ...14 Boiler drain valve 15 Filling valve 16 Diverter valve 17 Plate heat exchanger 18 FL FH VM Fan 19 AF AS PV Flue gas pressure switch 20 Safety valve 21 Automatic by pass 22 rb SRR Return temperature...

Страница 12: ...2 3 DIAGRAM OF FLOW RATE PRESSURE AVAILABLE FOR INSTALLATION Flow rate l h Flow rate l h Avaible Head m c a metres of water Avaible Head m c a metres of water MODULATING PUMP DIAGRAM OF FLOW RATE PRES...

Страница 13: ...nominal kW 17 23 27 32 Seasonal space heating energy efficiency s 93 92 93 93 Seasonal efficiency class in heating mode A A A A For CH only and combination boilers useful heat output Useful Heat Outpu...

Страница 14: ...5 0 5 Maximum domestic hot water circuit pressure bar 6 6 6 6 Domestic hot water specific flow rate t 30 C D l min 11 2 11 2 13 16 Production of D H W in continuous operation with t 45 K l min 7 4 7 4...

Страница 15: ...s dust and or if there are aggressive corrosive vapours present in the installation room the appliance must be protected suitably and must be able to operate independently from the air in the room Att...

Страница 16: ...ob jects due to failure to comply with the instruction above H P L As well as the appliance the packaging contains A DOCUMENTATION ENVELOPE System booklet User operating instructions booklet Instruct...

Страница 17: ...its weight The wall must not be made of flammable material KONe Since the temperature of the wall on which the boil er is installed and the temperature of the coaxial exhaust pipe do not exceed in no...

Страница 18: ...Horizontal exhaust and intake terminals directed outside via coaxial or double pipes C33x C33 TOTAL LENGTH LA intake L Exhaust COAXIAL 60 100 DOUBLE 80 FROM m TO m FROM m TO m 1 7 0 5 0 5 40 20A 20S C...

Страница 19: ...in the MT018 available on the website ATTENTION For the type of connection B23P the room follows the same installation rules for boilers with natural draught Please note these values relate to exhaus...

Страница 20: ...lue gas exhaust refer to the Technical Information section on the boiler page of the www unicalag it website It is recommended to only use original Unical exhaust pipes The supplier will have no contr...

Страница 21: ...2 Sc BOILER DRAIN S cond CONDENSATION DRAIN Rc FILLING VALVE Svs SAFETY VALVE DRAIN Provide a drain pipe with funnel and a trap that lead to a suitable drain in cor respondence of Svs This drainage m...

Страница 22: ...his operation must be performed carefully respect ing the following phases open the radiator vent valves and make sure the automatic valve is working properly in the boiler open the filling tap gradua...

Страница 23: ...nals TA1 OT after having removed the jumper ON OFF room thermostat connection RT OT A3 4 32 1 6 5 SE TA 1 OT TA 2 WH WH Y Y BK BK TA ON OFF Danger Only a qualified technician may per form the electric...

Страница 24: ...oiler installation requires electric al con nection to the mains power supply This connection must be made up to standard as required the regulations in force Remember that a bipolar switch must be ns...

Страница 25: ...oes the gas to be used correspond to the boiler calibration gas otherwise perform the boiler conversion in order to use the gas available see section 4 3 this operation must be carried out by technica...

Страница 26: ...ternates between SP and the flow temper ature the boiler operates at maximum output Perform combustion analyses 4 DISABLING The calibration function stays active for 15 min utes To disable the CALIBRA...

Страница 27: ...in steady state conditions see par 3 11 1 3 11 2 Positioning the probes 3 12 ADJUSTING THE BURNER KONe R 18 KONe C 18 Type of Gas Effective Ouput kW Heating Thermal kW Capacity Supply Press mbar Fan s...

Страница 28: ...5 0 43 kg h 2 17 kg h A P G230 4 3 27 2 4 4 28 0 20 9 6 9 0 0 34 m h 2 18 m h 0 2 Acceptable range for G20 G25 0 2 R Acceptable range for G31 G230 If the CO2 value detected is beyond the recommended r...

Страница 29: ...tart up output xx Minimum output 0 EDITING THE VALUE When the flame flashes correct the value with keys C or C VALUES FROM TO DEFAULT 3 3 0 corresponds to about 0 5 points of CO2 SELECTION Select the...

Страница 30: ...EM Act on parameter HP par 4 2 SE parameters list to achieve the value corresponding to the desired output The user is NOT authorised to activate the func tion described below E g KONe 24 to decrease...

Страница 31: ...01 Relation between the temperature C and the nom resistance Ohm of the heating probe SR and of the domestic hot water probe SS Example At 25 C the nominal resistance is 10067 Ohm At 90 C the nominal...

Страница 32: ...ater pressure is below 0 4 bar Without request close the shut off valves of the heating circuit open the drain valve to make the water pressure decrease Be fore pressurising again check the pressure o...

Страница 33: ...e heat ing sensor is faulty External temperature if there is no external probe or if it is faulty Domestic hot water temperature if there is no sensor or if it is faulty Return temperature if there is...

Страница 34: ...of the position 01 in which the error is stored DISPLAY Press the key B to display the sequence of faults between 01 12 EDIT VALUE RESET Press the key D for over 5 seconds to reset the whole errors lo...

Страница 35: ...10 0 30 External probe on Regolafacile 0 20 C 30 10 C default 10 0 5 30 Night reduction 0 T A default 5 30 night reduction 0 1 Domestic hot water pre heat function 0 Not active default 1 Active 0 100...

Страница 36: ...mum fan speed 10 750 rpmx100 0 199 Maximum fan speed 10 5000 r pmx100 1 20 Heating control proportional 1 20 Heating control integrative 1 20 Heating control derivative 1 20 Domestic hot water control...

Страница 37: ...ion of the tank contact the LPG supplier or a person qualified in compliance with law If the tank has not been profession 4 3 ADAPTATION TO THE USE OF OTHER GAS Gas Conversion The boilers are produced...

Страница 38: ...StArt scrolls on the display the function is active when the symbols flash Note After the ignition sequence which can also take place after a few attempts the boiler performs the calibration which co...

Страница 39: ...board MODULATION BOARD A universal board B memory board The memory board is programmed by de fault for METHANE gas operation In the event of LPG operation the GT pa rameter must be edited Factory par...

Страница 40: ...1 76 5 TLC TL SRR G G WH WH WH BL A6 VI WH R Mod On Off VG EV2 EV1 OR A3 4 32 1 6 5 SE BK TA 1 OT TA 2 WH WH Y Y BK BK MDV PK WSC YONOS GND WH SL BK CASING 4 5 WIRING DIAGRAM Practical connection boar...

Страница 41: ...y sensor 22 45 2 WATER OVERPRESSURE detected if the H2 O pressure Transducer is present with pressure 2 5 bar it is reset automatically when H2 O pres sure 2 bar Wait for the values to return to defau...

Страница 42: ...f the sensor see table Res Temp Par 4 or its connections 12 15 HEATING SENSOR 11 Heating sensor fault Check the efficiency of the sensor see table Res Temp Par 4 or its connections 38 16 FACTORY PARAM...

Страница 43: ...circuit problems Gas Valve Check the Gas Valve connec tions Replace the Gas Valve 3 Replace the Modulation Board BLOCK 32 Gas Valve opening time beyond limit time Check the parts that generate the hea...

Страница 44: ...ght to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 6...

Отзывы: