13
Installation info
2.2.3 - ASSEMBLING THE BOILER
Before connecting the boiler to the D.H.W.
and heating system pipes, carefully clean
the pipes to remove all traces of metal re-
sulting from processing and welding opera-
tions as well as any oil and grease which
could damage the boiler or jeopardize its
operation.
To install the boiler:
-
Fix with tape the paper template to the
wall
;
-
make two Ø 12 holes in the wall and in-
sert the dovels;
-
position the junction points for the con-
nect-ion of the gas supply pipe, cold wa-
ter supply pipe, D.H.W. outlet, CH flow
and return in the positions shown by the
Do not use solvents which
could damage the
components.
Unical
refuses all liability for
injury to persons and animals
or damage to property resul-
ting from non-observance of
the above.
template. ;
-
fit the boiler onto the support hooks;
-
connect the boiler to the gas pipe,
domestic cold and hot water pipes, CH
flow and return pipes.
-
connect to electrical supply
2.2.4 - VENTILATION
The boiler must be installed in a suitable room
according to the rules in force and particu-
larly:
FORCED DRAUGHT ROOM SEALED BOI-
LER
(TYPE C12 - C32 - C42 - C52 - C62 - C82)
The
EVE 05 CTFS 24 F
- EVE 05 RTFS 24 -
EVE 05 CTFS 24
are forced draught, room
seal-ed boilers; so they do not need particu-
lar ventilation openings for the combustion
air, in the room in which they are installed.
FORCED DRAUGHT, OPEN FLUE BOILER
(TYPE B22)
If the
EVE 05 CTFS 26 F
is installed in a room
according to the chimney configuration on
type
B22,
the same ventilation requirements
established in paragraphs
Direct ventila-
tion
and
Indirect ventilation
apply.
Direct ventilation:
-
The room has to have a ventilation open-
ing of, at least,
6 cm² /kW of installed input (see input
table on par. 2.7) and, in no case, lower
than 100 cm² and made directly onto an
external wall.
-
The opening has to be as close as possi-
ble to the floor.
-
It should not be possible to close it and it
should be protected with a grate not re-
ducing its usefull ventilation section.
-
A correct ventilation can be optained also
through the addition of more openings,
provided the addition of the different sec-
tions is not less than that really needed.
-
In case it is not possible to make a venti-
lation opening close to the floor, it will be
necessary to increase its usefull section
of at least 50%.
-
If an open fire is present in the same room
it needs an indipendent air supply, other-
wise the installation of a type B appliance
is not permitted.
-
If in the room there are other devices
which need air for their operation (e.g. a
wall exhauster) the section of the venti-
lation opening has to be the properly si-
zed.
Indirect ventilation
In case it is not possible to make a room
ventilation opening on an external wall, it is
possible to have an indirect ventilation, suc-
ting the air from an adjacent room, making
an
opening in the lowest part of a door.
This solution is possible only if:
-
The adjacent room is not a bed room
-
The adjacent room is not a common part
of the building and is not a room with fire
danger (e.g. a fuel deposit, a garage, etc..)