background image

20

Installation info

2.2.12 -

CONNECTION TO THE  GAS
MAINS

The supply pipe must have a section which is
the same as or greater than the one used in
the boiler.
Comply with the applicable local installation
requirements which shall be considered as
having been incorporated in full in this ma-
nual.
Before opening the internal gas supply system;
i.e. before connecting the gas meter, all seals
must be checked.
If any part of the system is concealed the seals
must be checked before the pipes are cove-
red.
The seal test must be conducted using air or
nitrogen at a pressure of at least 100 mbar.
The commissioning of the boiler also inclu-
des the following operations and checks:
-

Opening of the gas gate valve and venting

2.2.13 - HYDRAULIC CONNECTION

Before installing the boiler we recommend that
the system be cleaned to remove any impuri-
ties which could originate from components
and which could risk damaging the circulating
pump and heat exchanger.

Note: The use of solvents could damage

the components of the heating cir-
cuit.

PRELIMINARY OPERATIONS:

Act on the coupled spring (located in the lower
part) and remove the two screws (located in
the upper part) in order to remove the casing.

fig. 21

of the air contained in the piping and ap-
pliances, proceding appliance by applian-
ce

-

Check, with the gate valve of all the ap-
pliance Off, that there are no gas leaks.
During the 2

nd

 quarter of a hour from the

beginning of the test no pressure reduc-
tion is to be detected on the gas pressure

Move the control panel in the high position for
the hydraulic connection. Remove the three
screws 

"A"

 fixing the panel and then place

the panel in correspondence to the low holes

"B"

 and fix the panel.

After having carried out the connections, re-
store the panel's normal position.

HEATING

The heating flow and return must be connected
to the relevant ¾” connections of the boiler 

M

and 

R

 (see fig. 7).

When determining the size of the heating cir-
cuit pipes it is essential to bear in mind the
pressure losses induced by radiators, any ther-
mostatic valves, radiator cut-off valves and
the configuration of the system.
In the boiler, onto a bass group positioned,
between the flow and return an automatic by-
pass device is fitted (about a differential val-
ve with a flow rate of about 150 l/h) which gua-

fig. 22

A

B

C

D

To OPEN  the
By-pass
rotate the screw
anti-clockwise

To CLOSE the
By-pass
rotate the
screw
clockwise

Note:The control panel can be mo-
ved in two positions beyond the nor-
mal position 

‘’D’’

, that is to say high

and low position, in order to make
the maintenance operations easy.

rantees always minimum flow rate throught
the heat exchanger, also in the case, for in-
stance, that all the thermostatic valves fitted
on the radiators, are closed. It is possible to
adjust the by-pass by acting onto the adju-
sting screw (see fig. 21)
We recommend that the discharge of the sa-
fety valve mounted in the boiler be conveyed
into the sewer.

If this precaution is not taken, activation of
the safety valve may result in flooding of the
room where the boiler is installed.

UNICAL shall not be held responsible for da-
mage caused by non-observance of this tech-
nical precaution.

D.H.W.

Outlet and inlet of D.H.W. must be connected
to the relevant ½” connections of the boiler 

C

and 

F

 (see fig. 7).

The hardness of the supply water affects the
frequency of the cleaning of the heat exchan-
ger.

gauge. If gas leaks have to be found, use
only water soap solution or any other spe-
cific gas leak detector which can be avai-
lable on the market. Never look for gas le-
aks using a nacked flame.

While connecting gas inlet pipe of the boiler to the pipe coming from
gas network, it is MANDATORY to insert a TIGHT GASKET, whose
dimensions and material must be adequate. Connection is NOT sui-
table for hemp, teflon strip or similar materials

AVVERTENZA!

Содержание EVE 05 CTFS 24 F

Страница 1: ...00331967 1a edition 02 2004 IVEN 04 UK RTN 24 RTFS 24 RTFS 28 CTN 24 F CTFS 24 F CTFS 28 F INSTALLATION USE AND MAINTENANCE ...

Страница 2: ...airs to the boiler Non observance of the above requirement may jeopardize the safety of the boilers and expose people animals and property to danger To guarantee efficiency and correct functioning of the equipment it is legally binding to service the boilers once a year according to the schedule indicated in the relative section of this manual In the event of long periods of inactivity of the boil...

Страница 3: ...minal Output 10 Pcond Condensing Nominal Output only for condensing boiler 11 D Specific flow rate EN 625 12 Qn Nominal heat input 13 Qnw Nominal heat input for D H W system if there are different out puts between the C H and D H W circuits 14 NOx NOx Class 15 PMS Max pressure C H system 16 T max Max Temperature C H system 17 PMW Max pressure D H W system 18 T max Temperature D H W system 19 Adjus...

Страница 4: ...boilers pag 14 2 2 8 Smoke evacuation Ø80 air suction flange pag 15 2 2 9 Discharge of flue gas into coaxial ducts with a diameter of 100 60 mm Type A accessories pag 16 2 2 10 Flue gas discharge and air suction with separate pipes with 80 mm diameter pag 17 2 2 11 Measurements of combustion efficiency pag 16 2 2 12 Connection to the gas mains pag 20 2 2 13 Hydraulic connection pag 20 2 2 14 Arran...

Страница 5: ...odulation Minimum output control Electronic control of ignition ramp Anti freeze function Pump anti jamming function Pump over run function High limit thermostat 95 C Three speed circulating pump Expansion vessel Automatic air vent C H system water filling valve except Fren ch Belgium and England version Safety pressure switch for low water level Priority flow switch for D H W Tap water flow rate ...

Страница 6: ... Circulating pump 18 D H W flow restrictor 10 12 l min 19 Flow switch 20 Cold water filter 21 By pass M C H system flow C D H W outlet G Gas inlet F D C W inlet R C H system return 1 Heating circuit safety valve 2 Minimum water pressure switch 3 D H W temperature sensor 4 Expansion vessel 5 Gas valve 6 Burner nozzles 7 Expansion vessel filling valve 8 Ignition electrode 9 Bithermal heat exchanger ...

Страница 7: ...ic air vent 15 Circulating pump 16 Filling valve except French Belgium and England version 17 By pass M C H system flow G Gas inlet R C H system return 1 Heating circuit safety valve 2 Low water level pressure switch 3 Expansion vessel 4 Gas valve 5 Burner nozzles 6 Expansion vessel filling valve 7 Ionisation electrode 8 Heat exchanger 9 Room sealed combustion chamber 10 Flue gas extractor fan 11 ...

Страница 8: ... 87 43 87 32 2 93 2 86 8 1 76 3 19 87 7 17 5 17 6 60 86 2 65 7 9 163 2 13 2 6 8 0 256 1 4 OPERATING DATA Nominal output Minimum output Actual water efficiency at full load 100 Min required water efficiency at full load 100 Actual water efficiency at part load 30 Min required water efficiency at part load 30 Stars No off According EEC Directive 92 42 Combustion efficiency at nominal load 100 Combus...

Страница 9: ...as conduits and fittings must only be carried out by a registered service provider The system must be cleaned and serviced once a year This includes an inspection 900 495 390 Keep the packaging material cardboard box plastic strips plastic bag etc out of the rea ch of children as it represents a choking and suffocation ha zard In addition to the boiler packaging contains a bag with installation us...

Страница 10: ...he boiler above applian ces which might affect operation when in use cookers which produce greasy ste am washing machines etc avoid installing natural draught boilers in corrosive or very dusty atmospheres such as hairdressers laundrettes etc as the life of the boiler components could be si gnificantly shortened L M C H system flow C D H W outlet G Gas F Cold water inlet R C H system return S Safe...

Страница 11: ...5 FLUE GAS DISCHARGE SYSTEM NATURAL DRAUGHT OPEN FLUE BOILERS Connection to the chimney A good chimney is very important for the cor rect functioning of the boiler it must therefore conform with the following requirements it must be made from waterproof material and be resistant at the temperature of the flue gas and relative condensate it must have sufficient mechanical stren gth and low thermal ...

Страница 12: ...er minal will be fixed must protrude from the wall of the building for a length of at least twice the diameter of the duct the draught terminal must overlap the con nection to the boiler by at least 1 5 m see fig 8 DIMENSIONALS FOR CONNECTING FLUE GAS DUCT WARNING The boiler is fitted with an automatic safety reset device as protection against spillage of combustion products inside the building If...

Страница 13: ... including two ducts one for the suction of com bustion air and the other for the exhaust of the combustion products through coaxial or dual ducts The chimney must comply with rele vant applicable law provisions C52 Boiler with separate combustion air suction and combustion product exhaust ducts These ducts can discharge into are as with different pressure The dual ducts must not be located on two...

Страница 14: ...r of the building I 300 From the ground or from another floor L 2500 Between two vertical terminals M 1500 Between two horizontal terminals N 1000 From a facing front surface without opening or teminals within a radius of 3 mt from smoke outlet point O 2000 As above but with openings or terminals within a radius of 3 mt from smoke outlet point P 3000 NOTES 1 Terminals below a practicable balcony s...

Страница 15: ...e pipe of Ø80 mm dia is 20 m for IVEN 04 RTFS 24 e IVEN 04 CTFS 24 F and 25 m for IVEN 04 RTFS 24 e IVEN 04 CTFS 28 F included a wide radium curve and one smoke terminal For this type of installation the chim ney has to serve just one boiler i e the boiler must have its indipendent smo ke duct fig 11 fig 12 Diaphragm Ø 44 mm Fitting of the diaphragm Ø44 WARNING For the installation where there is ...

Страница 16: ...reduced by 1 metre The diaphragm Ø 44 supplied with the boi ler must be inserted in the flue gas exhaust pipe as shown in figure 13 for installa tions with horizontal coaxial pipe up to 1 m and with vertical coaxial pipe up to 2 m fig 13 VERTICAL FLUE DUCT WITH COAXIAL DUCT Ø 80 125 Tipo C32 The minimum length of vertical co axial ducts is 1 2 metres The maximum allowable length of vertical coaxia...

Страница 17: ...pe see fig 16 WARNING In case the flue duct has to cross walls or floors or if it is easily reachable it is ne cessary to foresee a convenient insulation of such a duct The flue duct during the operation of the boiler can reach tempera tures higher than 120 C fig 16 DIMENSIONS FOR CONNECTING TO COAXIAL FLUE GAS DUCTS Up to P 20 Pa Rubber foam gasket Diaphragm Ø 44 IMPORTANT Flue gas pressure switc...

Страница 18: ...ARICO CHE DI ASPIRAZIO NE Ø 80 DIMENSIONS FOR CONNECTING THE AIR INTAKE AND THE FLUE GAS DISCHARGE WITH DUAL DUCTS Example N 1 fig 18 Primary air suction from perimeter wall and flue gas discharge on roof Maximum allowable pressure loss 50 Pa IVEN 04 TFS 24 60 Pa IVEN 04 TFS 28 85 85 245 Ø 80 85 160 245 85 85 85 85 ...

Страница 19: ...owing measurements must be made the combustion air temperature measured in hole 2 see fig 20 the flue gas temperature and CO2 mea sured in hole 1 see fig 20 Make these measurements with the boiler running in a steady state condition 135 45 C Sonda analizzatore 2 1 250 min Sonda analizzatore NB These values refer to di scharges through original UNI CAL non flexible and smooth ducts Example of check...

Страница 20: ... must be connected to the relevant connections of the boiler M and R see fig 7 When determining the size of the heating cir cuit pipes it is essential to bear in mind the pressure losses induced by radiators any ther mostatic valves radiator cut off valves and the configuration of the system In the boiler onto a bass group positioned between the flow and return an automatic by pass device is fitte...

Страница 21: ... 0 0 8 0 6 0 4 0 2 0 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 V1 V2 V3 6 2 6 0 5 8 5 6 5 4 5 2 5 0 4 8 4 6 4 4 4 2 4 0 3 8 3 6 3 4 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 0 8 0 6 0 4 0 2 0 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 V1 V2 V3 DIAGRAM FLOW RATE MANOMETRIC HE...

Страница 22: ...ce to the upper holes C and fix the panel If the boiler is already installed go on with the emptying of the boiler Relate for the discharge connection of the safety valve a plastic pipe with hose adap ter whose length can reach a drain Remove the components from 1 to 6 of fig 25 A and assemble the components from 1 to 6 contained in the kit and shown in the fig 25 B also remove the minimum pres su...

Страница 23: ...The female faston of the earth wire must be introduced in the male faston GND1 Connection of the ON OFF room thermo stat RT Approach the connector Y1 Remove the existing jumper and connect on its place the room thermostat cable passing it through one of the cable clam ps avaible Connection of the room modulating ther mostat OT Approach the connector Y1 Connect the room thermostat cable pas sing it...

Страница 24: ... 2 1 4 N L N C N A C V P V A 5 5 4 3 2 1 5 4 3 2 1 R T N 2 4 C T N 2 4 F R T F 2 4 R T F 2 8 C T F S 2 4 F C T F S 2 8 F Y 1 6 A 2 S S 5 4 3 2 1 6 IG A 7 T A E R IV TEFLO N W H ITE F S 1 TEFLO N RED IGNITION TRASFORMER SUPPL Y L1 L2 V G PE 6 5 4 3 2 1 A 6 E A C C 2 TE FLO N RED E A C C 1 1 2 Y 2 N L POWER SUPPL Y 230 V 50 Hz 6 5 4 3 2 1 YELLO W G REEN BL U E GR EEN W HITE R ED BRO W N P 7 L1 N 6 5...

Страница 25: ... than 0 8 1bar if this value is lower use the water filling tap on the boiler to adjust the pres sure This must be performed when the system is cold Use the temperature and pressure gau ge on the boiler to read the pressure value of the circuit NB After a given period of inactivity and without electrical supply the pump could be blocked Before switching on the boiler it is important to restart the...

Страница 26: ... sweeper switch H fig 35 on the panel board in this way the boiler will operate at maximum output when the burner is ignited check that the MAXIMUM pressure value corresponds to that indicated on the table NOZZLES PRESSURES if it does not correct it by removing the screw plug A fig 28 and by turning screw B fig 29 CLOCKWISE to increase and ANTICLOCKWISE to de crease 2 Minimum output adjustment Dep...

Страница 27: ...valve see table INJECTORS PRESSU RES and adjust the pressure of the bur ner as indicated in section ADJUSTING THEBURNER check that the burner is functioning pro perly check that there are no gas leaks tighten the plug A fig 28 of the max pressure adjustment screw when the conversion is completed fill in label supplied with the kit with the informa tion required and stick it onto the boiler alongsi...

Страница 28: ...urner as previously shown in fig 30 switch on the boi ler in heating mode and proceed as follows Wait about 50 sec to allow the burner pres sure to reach the standard operating va lue Check the pressure value and through the diagrams of fig 34 estimate if the boiler output is correct for heating needs If not act on the adjuster 1 CH POWER fig 31 on the panel board and turn it to reach the desired ...

Страница 29: ... is in short circuit with earth d The input at the minimum rate is not enough e The PCB does not detected the flame a The chimney draught is not correct b The H L thermostat has cut in An over heating of the heat exchanger oc currend a The flue gas pressure switch is faulty b The silicon pipes are disconnected or bro ken c There is insufficient combustion air suction or flue gas discharge d The fa...

Страница 30: ...ed the thermostatic val ves are closed or the system gate valves are closed b The circulation pump is blocked or is faulty a The boiler may be frozen 2 10 7 b The D H W sensor is faulty 2 10 6 c One or both temperature sensors are discon nected or faulty 2 10 5 or 2 10 6 d There is insufficient water pressure in the C H system 2 10 2 e The minimum water pressure switch is disconnected f The The mi...

Страница 31: ...TION priority 4 Description False flame has been detected at ignition start up 2 10 5 CH TEMPERATURE SENSOR priority 3 Description CH sensor interruption or short circuit 2 10 6 DHW TEMPERATURE SENSOR priority 2 Description DHW sensor interruption or short circuit This failure is not de tected if DHW mode is disabled 2 10 7 FROST priority 1 Description Freezing of the heat exchanger is detected if...

Страница 32: ...ways gives priority to the production of domestic hot water if it is requested and controls the temperature of the water of the heating circuit from a minimum of 45 C to a maxi mum of 78 C D H W temperature control C Only for IVEN CTN CTFS If the knob is set within the range indicated by the arrow on the illustration it means is possibile to adjust the dome stic hot water temperature The temperatu...

Страница 33: ...ge tank is not fitted the knob C must be positioned and must stay onto the symbol Power ON lamp Green D When this lamp is illumina ted it indicates that the boiler is connected to the mains sup ply CH request lamp Green E If this lamp is illuminated it indicates that there is a hea ture of the H L thermostat 95 C to drop at least of 25 K Chimney sweeper push button H This button allows the startin...

Страница 34: ...in lockout position and the red warning lamp G lights In this case proceed as follows Ascertain that the gas cock is open and that there is gas in the gas pipe try to ignite a gas cooker If so wait one minute before resetting the boiler by depressing the L push button If the boiler does not start and goes into lockout position after three times ask for a service or for a qualified technician If th...

Страница 35: ...35 ...

Страница 36: ... ad errori di trascrizione o di stampa Si riserva altresìil diritto di apportare ai propri prodotti quelle modifiche che riterrà necessarie o utili senza pregiudicarne le caratteristiche essenziali AG S P A 46033 casteldario mantova italia tel 0376 57001 r a telefax 0376 660556 ...

Отзывы: