20
Instructions for the installer
KIT5740C
KIT5820C
KIT5810C
KIT5800C
303,5
121
12,5
Type C33
The maximum allowable length of the vertical concentric pi-
pes is of
6 metres
including the terminal (Ø 80/125). For each
elbow added the maximum length permitted has to be redu-
ced by 1 metre.
Type C13
The minimum allowable length of the horizontal concentric pi-
pes is of
0,75 metres.
The maximum allowable length of the horizontal concentric
pipes is of
3,5 metres
. For each elbow added the maximum
length permitted has to be reduced by 1 metre.
FLUE OUTLETS WITH CONCENTRIC DUCTS Ø 60/100 mm
Important: the outlet/inlet flue has to
have a minimum inclination of 3%
towards the top in the outlet direction,
so as to enable the collection of any
condensate formed in the boiler.
slope 3%