36
PUMP OVERRUN - ( 2 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
1
min
10 min
5
min
Pump overrun time after DHw operation - ( 3 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
0 sec.
60 sec.
30 sec
CAPACITY TO FLOw-RATE RATIO - ( 5 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
20
100
99
DHw: ENABLE THE TEMPERATURE SENSOR - ( 7 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
0
1
0
MODULATING PUMP MINIMUM MOD. LEVEL - ( 6 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
ALKON 34,5 - 50
ALKON 70
0 %
99 %
19
25
RELAY PUMP BOILER COLLECTOR - ( 4 )
Continue with the modification of parameters by pressing
the -
(MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM
TO
DEFAULT
0
1
0