1.7 - wATER TREATMENT
The treatment of the supply water allows to
prevent inconveniences and maintain the
functionality and efficiency of the generator
over time.
The ideal water pH in heating systems must
be within:
To minimise corrosion, it is crucial to use
a corrosion inhibitor; in order for it to work
properly, the metal surfaces must be clean.
(see system protection ACCEssORIEs sect.
in domestic price list)
ATTENTION (*) see general warnings 1.1
The heating only models are NOT suitable
for the production of water for human con-
sumption according to Ministerial Decree
D.M. 174/2004.
ATTENTION!
ANY DAMAGE TO THE BOILER CAUsED BY
THE FORMATION OF FOULING OR BY COR-
ROsIvE wATER wILL NOT BE COvERED BY
THE wARRANTY.
1.8 - BOILER ANTIFREEZE
PROTECTION
Enabled by default
VALUE
MIN
MAX
PH
6,5
8
Hardness [°fr]
9
15
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler
indicated at page 2.
This protection can intervene only if the
electricity and gas supplies are connected.
If one of the two is not available and upon reset
30 (sMG)
a temperature between 2 ÷ 5°C is
detected, the appliance will behave as described
in tab.
pos 2.
The heating system can be protected effectively
from frost by using antifreeze products with
inhibitor for heating systems (specific for
multidmetal)
Do not use car engine antifreeze products as
they could damage the water gaskets.
P
O
s
ANTIFREEZE FUNCTION
Power supplies
30 - sMG
(*)
Status function
antifreeze
Actions
Electric
Gas
1
ON
ON
< 7 °C
ON
- Burner and Pump ON until T > 15°C
2
ON
OFF
< 2 ÷ 5 °C
OFF
FAULT CODE 16
(see par. 4.6 ERROR CODES).
Ignition disabled.
OFF
ON
OFF
Ignition disabled.
OFF
OFF
OFF
Ignition disabled.
(*) Sensor 30 par. 2.2
For outdoor installations, in partially protected places, you must use the additional heater
kit (optional) for antifreeze siphon cap.
Содержание ALKON 115 EXT
Страница 10: ...10 2 3 DIMENSIONI VISTA FRONTALE VISTA DA SOTTO VISTA SUPERIORE VISTA LATERALE...
Страница 19: ...19 Istruzioni per l installazione I TA L I A N O Adattatori 120 opzionali per sistemi sdoppiati...
Страница 35: ...35 Istruzioni per l installazione I TA L I A N O QUESTA PAGINA E LASCIATA INTENZIONALMENTE IN BIANCO...
Страница 36: ...36 4 5 SCHEMA ELETTRICO DI COLLEGAMENTO PRATICO...
Страница 48: ...10 2 3 DIMENSIONS Front view View from below View from above Side view...
Страница 57: ...19 E N G L I S H Installation Instructions 120 optional adapters for twin flue systems...
Страница 62: ...24 Control panel remotely NOTE For more information See Technical Info from site indicated at pag 2...
Страница 73: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 74: ...36 4 5 WIRING DIAGRAM...
Страница 78: ...40...
Страница 79: ...41...