background image

ENGLISH  

OPERATING MANUAL FOR 

 

DALI 3-PHASE TRACK 

 

  

 

Read  this  short  manual  carefully  and  keep  it  accessible  for  further 

reference! 

 

  

 

 

SAFETY MESSAGES

 

 

  

 

Disregard  of  the  safety  messages  may  lead  to  danger  of  life,  burning  or 

fire!

 

 

•  Installation, mounting or works on the electrical connection may only be 

carried out by an approved electrician.  

•  The product may not be modified or converted.  
•  Do not hang or fasten anything on the product, especially no decoration.  
•  Do not cover the product - provide free air circulation.  
•  The rail and the individual components of the system may not be used with 

components of other rail systems.  

•  Do not direct the spots on each other.  
•  Do not direct the spots on the track or the transformer.  
•  All open rail ends must be equipped with end caps.  
•  In case of a malfunction you may NOT touch the product or operate it 

further. Disconnect the product from the power supply by an external switch 
or by the fuse.  
A malfunction exists when:  
•  visible damages appear.  
•  the product does not work properly (e.g. flickering).  
•  smoke, steam or crackling sounds appear.  
•  smell of burning is recognisable.  
•  an overheating is recognisable (e.g. by discolouration of adjacent 

surfaces).  

Operate the product only after maintenance and examination by an 
approved electrician!

 

 

•  This product is not intended to be used by children. Ensure that children 

do not suffer any harm e.g. by burns from hot surfaces or by electrical 
shock.  

Additional safety messages are indicated by this symbol: 

 . 

 

  

 

USE AS DIRECTED  

  

 

This product serves exclusively lighting purposes and may:  

•  only be used with a voltage of 220-250V ~50Hz.  
•  only be installed according to safety class I (one).  
•  only be operated when firmly mounted on a stable, even and tilt-fixed 

surface.  

•  only be operated on normally or not flammable surfaces.  
•  only be used in dry condition,   not in damp or dirt-endangered rooms.  
•  not in areas of high air humidity.  
•  not be exposed to strong mechanical loads or to strong contamination.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATION  

  

 

 It is the responsibilty of the user to ensure the electrical and thermal 

compatibility between the rail system and the luminaires connected to it.  

  

 

 The safety of the complete system is only assured permanentely, when all 

connection between electrical components are seated tightly. Check all 
electrical connections on a regular basis(every three months). Tighten these if 
necessary(turn off power before!).  

  

 

MAINTENANCE AND CARE

 

 

  

 

Care 

 

 

Disconnect the product from the power supply and let it cool down, before 

you clean the product.  

  Clean  the  product  on  a  regular  basis  using  a  slightly  moistened,  soft  and 

flufffree  cloth.  Please  also  note  additional  supplied  notes  on  maintanance 
and care.  

  

 

STORAGE AND DISPOSAL

 

 

  

 

Storage 

 

•  The product must be stored in a dry and clean environment. Do not strain 

the product mechanically during storage.  

 After a damp or soiling storage the product may only be installed after 

checking its condition by an approved electrician.  

Disposal 

(European Union) 

  

•  Do not dispose the product with the regular household waste! Products 

marked with this sign must be disposed according to the directive (WEEE, 
2012/19) on electrical and electronic devices at local collection points for 
such devices!  

  

 

INSTALLATION 

(only by an approved electrician)

 

 

  

 

 

Switch off the mains or respectively the connection lead before doing any 

works!  

 

Use only parts, which are supplied with the product or are described as 

accessories!  

 

Inspect the product for loose parts inside the housing. When there are 

loose parts inside the housing and these are not explicitly described the 
product may not be installed or operated. 

 

 

 

Use the supplied fastening material only when it is suited for the 

installation background. If this is not the case use only fastening material 
suiting the installation background.

 

 

  

 

Unpacking 

 

•  Carefully take the product out of the packaging removing any transport 

safeguards.  

•  Before disposal of the packaging material make sure that all components of 

the product are removed.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation place 

 

•  The product is solely suited for installation on the ceiling.  

  

 

Installation steps 

(read completely before installation)

 

 The rail may 

be cut using a regular metal saw. Note a straight cut!  

•  Install the rail as shown in the figure.  
•  Electrical Connection  
•  The product must be able to be separated by an all pole separation from 

the current supply.  

•  For electric connection attach the black or brown wires (live conductor) of 

the connection lead with the clamp L1 or L2 or L3 and the blue wire (neutral 
conductor) of the connection lead with the clamp N. The green-yellow wire 
(protective conductor) of the connection lead has to be tightly screwed into 

the earth clamp 

 of the product.  

DA+ and DA- for DALI. 

•  Close the open rail ends by applying end caps.  

 Check if the product functions properly and is securely fixed! 

 

  

 

© 08.11.2018   
Technical Details are subject to change.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание 141-003-00 Series

Страница 1: ...41 002 X01 141 005 00X 141 006 00X 141 007 00X 141 008 00X 141 009 00X 141 010 00X 141 015 00X 141 013 00X 141 014 00X 141 015 00X 141 012 00X 141 016 00X 141 017 00X 141 018 00X 141 019 00X 141 021 0...

Страница 2: ...Technische nderungen vorbehalten 08 11 2018 Unex Dakota AG Unex Dakota AG Fl elastrasse 12 CH 8048 Z rich Schweiz Tel 41 44 404 22 22...

Страница 3: ...Technische nderungen vorbehalten 08 11 2018 Unex Dakota AG Unex Dakota AG Fl elastrasse 12 CH 8048 Z rich Schweiz Tel 41 44 404 22 22 Adapter 141 027 00X PRO D680...

Страница 4: ...st dauerhaft nur dann gew hrleistet wenn alle Verbindungen zwischen den elektrischen Komponenten festen Sitz haben berpr fen Sie regelm ig ca alle drei Monate die elektrischen Verbindungen und ziehen...

Страница 5: ...onths Tighten these if necessary turn off power before MAINTENANCE AND CARE Care Disconnect the product from the power supply and let it cool down before you clean the product Clean the product on a r...

Страница 6: ...le si toutes les connexions entre les composants lectriques disposent d un maintien solide Contr lez r guli rement environ tous les trois mois les connexions lectriques et veuillez le resserrer en cas...

Страница 7: ...rici e se opportuno tirarli togliere prima la tensione all impianto MANUTENZIONE E ASSISTENZA Assistenza Scollegare il prodotto dalla corrente e lasciarlo raffreddare prima di eseguire lavori di puliz...