Ultravation UVMATRIX SI Seris Скачать руководство пользователя страница 2

 

 

www.ultravation.com 

 
 
 
 

 

 

NOTICE: 

Ultravation coil irradiation equipment is designed for installation in HVAC (heating, ventilation, and air conditioning) systems. 
It is recommended a trained technician install this unit. Installation near an A/C coil will help keep the coil free of microbial 
growth and eliminate odors associated with such growth. The UVMatrix

TM

 SI is designed to operate constantly and should 

not

 cycle on and off with a blower motor. The preferred location to install the unit is on the supply side of the evaporator coil 

exiting the HVAC system. Placement between 4-24 inches to the coil surface assures less untreated area as shown below:   

 
 
 
 
 
 
 
 
 
 
 

Shipping and Packaging List:                                                                    

 

2 Electrical Housing 

 

2 Expandable Poles 

 

4 ¼x20 Phillips head pole screws  

 

UVC Warning Label 

 

Warranty Card 

 

Center Lamp Support 

 

Appropriate Quantity of Lamps 

 

Appropriate Quantity retaining nuts 

 

1 Grommet per retaining nut 

 

– “L” Brackets for optional mounting 

 

– ¾” Self tapping mounting screws 

 
 

       

It is recommended that this unit be installed and 

maintained by a trained technician. 
 
The UVMatrix

TM

 SI Series systems are required to be 

wired from a disconnect switch so the power can be 
turned off for maintenance. 

It is recommended that the UVMatrix

TM

 SI Series systems 

be wired through a safety interlock switch that will 
disengage power to the equipment in the event that a 
door or access panel is opened. 

In the event of accidental breakage or replacement of the 
ultraviolet lamp, please ensure that the lamp is disposed 
of in accordance with local and state environmental laws 
regarding fluorescent lamps containing mercury. 
 

                          

 

Safety Precautions:                                          

WARNING: UV hazard. Always protect eyes from 

ultraviolet light. NEVER look at UV lamps in                     
operation. Unplug or disconnect power 
before re-lamping or servicing. 

 
WARNING: No openings in the air handler or duct are 

allowed which would give direct line-of-sight 
to the UV light. 

 
CAUTION:  Equipment Damage Hazard.  Ultraviolet light 

can cause shift or surface degradation and 
sometimes structural degradation of non-
metallic components.  Select mounting 
location that prevents exposure to plastic 
flexible duct components, polyurethane 
foam, insulation material, rubber hoses, wire 
insulation, etc.  If mounting options are 
limited, items above should be protected with 
ultraviolet resistant material such as 
aluminum foil, aluminum tape, or metallic 
shields. 

 

 
 

Evaporator 

Coil

Airflow

UVC 

Equipment

 