- 7 -
ULT33063
Battery Replacement Procedure
5.3 Storage
To store the UPS, cover it and store it with the battery fully charged. During extended
storage, it is suggested to connect the utility power to the UPS to recharge the battery every
three months to ensure battery life.
A
PPENDIX A
T
ROUBLESHOOTING
Problems Possible
Cause
Solution
Full-time Bypass
Protection outlets
stop providing
power to the
equipment
Circuit breaker button popped up as
a result of overload.
Unplug at least one piece of
equipment from the Full-time
Surge Protection outlets,
switch off the UPS, wait for 5
seconds and reset the circuit
breaker (press down breaker
button, then switch on UPS).
Battery undercharged or depleted
due to frequent power outages.
Recharge the battery by leaving
the UPS plugged in and switched
on.
The power required by your
equipment slightly exceeds the
capacity of the UPS.
Unplug at least one piece of
equipment from the UPS outlets.
UPS doesn’t
perform to its
expected runtime.
The battery is slightly worn-out.
Consider replacing the battery.
UPS has a circuit breaker designed
to prevent damage.
Switch UPS off, wait for 5
seconds, and then switch UPS
on.
The battery is worn-out.
Consider replacing the battery.
UPS cannot be
turned on.
Mechanical problem.
Contact your sales
representative.
- 8 -
A
PPENDIX B
S
PECIFICATIONS
Part No.
ULT33063
Model
RCD-UPS700
UPS Capacity
700VA
Total Capacity
(Protection)
1200VA
No. of sockets
Style A UPSx3, Bypassx3
Voltage (on battery)
Simulated sine wave at 120V +/- 5%
Frequency(on battery)
50 or 60Hz +/- 0.3Hz
Output
Transfer Time
2-4 milliseconds, including detection time
Voltage (single phase)
120V +15%/-20% at line input
Input
Frequency
50 or 60Hz +/- 10% (auto sensing)
Unit Input
Circuit breaker for overload & short circuit
protection
Overload Protection
AC Mode: If load exceeds 110% of nominal,
Buzzer beeps continuously. If load exceeds
120% of nominal for 30 seconds, 130% for 3
seconds, UPS shuts down automatically.
Back up Mode: If load exceeds 105% of
nominal for 20 seconds, 120% for 10 seconds,
130% for 3 seconds, UPS shuts down
automatically.
Short Circuit
UPS output
shuts o
ff immediately
Protection
Surge Protection 1140 Joules, 2ms
Type
Sealed, maintenance-free lead acid batter
y
,
with 3-6 years typical lifetime
Typical Recharge Time
6 hours (to 90% of full capacity)
Back-up Time
9-11 minutes (a PC with 15” CRT monitor)
17-19 minutes (a PC with 15” LCD monitor)
Battery
Protection
Automatic self-test, Over
discharge
protection, short circuit protection by fuse
Net weight Kg (lbs)
2.58(5.67)
Physical
Dimension (W x D x H)
104 x 316 x 85 (4.1” x 12.4” x 3.3”)
Interface USB
Battery low detecting, USB on/off scheduling
AC input/output power status display.
Battery Back-Up
Slow beeping sound every 4 seconds
Battery Low
Rapid beeping sound every second
Charge Abnormal
AC Mode: Rapid beeping sound every 0.5
second
Alarm
Overload
Continuous beeping sound
Ambient operation
3,500 meters max. elevation, 0-95% humidity
non-condensing, 0-40
℃
Environment
Audible Noise
<40dBA (1 meter from surface)