Ultra-Aire MD33 Installation Instructions
www.InWallDehumidifier.com | (800) 533-7533
SERVICE
Troubleshooting
Symptom
Possible Reason
Troubleshooting Procedure
Blower is running
and compressor is
off while ambient
humidity is high
(evaporator coil is
warm).
1. Wiring or connectors
loose
2. Compressor relay failure
3. Compressor capacitor
failure
4. Compressor failure
• Check wiring and connectors for damage or loose
connections.
• Check power to compressor circuit, replace power board if
no power is detected.
• Replace compressor capacitor if failed.
• Note that sealed system is not generally field serviceable.
Poor dehumidification
performance and
evaporator coil is
covered in ice or frost.
1. Defrost sensor or
connection is defective
2. Poor airflow
3. Low refrigerant charge
• Check circuit board connection for loose plug or wires.
• Press and hold both arrow buttons for >5 seconds to
display the defrost sensor temperature, replace sensor if
reading is an error. See diagnostic - Error code “ 1”
• Verify airflow over the coils is not blocked or restricted,
clean filter and/or coils as required.
• Note that sealed system is not generally field serviceable
• See diagnostic - Error code “3”
Poor dehumidification
performance,
compressor is
running and
evaporator coil is
not cooling.
1. Failed compressor or
low refrigerant charge
• See diagnostic - Error code “3”
• Note that sealed system is not generally field serviceable.
Blower is not
spinning humidity
is high and
compressor is
running.
1. Wiring or connectors loose
2. Blower relay failure
3. Blower capacitor failure
4. Blower failure
• Check wiring and connectors for damage or loose
connections.
• Check power to blower circuit, replace power board if no
power is detected.
• Replace blower capacitor if failed.
• Replace blower (note requires unit be removed from
installation).
Blower is running
and compressor
is cycling on and
off while ambient
humidity is high.
1. Unit is defrosting
2. Ambient temperature is
too low
3. Defrost sensor malfunction
4. Poor airflow
5. Failing compressor relay
6. Compressor or sealed
system failure
• Check setpoint, if setting is “00” increase setpoint to 55%.
• Cold ambient conditions will cause unit to go in and out of
defrost (this is normal).
• Press and hold both arrow buttons for >5 seconds to
display the defrost sensor temperature, replace sensor if
reading is in error.
• Verify airflow over the coils is not blocked or restricted,
clean filter and/or coils as required
Replace power board.
• Note that sealed system is not generally field serviceable.
Neither blower
nor compressor is
running and display
is on.
1. No call for
dehumidification
2. Wiring or connectors
loose
• Press down arrow until setpoint reads “00”, wait 1 minute,
fan and compressor should run.
• Check wiring and connectors for damage or loose
connections.
• Locate circuit breaker and reset if necessary.
• Check all circuit board connections for loose plugs
or wires.
• Replace control board and power board.
Neither blower
nor compressor is
running and display
is off.
1. No power to unit, circuit
breaker tripped
2. Power board wiring or
connector loose
3. Control board wiring or
connector loose
4. Circuit board failure