Ultra-Aire MD33 Installation Instructions

The Ultra-Aire MD33 has an illuminated display, user selectable setpoint, and a power ON / OFF button located 

behind the diffuser. The diffuser is fastened with tamper resistant screws to limit access to the control. The diffuser 

can also be fastened with the included phillips screws if limiting access to the control is not needed. 
When turning power on for the first time, the set point will be at the factory setting of 55% RH. In the event of  

a power outage, the dehumidifier restarts at the previous set point when power is restored.
Pressing the middle button (the power button), the control will toggle the Ultra-Aire MD33 to turn ON or OFF.  
If the unit is on and power button is pressed, control will turn compressor and fan off. As a result, both DISPLAY  

and LED will go off.  
If the unit is off and power button is pressed, control will turn fan on. As a result, both DISPLAY and LED will  

go on. 
If there is an error, the unit will shut down and indicator LED will turn to red and display will show an error code 

(see page 14 for error codes).  

Sequence of Operation

1.  Press the ON 

/

 OFF button to turn the dehumidifier control on. The display will show “00” for a couple of  

seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start  

sampling the air for one minute.
Indicator LED, located above display, will be green, showing the unit is operating normally.

2.  Pressing either of the arrow keys will cause the DISPLAY to flash and indicate the current set point. The RH set 

point can be adjusted from a minimum of 35% to a maximum of 99% in 1% increments. Adjust the humidity set 

point as desired. The recommended initial setting is 55%.
Pressing the DOWN arrow key below the 35% set point on the control will cause the display to read “00” and 

the Ultra-Aire MD33 will run continuously. After 10 seconds, it will go back to display room RH level.
Ten seconds after making an adjustment, from either UP or DOWN arrow keys, the display will go back to show 

the room RH level.

3.  If the sensor detects a reading above the set point, it will run the fan to sample the return air for a period of one 

minute. The sampled humidity of the return air will be compared to the RH setting. If the humidity is above the 

setting, the dehumidifier compressor turns on. The compressor remains on until the measured humidity falls 3% 

below the RH setting. If the sampled humidity is below the setting, the compressor and blower turn off and the 

display returns to showing the RH setting. The dehumidifier will sample again every 15 minutes.

CONTROLS

Содержание 4035900

Страница 1: ...ll framing The Ultra Aire MD33 provides the ultimate in comfort health and property protection TS 927 6 18 Rev E P N 4035900 Serial No Install Date Sold by HVAC Installer Please Leave Manual for Homeowner Installation Instructions INSTALLATION BY AN HVAC PROFESSIONAL IS RECOMMENDED Patent Pending D Therma Stor LLC ...

Страница 2: ...irements 7 Dehumidifier Installation 8 Maintenance 12 Air Flow 12 Controls 13 Service 15 Warranty 17 TABLE OF CONTENTS Therma Stor is committed to manufacturing quality products To maintain our standards product specifications may change without notice 4201 Lien Road Madison WI 53704 800 533 7533 www Thermastor com 2017 Therma Stor LLC ...

Страница 3: ...CTRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR PROPER UNIT OPERATION AND WARRANTY COMPLIANCE IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CARE AND FOLLOW INSTALLATION INSTRUCTIONS DO NOT USE IN POOL APPLICATIONS OR WARRANTY WILL BE VOID THIS APPLIANCE IS INTEND...

Страница 4: ...VENT ÊTRE RESPECTÉS POUR UNE UTILISATION ADÉQUATE DE CETTE UNITÉ ET UNE VALIDITÉ DE LA GARANTIE UNE INSTALLATION NON CONFORME PEUT CAUSER DES DOMMAGES MATÉRIELS OU DES BLESSURES TOUTE INSTALLATION TOUT ENTRETIEN ET TOUTE RÉPARATION DOIVENT ÊTRE EFFECTUÉS PAR UN TECHNICIEN D ENTRETIEN QUALIFIÉ LE DÉSHUMIDIFICATEUR EST LOURD MANIPULER AVEC SOIN ET SUIVRE LES INSTRUCTIONS D INSTALLATION ÉVITEZ D UTIL...

Страница 5: ...nted behind tamper proof cover Air Filter 1 2 Washable mounted behind diffuser Dehumidistat Digital tamper proof float switch input Cabinet Galvanized Steel Decibels 46 dBA Drain Connection 3 4 O D Drain Hose 10 gravity fed 3 4 I D hose can be routed through bottom or out the back of the cabinet Refrigerant Type R134A Refrigerant Amount 10 oz Coils Electrophoretic coated coils prevents corrosion a...

Страница 6: ...ding members or unwanted noise may result Unit is designed to be suspended by side mounting flanges only Drain hose must be routed with downward slope from unit drain connection to appropriate location Consult local building codes for acceptable condensate drain connections Location Considerations Install the unit on or inside of an interior wall and with direct connection to building electrical s...

Страница 7: ...Hz AC only 15 amp fused and grounded electrical supply A visible circuit breaker or disconnect switch near the unit is required for maintenance and service A dedicated circuit is recommended Use of a UL listed or CSA approved strain relief is required ELECTRICAL REQUIREMENTS Wiring Schematic DRAIN INSTALLATION CONSIDERATIONS Consult local building codes for condensate drain restriction and additio...

Страница 8: ...KER POWER BEFORE BEGINNING INSTALLATION 1 2 Electrical Box Shipping Bracket AVERTISSEMENT FERMEZ LE DISJONCTEUR ALIMENTATION AVANT DE COMMENCER L INSTALLATION Items Included in Box Ultra Aire MD33 Dehumidifier Diffuser Cover with Filter Ultra Aire MD33 Installation Instructions Drain Hose 10 Power Cord 10 Hose Clamp Grommet for Drain Hose Non Metallic Cable Clamp Bag A 10 Wood Screws 5 Bag B 8 She...

Страница 9: ...ep 3 There are three electrical knock outs one on the back and two on the bottom of the unit Remove appropriate knock out and install non metallic cable clamp with clamp screws inside of unit oriented so they are accessible for tightening later If using included power cord insert cord through non metallic cable clamp so that a minimum of insulation jacket is inside of cabinet before tightening non...

Страница 10: ...ing on both sides Additional insulation or sound dampening material not provided may be required if the dehumidifier cabinet contacts the studs especially in applications involving metal studs Fasten the unit to the framing by inserting four of the 10 wood or 8 sheet metal screws into the slotted holes Top and bottom blocking is not necessary for securing the dehumidifier Any existing blocking hea...

Страница 11: ...ne of the electrical wires are pinched Step 15 Turn breaker power back on Step 16 Set the digital controller to desired RH See Controls Section on page 13 Step 17 Install diffuser cover by aligning the lower tabs first then setting the cover back against the wall Insert the included four tamper resistant or phillips screws to secure the diffuser cover DEHUMIDIFIER INSTALLATION 14 17 Step 13 Comple...

Страница 12: ...ORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD AVERTISSEMENT ASSUREZ VOUS QUE L UNITÉ EST FERMÉE OU DÉBRANCHÉE OU QUE LE CIRCUIT D ALIMENTATION EST FERMÉ AVANT DE RETIRER LE PANNEAU AVANT POUR ENTRETENIR L UNITÉ AIR FLOW Supply Air Return Air Supply Air Supply Air Return Air Return Air The Ultra Aire MD33 functions...

Страница 13: ...y will show 00 for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute Indicator LED located above display will be green showing the unit is operating normally 2 Pressing either of the arrow keys will cause the DISPLAY to flash and indicate the current set point The RH set point can be adjusted from...

Страница 14: ...t after an hour Evaporator Temperature Mode To enter evaporator temperature mode press and hold both arrow buttons for 5 seconds and the LED will change to Blue The display will flash at twice the rate of set point mode and display the evaporator coil temperature Press any button to exit evaporator temperature mode Ambient Temperature Mode To enter ambient temperature mode press and hold the up ar...

Страница 15: ...PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON MISE EN GARDE LES TRAVAUX DE DÉPANNAGE NE DEVRAIENT ÊTRE EFFECTUÉS QUE PAR UN TECHNICIEN CVCA QUALIFIÉ AVERTISSEMENT RISQUE DE DÉCHARGE ÉLECTRIQUE UNE ALIMENTATION ÉLECTRIQUE DOIT ÊTRE UTILISÉE POUR EFFECTUER CERTAINES VÉRIFICATIONS CES VÉRIFICATIONS DOIVENT ÊTRE EFFECTUÉES PAR UN PERSONNEL D ENTRETIEN QUALIFIÉ WARNIN...

Страница 16: ...nning 1 Wiring or connectors loose 2 Blower relay failure 3 Blower capacitor failure 4 Blower failure Check wiring and connectors for damage or loose connections Check power to blower circuit replace power board if no power is detected Replace blower capacitor if failed Replace blower note requires unit be removed from installation Blower is running and compressor is cycling on and off while ambie...

Страница 17: ...ny costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the...

Страница 18: ...18 Ultra Aire MD33 Installation Instructions www InWallDehumidifier com 800 533 7533 ...

Страница 19: ...19 www InWallDehumidifier com 800 533 7533 Ultra Aire MD33 Installation Instructions ...

Страница 20: ......

Отзывы: