CYLINDER FAULT FINDING

PROBLEM

POSSIBLE CAUSE

REMEDIATIVE ACTION

Water is visible at tundish

Potential discharge from T&P valve

Follow tundish/T&P fault finding

Potential discharge from Expansion relief 

valve due to fault at PRV

Follow inlet control set fault finding

Back pressure from system

Check all cold connections into mixer 

outlets are fed from the balanced cold 

service from the inlet control valve. If 

not, additional PRV’s must be fitted.

Expansion relief valve opens when 

cylinder is heated

Possible fault at Expansion Vessel

Follow expansion vessel fault finding

Cylinder appears to be leaking from 

inside the steel case

Loose cylinder connection - notably from 

hot water outlet

Check all connection points including 

the immersion heaters and the hot 

outlet to ensure that these are not 

leaking, and remake joints if necessary.

Noise when operating tap or shower 

Vibrating/insecure pipework

Ensure that all pipework is secured to 

the wall with pipe clips as appropriate.

Reduced water flow

Possible external water works being 

carried out

Check with local authorities and wait 

for works to be completed

Lodged debris from mains at Inlet control 

set or PRV sticking

Strip & clean PRV/inline filter, or 

replace inlet control set.

No hot water available

Possible immersion heater failure

Follow immersion heater fault finding

EXPANSION VESSEL FAULT FINDING

PROBLEM

POSSIBLE CAUSE

REMEDIATIVE ACTION

Discharge of water from relief valve 

into tundish

Expansion Vessel is undersized

Vessel needs resizing and installing by 

a qualified heating engineer.

Pre-charge set incorrectly on vessel 

installation

Pre-charge requires setting when the 

system is depressurised according to 

manufacturer’s recommendations.

Vessel membrane is ruptured and may 

require replacement

Check schrader valve for leaks or  

damage. Replace vessel if necessary

Membrane may be partially  

depressurised due to losses over time and 

require re-pressurisation

Check schrader valve for leaks or  

damage. Have heating system serviced 

and vessel repressurised or replaced.

Leak from flange or water 

connection

Failure of flange plate

Replace flange plate or entire vessel

Ruptured membrane has led to internal 

corrosion and has caused leak in vessel

Replace entire vessel

Vessel appears full of liquid when 

system is cold

Membrane is fully depressurised

Replace membrane or entire vessel. 

Check schrader valve for leaks or 

damage.

Water discharges from vessel 

when schrader pin is depressed for 

inspection of pressure

Vessel membrane is ruptured 

Replace membrane or entire vessel.

Содержание 175006

Страница 1: ...ers range of water heaters and unvented water storage cylinders should only be installed as per these instructions by a competent certified heating installer By installing this product you agree to be bound by the purchasing and warranty terms and conditions found in this manual and on our website at www ukcylinders co uk IMPORTANT ...

Страница 2: ...te compliance with Building Regulations and should be provided to the customer for future reference Installers are required to carry out installation commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the scheme Visit www centralheating co uk for more information COMPONENT LISTI...

Страница 3: ...eed WATER SUPPLY We recommend that the maximum on site water demand be assessed and the water supply be tested to ensure it meets the following requirements This should be sourced from mains water only your warranty does NOT include the use of wells or bore holes as a water supply It must be noted that a high mains water pressure does NOT always guarantee a high flow rate Ensure a working not stat...

Страница 4: ...ion to the wall using the provided bracket and connect the pipework to the expansion vessel connection provided on the cold water inlet set There must be no obstruction or flow restriction between the cylinder and the expansion vessel You must ensure that the cylinder does not fill to a pressure of greater than 3 0bar If there are to be any showers bidets or monobloc taps in the installation or wh...

Страница 5: ... qualified electrician in accordance with latest I E E regulations Ensure the electrical supply is isolated before working on the system The electrical supply to each immersion heater must be fused at 13A via a double pole isolating switch with a separation of at least 3mm to both poles to BS 3456 The cable must be 2 5mm 2 heat resistant 85 C HOFR sheathed flex complying to BS6141 1981 Table 8 Do ...

Страница 6: ...are available The O ring on the head of the immersion heater should be correctly positioned and lubricated with a WRAS approved silicon lubricant before fitting Screw in by hand until almost sealed and then gently finish tightening as the O rings will seal easily Remake the wiring connection as per instructions provided INSULATION OF THE TEMPERATURE PRESSURE RELIEF VALVE Components for insulating ...

Страница 7: ...ible termination point or onto a roof capable of withstanding high temperature discharge at least 3m away from any plastic guttering Building Regulation G3 allows non metallic pipework within the tundish discharge D2 The discharge pipe D2 should be made of a metal or b another material that has demonstrated it can safely withstand high temperature water discharges and is clearly and permanently ma...

Страница 8: ...rrupt the power supply to the solar pump or controller in the event of excessive temperature In systems where the cylinder is above the panels then the energy cutout should be wired to a suitable 2 port valve not supplied on the return pipework to the solar panel LOWER COIL NON SOLAR This is connected to the additional boiler as per the instructions for a single coil cylinder with the high limit t...

Страница 9: ...2 3 E E E 2 2 1 C C SL Br Bl G O G Y Br Bl G O G Y HTG ON DHW ON DHW OFF TYPICAL WIRING S PLAN SINGLE ZONE TYPICAL WIRING Y PLAN COLOUR CODES W WHITE G GREEN Bl BLUE G Y GREEN YELLOW Br BROWN L LIVE N NEUTRAL C COMMON SL SWITCH LIVE E EARTH 9 2 PORT VALVE HEATING DUAL CYLINDER STAT 2 PORT VALVE DHW WIRING CENTRE ROOM STAT PROGRAMMER BOILER PUMP 3 PORT VALVE DUAL CYLINDER STAT 2 PORT SAFETY VALVE W...

Страница 10: ... ON DHW OFF 11 11 12 12 1 2 3 Br Bl G O G Y N 1 2 3 E HTG 2 ON 12 TYPICAL WIRING S PLAN TWIN ZONE COLOUR CODES W WHITE G GREEN Bl BLUE G Y GREEN YELLOW Br BROWN L LIVE N NEUTRAL C COMMON SL SWITCH LIVE E EARTH 10 DUAL CYLINDER STAT 2 PORT VALVE DHW WIRING CENTRE ROOM STAT PROGRAMMER BOILER PUMP 2 PORT VALVE HEATING 2 2 PORT VALVE HEATING 1 ROOM STAT ...

Страница 11: ...vicing must be carried out annually by competent installers Any spares used must be purchased from UK Cylinders Safety devices must not be bypassed Do not use the unit if safety features are not fully operational Proof of annual servicing is required to avoid invalidating your manufacturer s guarantee Upon installation of the unit the installer must complete the accompanying commissioning certific...

Страница 12: ...cking Strip clean PRV inline filter or replace inlet control set No hot water available Possible immersion heater failure Follow immersion heater fault finding EXPANSION VESSEL FAULT FINDING PROBLEM POSSIBLE CAUSE REMEDIATIVE ACTION Discharge of water from relief valve into tundish Expansion Vessel is undersized Vessel needs resizing and installing by a qualified heating engineer Pre charge set in...

Страница 13: ...13 INLET CONTROL SET FAULT FINDING TUNDISH FAULT FINDING ...

Страница 14: ...14 TEMPERATURE PRESSURE RELIEF VALVE FAULT FINDING DUAL THERMOSTAT FAULT FINDING ...

Страница 15: ...IMMERSION HEATER FAULT FINDING ENERGY CUTOUT FAULT FINDING 15 ...

Страница 16: ... has a water scale reducer been fitted Yes No What type of scale reducer has been fitted _______________________________________________________________________ What is the hot water thermostat set temperature C What is the maximum hot water flow rate at set thermostat temperature measured at high flow outlet l min Time and temperature controls have been fitted in compliance with Part L of Buildin...

Страница 17: ... Number ___________________________________ Comments __________________________________________ ___________________________________________________ ___________________________________________________ Signature ___________________________________________ SERVICE 6 Date______________________________________ Engineer Name ______________________________________ Company Name ___________________________...

Страница 18: ...ted in full at the time when the faulty part unit is returned to us We will not cover any installer claims for excessive travelling where the installer has accepted a job more than 30 miles from their base of operations Removal costs cannot be recovered for the collection of a faulty unit from a difficult to reach area or where cylinder access has been restricted as per this manual guidance Claims...

Страница 19: ... third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held in trust for us in a manner which enables such proceeds to be identified as such and 6 6 2 shall not be mixed with other monies nor paid into an overdrawn bank account The Company as principal shall remunerate the Bu...

Страница 20: ...UK Cylinders Limited Unit 3 RCM Business Centre Sandbeds Trading Estate Dewsbury Rd Ossett WF5 9ND Tel 03330 329650 Email sales ukcylinders co uk ...

Отзывы: