Grounding the Router

Warning

This equipment must be grounded. Do not defeat the ground conductor or operate 

the equipment without correctly grounding the equipment. If there is any uncertainty 

about the integrity of the equipment's grounding, please contact the electrical 

inspection authority or a certified electrician. 

1.

Before grounding the router, ensure that the rack is properly grounded and in

compliance with local regulatory guidelines. 

Ensure that there is nothing that can obstuct

the connection for grounding and remove any paint or materials that may prevent good

grounding contact.

2.

Strip the insulation from a size #6 AWG 

grounding

 wire (not provided within the package

contents), leaving 0.5” +/-0.02” (12.7mm +/-0.5mm) of exposed grounding wire.

3.

Insert the exposed grounding wire all the way into the hole of the

 grounding

 lug

(provided

 

with package contents).

4.

Using a crimping tool, firmly secure the grounding wire to the 

grounding 

lug.

/ŶƐƵůĂ

ti

ŽŶ

tŝƌĞ>ĞĂĚ

Green/Yellow

'ƌŽƵŶĚtŝƌĞ

;ƐŝnjĞηϲt'Ϳ

Ϭ͘ϱнͬͲϬ͘ϬϮ͟

;ϭϮ͘ϳнͬͲϬ͘ϱŵŵͿ

ƌŝŵƉŝŶŐdŽŽů

'ƌŽƵŶĚŝŶŐ>ƵŐ

&ŝŐƵƌĞ

 24. 

It is recommended that equipment changes be done on a grounded rack system. This will 

reduce or prevent the risk of shock hazards, equipment damage, and potential of data 

corruption.

The router can be grounded from the 

router's case

 and/or the power supply units (PSUs). 

When grounding the PSUs, ensure that both PSUs are grounded at the same time in case 

one of them is removed. 

A grounding lug and M4 screws and washers are provided with the 

package contents, however, the grounding wire is not included. For convenience, there are 

two locations on th

e

 case in which the grounding lug may be fixed.

The following instructions are for grounding the router.

Содержание S9501-18SMT

Страница 1: ...S9501 18SMT Disaggregated Cell Site Gateway Hardware Installation Guide R1 0...

Страница 2: ...our System 7 4 1 S9501 18SMT DC Version Overview 7 4 2 S9501 18SMT AC Version Overview 8 4 3 DC Version PSU Overview 9 4 4 AC Version PSU Overview 10 4 5 Fan Overview 10 4 6 Port Overview 11 5 Rack Mo...

Страница 3: ...ns 23 12 1 Connecting the USB Extender Cable 23 12 2 Connecting a Cable to the ToD Interface 23 12 3 Connecting the GNSS Interface 23 12 4 Connecting the 1PPS Interface 24 12 5 Connecting the 10MHz In...

Страница 4: ...ted open network infrastructure to lower costs and rapidly scale existing services for edge computing mobile backhaul and broadband access applications The S9501 18SMT is future proofed with a powerfu...

Страница 5: ...2 Insula on Wire Lead Ground Wire size 6 AWG 0 5 0 02 12 7 0 5 mm 14 AWG wire with ring terminal for DC power supply 6 AWG wire for grounding Wire stripping tools for stripping 6 AWG copper wire Conso...

Страница 6: ...h a rack mount brackets suitable for 19 inch 48 3cm wide racks The depth of the S9501 18SMT chassis is 11 89 inches 30 2cm without the field replaceable units FRUs and comes with adjustable mounting r...

Страница 7: ...8V DC 8 4 ampere maximum or AC version 100 240V 3 1 5 ampere Installation spacing and weight load requirement S9501 18SMT is 1RU 1 75 4 5cm in height 19 48 3cm in width and 16 40 6cm in depth without...

Страница 8: ...3 Rack Mount Bracket 1 98 x 1 69 x 0 79 19 width rack 50 4 x 43 x 20mm 2 pcs 0 15lbs 67 2g 2 pcs 0 07lbs 33 6g pcs 4 Screw Kit for Rack Mount Bracket 8 x Screws M4 0 L6 5mm 8 sets 0 01lbs 6 5g set 5 A...

Страница 9: ...mounting rail 0 89lbs 405g USB extension cord 0 021lbs 9 7g Screw kit for ground lug 0 008lbs 3 8g per set Screw kit for rack mount bracket and adjustable mounting rail 0 1lbs 6 5g per set Dimension S...

Страница 10: ...18SMT Hardware Installation Guide 7 4 Identifying Your System 4 1 S9501 18SMT DC Version Overview SPEC LABEL CUS BAR CODE SPEC LABEL CUS BAR CODE D 11 89 302 mm W 17 32 440 mm H 1 713 43 5 mm 1RU Fig...

Страница 11: ...dules OOB Type A USB 8 x 2 5G SFP TOD Console Grounding Lug Figure 6 4 2 S9501 18SMT AC Version Overview Figure 7 4 x 1G RJ45 SPEC LABEL CUS BAR CODE SPEC LABEL CUS BAR CODE D 11 89 302 mm W 17 32 440...

Страница 12: ...SU field replaceable unit FRU Figure 9 AIR FLOW 50 5 2 6 0 25 Handle Color Black EMI Shielding Gaskets 3x SPEC LABEL CUS BAR CODE 39 85 40 2 198 5 Latch Color Blue Figure 10 3 x 4028 Fan Modules 1PPS...

Страница 13: ...re Installation Guide 10 4 4 AC Version PSU Overview 1 1 hot swappable power supply unit PSU field replaceable unit FRU Figure 11 Figure 12 4 5 Fan Overview 2 1 hot swappable fan field replaceable uni...

Страница 14: ...Guide 11 4 6 Port Overview Port ID Form Factor Maximum Support Distance Support Speed 0 3 RJ45 238 01ft 100m 1GE 100M 4 11 SFP 24 85mi 40km 2 5GE 1GE 100M 12 17 SFP 24 85mi 40km 10GE 2 5GE 1GE DC Vers...

Страница 15: ...L6 5mm screws provided with the package Figure 16 2 Secure the router onto the rack posts Mark the location on both posts to ensure it is leveled before securing the router onto the rack using the sc...

Страница 16: ...led and the following steps are instructions on how to install a new fan module 1 Loosen the captive screw located on the fan module E Figure 19 2 Grip the fan s handle and firmly pull it out of the f...

Страница 17: ...d the following are instructions on how to install a new PSU Figure 22 Caution Shock hazard For safety please disconnect all power inputs from the power supply unit before servicing the router 1 Locat...

Страница 18: ...er bay and gently push until it is flush with the case 5 An audible click will be heard when the PSU is installed correctly The PSU will not go in all the way if it is in the wrong direction Note The...

Страница 19: ...tents leaving 0 5 0 02 12 7mm 0 5mm of exposed grounding wire 3 Insert the exposed grounding wire all the way into the hole of the grounding lug provided with package contents 4 Using a crimping tool...

Страница 20: ...4 screws and 4 washers provided with the package contents firmly lock the grounding lug to either of the designated grounding locations on the router OR Figure 25 2 x M4 L8 0 mm Screw 4 x M4 Lock Wash...

Страница 21: ...PSU has a built in 20 amperes fast acting fuse based on the PSU maximum capacity which will act as a second tier system protection in case the power distribution unit s fuse is not functioning 5 Verif...

Страница 22: ...er consumption is 200 watts with an input voltage of 100 240V and 3 amperes 2 Attach the power cable Plug the power cord into the AC PSU and secure it tightly 3 Verify that the power supply is operati...

Страница 23: ...r System power fail FAN OFF No fan modules present Solid Green All fan modules work well Blinking Green Reserved Solid Amber Reserved Blinking Amber One or more FAN module s fail STAT OFF System x86 B...

Страница 24: ...in learning state Self survey is not completed NOTE Need NOS to activate this feature Blinking Amber GNSS antenna is short to ground NOTE Need NOS to activate this feature 10 2 PSU FRU LED LED Condit...

Страница 25: ...ug a RJ45 serial cable into the console port and connect the other end to the computer Cable types may vary depending on the model 2 Check for serial control availability Disable any serial communicat...

Страница 26: ...traight through Ethernet cable to the GNSS unit 2 Connect the other end of the straight through Ethernet cable to the port marked TOD located on the front panel of the router 12 3 Connecting the GNSS...

Страница 27: ...nize the cables For easier management label each fiber optic cable and record its respective connection Maintain a clear line of sight to the port LEDs by routing the cables away from the LEDs Caution...

Страница 28: ...ment damage may result Caution Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure Warning Do not use optical instr...

Страница 29: ...www ufispace com...

Отзывы: