M3000-14XC Hardware Installation Guide | 3
Installation Environment Requirements
•
Power Reserve: The M3000-14XC power supply is available with:
1.
DC Version:
1+1 active-active -36 to -75V DC power supply field replaceable unit or;
2.
AC Version:
1+1 active-active universal 100 to 240V AC power supply field replaceable unit.
To ensure the active-active feed power design functions properly, a field with dual power
circuit is recommend with a reserve of at least 200 watts on each power circuit.
•
Space Clearance: The M3000-14XC width is 17.32 inches (44cm) and shipped with a rack
mount brackets suitable for 19 inch (48.3cm) wide racks. The rack mount brackets can be
installed at the front or in the center of the M3000-14XC. The depth of the M3000-14XC
chassis is 9.84 inches (25cm) without the field replaceable units (FRUs). To accommodate the
air inlet and front cabling, a recommended minimum space clearance of 6 inches (15.2cm) for
the front of the unit. A total minimum reserve depth of 15.84 inches (40.23cm) is required.
Illustrations are for reference purposes only. Actual scenario and equipment may
differ.
Figure 1.
Figure 2.
•
Cooling: The M3000-14XC airflow direction is front-to-back. Make sure the equipment on
Содержание M3000-14XC