The UEi LRA Inrush is programmed to properly capture the starting current for
compressor motors.
• Select AC Amps.
• Select the range capable of capturing the maximum value.
• Press the ZERO button – INRUSH will now be shown on the screen.
• Activate the compressor and read value on the display.
• Press the Zero button to return to live readings.
LRA Inrush
• Default =
• Press ZERO = Inrush
• Readings show on upper display
30V
T
1
TEMP
T
2
True RMS
DL589
PEAK
µA
Temp
600V
600A
CAT IV
V
A
SELECT
Low Z
AUTO
V
A
Select DC current.
• Press to zero any offset in Amps DC.
• Used to monitor change from present displayed value.
• Required during DC Amps measurement to establish a zero level.
WARNING
Do not use DC Zero mode at amps greater than 600A DC.
Zero DC Amps
• Default =
• Press SELECT=
• Press ZERO = DC Amps Zero