TOOLS NEEDED  

3/16” open end wrench (2)

1/4” open end wrench

5/64” allen wrench

5/16” open end wrench (2 required for 822e only)

after coMpleting adjustMents on all 120 series, be sure to 

re-install adjustMent cover.  do not over tighten cover screws. 

for  set point adjustment and recalibration, connect device to a calibrated 

temperature source and stabilize.

Types C120, F120 

remove cover.

 

adjust set point by holding plunger with 3/16” open end 

wrench and turning the calibrating screw with another 3/16” open end 

wrench (see figure 3). turn clockwise to increase setting or counter-

clockwise to decrease setting. 

ORN

YEL

RED

TYPES B122, E122, E122P

BLU

VLT

BLK

NOTE 

REVERSE 

WIRING OF 

LOW SWITCH

N.C.

N.O.

COM.

N.C.

N.O.

COM.

2SPDT

N.C.

N.O.

COM.

Plunger

TYPES B121, C120, E121, F120, 820E

SPDT

N.C.1

N.C.2

N.O.1

N.O.2

COM. 1

COM. 2

Plunger

RED

YEL.

ORN.

OPTION 1010, 1190, 1195

(FOR TYPE B121, C120, E121, F120 ONLY)

DPDT

N.C.

N.O.

COM.

N.C.

N.O.

COM.

TYPE 822E

#1

#2

NC NO COM NC NO COM

SWT#2

SWT#1

BLK BLU VLT RED ORN YEL

Figure 3

Figure 2

use 90°c copper conductors only. 
recommended tightening torque for 
field wiring terminals is 7-17 in-lbs.

Part II - Adjustments

 

Types  B121 and E121

remove adjustment cover. adjust set point by turning external knob and 

pointer to desired setting on scale (see figure 4).  

Types  B122 and E122

individual switches may be set together or separately by up to 100% of 

range. the front (low) switch should never be set higher than the rear (high) 

microswitch.  turning external knobs will increase or decrease each switch 

setting independently (see figure 4).

Indicating Temperature Switch Types 820E & 822E
NOTE: 

prior to making any device adjustment, the cover and adjustment 

knob should be removed. when adjustment is completed, all applicable parts 

should be replaced. 

Type 820E

Move the set point adjustment pointer up scale beyond the brown indicating 

pointer. this permits checking the set point by moving the lever arm upward 

with a finger or tool simulating thermal assembly movement. connect test 

lights to indicate switch operation or listen for the switch to click. loosen 

adjustment “a” and move the adjustment pointer until it agrees with the 

indicating pointer (see figure 5). when the switch clicks re-tighten the screw.

Type 822E
NOTE: 

type 822e has a single knob and pointer for both switches. both 

switches are standardly, factory set together within 5% of the dial range. 

turning the knob positions both switches simultaneously, maintaining a 

constant separation between them. 
remove the explosion-proof die-cast cover to permit access to the switches. 

Move the adjustment pointer up scale beyond the indicating pointer by an 

amount greater than the difference between the switch settings by moving 

the actuating lever upward with a finger or a tool simulating thermal assembly 

movement (see figure 5). connect test lights to indicate switch operation or 

listen for the individual switch clicks.
the set point of switch #1 is determined by the red adjustment pointer. the 

set point of switch #2 may be adjusted by up to 25% of the range span 

below the switch #1 set point by turning adjustment “d” in (clockwise).  

see back page for 822e dual switch adjustment. the set point of switch #2 

should not be above that of switch #1.
to align switch #1 to the adjustment pointer, loosen adjustment “a” and 

set the adjustment pointer to the scale, then re-tighten adjustment “a” (see 

figure 5).

NOTE:

 indicating pointer deflection (820e, 822e): the indicating pointers 

will read slightly low when the bulb temperature is 15° above the controller 

setting. this deflection is normal and repeatable (approximately 0.5% of 

scale range on single switch models) and is due to the transference of the 

switching mechanism load to the thermal system. it can be measured by 

moving the setting pointer from the high to the low end of the scale and 

observing the resultant indicating pointer deflection.

Figure 4

external knob and pointer 
adjustment

ORN

YEL

RED

TYPES B122, E122, E122P

BLU

VLT

BLK

NOTE 

REVERSE 

WIRING OF 

LOW SWITCH

N.C.

N.O.

COM.

N.C.

N.O.

COM.

2SPDT

N.C.

N.O.

COM.

Plunger

TYPES B121, C120, E121, F120, 820E

SPDT

N.C.1

N.C.2

N.O.1

N.O.2

COM. 1

COM. 2

Plunger

RED

YEL.

ORN.

OPTION 1010, 1190, 1195

(FOR TYPE B121, C120, E121, F120 ONLY)

DPDT

N.C.

N.O.

COM.

N.C.

N.O.

COM.

TYPE 822E

#1

#2

NC NO COM NC NO COM

SWT#2

SWT#1

BLK BLU VLT RED ORN YEL

ALSO FOR OPTION 1180

Содержание B121

Страница 1: ...signal Control set point s may be varied by turning the adjustment hex C120 F120 or the external knob s and pointer s B121 B122 E121 E122 820E 822E according to the procedures outlined See Part II Adjustments Please refer to the product technical brocures for product specifications Product technical brochures may be found at www ueonline com UE declarations and third party issued certifications ar...

Страница 2: ... wrench on the temperature housing hex when mounting the device do not tighten by turning the enclosure as this will damage sensor and weaken solder and welded joints vertical mounting temperature probe facing down is recommended however device can be mounted in any orientation with adherence to previous warnings and exceptions below Remote mount types E121 E122 F120 temperature devices may be mou...

Страница 3: ...r the switch to click Loosen adjustment A and move the Adjustment Pointer until it agrees with the Indicating Pointer see Figure 5 When the switch clicks re tighten the screw Type 822E NOTE Type 822E has a single knob and pointer for both switches Both switches are standardly factory set together within 5 of the dial range Turning the knob positions both switches simultaneously maintaining a const...

Страница 4: ...g screws Re position the housing index against the calibration on the instrument case or skeleton casting at a rate of 1 divi sion line per capillary length listed in Figure 6 Move to the left if capillary is to be added to the process or to the right if capillary is to be removed from process Added to or taken away from the process Model Number Range Cap Length Division 1 180 to 120 F 2 ft 2 125 ...

Страница 5: ... 1mm 4 11 16 119 3mm 1 11 16 43 2mm 2 1 4 57 5mm 1 17 32 38 9mm 3 8 9 5mm A 7 8 22 2mm BULB SET POINT ADJUSTMENT KNOB SET POINT INDICATING POINTER RED CLEARANCE FOR 1 4 SCREW 4 MT G HOLES TEMPERATURE INDICATING POINTER BLACK 3 4 NPT E C BOTH SIDES B LU B LK R E D V LT O R N Y E L S W T 1 S W T 2 N C C O M N O N C C O M N O 5 64 2mm SOCKET COVER LOCK SCREW GROUND SCREW 3 4 NPT E C PLUGGED ADJUSTMEN...

Страница 6: ...uld endanger property or personnel For all applications a factory set unit should be tested before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding publ...

Отзывы: