SMoGHoG

®

SHM Series Models 

8

3.5.3 ELECTRICAL TOUCHSCREEN 

CONTROLS

the main control panel for the SHM unit is a touchscreen 

interface  located  integrally  on  the  front  of  the  unit  or 

remotely in an auxiliary enclosure (refer to section 3.5.4) 

that operates the blower. 
the  touchscreen  control  panel  is  powered  by  24V  dc. 

refer  to  Section  4  of  this  manual  for  operation  of  the 

touchscreen. all wiring in the touchscreen controls panel 

is  pre-wired  at  the  factory  and  there  are  no  customer 

connections at this panel. the panel door should remain 

closed and locked during operation. 

3.5.4 ELECTRICAL REMOTE PANEL 

CONTROLS

Both  the  Basic  and  touchscreen  controls  can  be 

mounted  remotely  from  the  unit.  The  max  distance  is 

 

100 ft (30.5 m). the controls are provided in a neMa 4X 

enclosure for mounting. 
Basic controls – the remote controls panel/enclosure will 

contain  the  blower  speed  adjusting  potentiometer  inside 

the  enclosure,  and  an  on/off  switch  on  the  cover.    this 

enclosure will be attached to the SHM unit at the factory 

with 50ft of wire.  the cable can be cut down in length at 

the time of installation if needed by disconnecting the wire 

from the remote panel, cutting to length, and reconnecting. 

use the wire diagram on page a2 for reference.
touchscreen controls – the remote touchscreen controls 

enclosure will contain the touchscreen and terminal blocks 

for the wire connections.  there are two cables connected 

to the remote enclosure that are 100ft each. one is the 

24  Vdc  power  supply  and  control  cable,  and  the  other 

is  a  communication  cable.   these  wires  will  need  to  be 

connected to the rear control panel of the SHM unit by the 

customer at the time of installation.  the first wire is the 

low voltage controls wire that will connect to the terminal 

blocks in the back of the SHM unit on +24Vdc, -24Vdc, 

an2, an3, an4, i0, and o0.  use the wire diagram on page 

a6 for wire colors and terminal location for landing.  the 

second wire is a communication wire that needs landed in 

the WaGo 222 Lever Wall nuts.  Match the colors of the 

wires, brown with brown and black with black.

3.5.5 MACHINE INTERLOCK DRY CONTACT

the  customer  has  the  option  to  control  the  SHM  on/

off  operation  with  the  oil  mist  generating  equipment  or 

process. this will allow the operator to control the SHM 

with a dry-contact off another piece of equipment. refer 

to the  wiring  diagrams  in  the appendix  for  wiring  of this 

option and to Section 4 for Machine interlock set up on 

the touchscreen. 
Wiring will be terminated to the terminal blocks located in 

the rear electrical panel in figure 1B When the machine 

dry contact is closed, the SHM blower will be on and when 

the contact is open, the SHM unit blower will shut down. 

Note: 

a relay coil cannot be connected to the SHM and 

will not work for this type of electrical circuit.

3.6  FILTER INSTALLATION

the primary filter elements are shipped already installed 

in the SHM unit. if an after-filter option is selected by the 

customer, those filters will be shipped separate of the unit 

to be mounted following unit installation at the customer 

facility. filters may removed from the primary filter cabinet 

by the customer when delivered to lessen weight, protect 

them from damage, and ease unit installation.
Proper removal and installation of each filter type is shown 

in figures 5a & 5B.

3.6.1 INSTALLATION PROCEDURE FOR 

AFTER-FILTERS

3.6.1.1 HOLD DOWN

center  the  filter(s)  atop  the  unit  when  viewed  from  the 

front. if the unit is two filters deep, then the two after-filters 

will be butted against each other in the center of the unit 

(looking at it from the side) from front to back just as with 

the internal filters.
the hold-down brackets are to be placed on top the filters 

as shown in figure 5a balloon #7 and secured down with 

all-thread  rods,  washers  and  nuts.  tighten  nuts  using 

hand tools and be sure not to over compress the gasket 

on the bottom side of the after-filter. Minimal torque should 

be applied; just enough to cinch down each bracket so it 

will not slide around on top of the filter(s). on units two 

filters deep, a center bracket is also supplied that runs in 

the same direction, it is placed immediately over the seam 

where the two filters are butted together. 
Larger  size  unit  after-filter  setups  will  be  installed  in  an 

identical fashion. the filters will always be installed in-line, 

directly  over  the  perforated  square  cutouts  on  the  top 

panel. 

Содержание SMOGHOG SHM-11C

Страница 1: ...Model SHM 11C Shown SMOGHOG Media Mist Collector l Models SHM C SHM F OWNER S MANUAL ...

Страница 2: ... following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ___________________...

Страница 3: ...on 8 3 6 1 Installation Procedure for After Filters 8 3 6 1 1 Hold Down 8 3 6 1 2 Enclosed 10 3 7 Drains 10 4 UNIT OPERATION 10 4 1 Start up 10 4 2 System Operation 10 4 2 1 Airflow Adjustment Using Manual Speed Control 10 4 2 2 Airflow Adjustment Using Auto Flow Control 10 4 3 Touchscreen Operation 11 4 3 1 Start Up And Home Screen 11 4 3 2 Standard Format 11 4 3 3 Basic Screens 12 4 3 4 Auto Flo...

Страница 4: ...terials and vapors such as gasoline away from the unit The unit should be inspected frequently and contaminants removed to prevent excessive accumulation which may result in flash over or fire damage Operate only in a safe and serviceable condition Operating temperature to the air stream should not exceed 120 F 49 C DANGER WARNING WARNING CAUTION C A U T I O N This is the safety alert symbol This ...

Страница 5: ...re assistance in the installation startup operation maintenance or troubleshooting of your air cleaning equipment contact your local UAS sales representative 2 1 SMOGHOG NOMENCLATURE SMOGHOG oil mist air cleaners are available in a variety of configurations and sizes The model string for each given unit represents the base configuration The model number completely identifies the design and can be ...

Страница 6: ...REV 16I SMOGHOG SHM Series Models 2 FIGURE 1B SHM Equipment Description 61 10113 FIGURE 1A SHM Equipment Description ...

Страница 7: ... the unit in each corner Do not lift the unit by placing lift truck forks through the legs on the underside of the unit Filter Elements Stage 1 Mist Stop fine fiber aluminum mesh Stage 2 Primary coalescer featuring Peach Saturated Depth Coalescing Technology or fiberglass bag Blower Cabinet Most units will have a blower cabinet where the motorized impeller style blower is housed as well as the ele...

Страница 8: ...eering drawings of your specific equipment and options will be provided These and all available documentation for your system should be thoroughly reviewed prior to beginning any installation work This includes the unit and electrical controls Ensure to leave an appropriate amount of room around your unit to allow for maintenance and servicing A minimum of 2 1 2 feet 0 76 m of clearance is recomme...

Страница 9: ...iguration Secure the unit at all four corners using the standard unit feet or extension leg foot pads At least one of the two holes per foot pad on the extension legs should be secured See Figure 1 for reference Ceiling mounted units are suspended by means of 1 2 threaded rods item 1 in Figure 3 which run through weld nuts item 2 in Figure 3 in the top corners of the units Refer to Figure 2 for we...

Страница 10: ...LS ON SHM 11 SUBTRACT 0 5 AMP FROM FLA VALUES ABOVE TABLE 2 Wire Diagrams 3 5 1 ELECTRICAL SUPPLY POWER The main power supply is connected to the SHM unit through a 1 FNPT coupling located on the rear of the unit shown in Figure 1B After feeding wires through the coupling terminations are made on the main bus bar terminal for each phase and frame ground connection The rear electrical panel also co...

Страница 11: ...REV 16I SMOGHOG SHM Series Models 7 61 10126 Figure 4 Remote Panel Touchscreen Connection ...

Страница 12: ... INTERLOCK DRY CONTACT The customer has the option to control the SHM On Off operation with the oil mist generating equipment or process This will allow the operator to control the SHM with a dry contact off another piece of equipment Refer to the wiring diagrams in the appendix for wiring of this option and to Section 4 for Machine Interlock set up on the touchscreen Wiring will be terminated to ...

Страница 13: ...REV 16I SMOGHOG SHM Series Models 9 61 10115 Figure 5B SHM Filter Removal Installation Figure 5A SHM Filter Removal Installation ...

Страница 14: ... other equipment will need to be engaged as well 7 Verify performance of the system by measuring airflow or evaluating capture at each collection point It is recommended to record baseline performance parameters so the system can be reset in case of an upset condition or system change The recorded data should include the static pressure at each collection hood system amperage draw and filter press...

Страница 15: ...After Filter monitoring or unique screens required for a special application These screens are based on customer order and loaded at the factory Figure 6 4 3 2 Standard Format The icon key Table 3 outlines the various icons that are used on the screen for various reasons and may indicate status or conditions The Home Settings and Information icons are shown at the bottom of most screens and will t...

Страница 16: ...n arrows The second method of airflow adjustment is to touch the box that shows the percentage of the airflow A number pad will be shown in a pop up screen You can enter any number between 20 and 100 This will correspond to the percentage of blower capability The blower is capable of 4 200 RPM at 100 3150 RPM for 75 2100 RPM for 50 and 1050 RPM for 20 These number are approximate and may display s...

Страница 17: ...are not password protected To select one of the items just touch the box with the item you want to make a change too The Locked Settings selection will allow the operator to select options of the system One option is Machine Interlock With Machine Interlock the operator can allow another device CNC machine center plasma table or weld machine to turn the SHM on when the primary device is in operati...

Страница 18: ...ocked Settings group on the Customer settings screen The Auto Flow is an option that is selected at order time and loaded into the SHM at the factory The Auto Flow Settings will allow the unit to maintain a precise operating point based on a desired air volume The operator will select an air volume setting in the airflow set point box using the up down arrows or the selection box If the screen is ...

Страница 19: ...r hose This filter can be replaced if contaminants become impossible to remove or due to excessive wear Always wear proper PPE including goggles dust mask and work gloves when installing or replacing filter elements Oil accumulated on the filter elements can result in irritation of the lungs skin and or eyes Remove used filter elements from the collector and dispose of properly in accordance with ...

Страница 20: ... into place prior to hanging the individual bags loops For units that are two filters deep be sure to push the first filter all way toward the back of the primary filter cabinet until it contacts the stop Reference balloon 1 in Figure 5A The hanging rod is to be inserted through each filter loop and hung from a bracket on each side of the primary filter cabinet Work from the back of the cabinet to...

Страница 21: ...ker Open rear panel on unit and switch breaker if necessary Loose or disconnected wires Inves gate wiring in the rear panel Disconnect is switched to OFF posi on Switch disconnect to ON posi on Improper source power Refer to data plate to verify required input power Screen Displayed Warning Possible Causes Recommended Solu ons Filter Cau on Filter is approaching max life Replace filter s soon Yello...

Страница 22: ...ILTER HEPA 99 97 0 3 μm 5 33 10117 ALUMINUM MESH PRE FILTER 6 33 10128 COALESCING CARTRIDGE FILTER 9 OD PEACH MEDIA 33 LENGTH 3 33 10129 CABINET AFTER FILTER MICROGUARD O M 95 0 3 μm 7 39 10008 0006 CONTROLS PANEL LATCH 10mm HEX 8 39 10058 FLUSH MOUNT FILTER CABINET LATCH NOT SHOWN 42 0168 FILTER CABINET GASKET NOT SHOWN 42 1549 SEALANT NOT SHOWN 20 10413 PRESSURE TRANSDUCER NOT SHOWN 38 10145 BUL...

Страница 23: ...REV 16I SMOGHOG SHM Series Models 19 Figure 6 SHM Replacement Parts SHM 11C SHM 11F ...

Страница 24: ...REV 16I SMOGHOG SHM Series Models 20 APPENDIX WIRING DIAGRAMS BASIC CONTROLS A1 04 001682 ...

Страница 25: ...REV 16I SMOGHOG SHM Series Models 21 A2 REMOTE PANEL BASIC CONTROLS 04 001799 ...

Страница 26: ...REV 16I SMOGHOG SHM Series Models 22 A3 ONE BLOWER AND CONTROLS 04 001695 ...

Страница 27: ...REV 16I SMOGHOG SHM Series Models 23 A4 TWO BLOWER AND CONTROLS 04 001696 ...

Страница 28: ...REV 16I SMOGHOG SHM Series Models 24 A5 THREE BLOWER AND CONTROLS 04 001697 ...

Страница 29: ...REV 16I SMOGHOG SHM Series Models 25 A6 REMOTE PANEL TOUCH CONTROLS 04 001802 ...

Страница 30: ...REV 16I SMOGHOG SHM Series Models 26 A7 ONE BLOWER AND REMOTE CONTROLS 04 001798 ...

Страница 31: ...REV 16I SMOGHOG SHM Series Models 27 A8 TWO BLOWER AND REMOTE CONTROLS 04 001797 ...

Страница 32: ...REV 16I SMOGHOG SHM Series Models 28 A9 THREE BLOWER AND REMOTE CONTROLS 04 001796 ...

Страница 33: ...REV 16I SMOGHOG SHM Series Models 29 A10 575 480 TRANSFORMER 04 001717 ...

Страница 34: ...This page intentionally left blank ...

Страница 35: ...This page intentionally left blank ...

Страница 36: ...ranty as to goods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE...

Отзывы: