background image

19

EMP

Installation & Service Manual

109529-03 - 11/19

Figur

e 9A:

 R

ecommended 

W

at

er Piping f

or Cir

culat

or Zoned Heating S

yst

ems

3

 Water Boiler Piping 

(continued)

Содержание EMP Series

Страница 1: ...Direct Vent 140E thru 224E Models EMP84E EMP115E EMP140E EMP182E EMP224E TO THE INSTALLER Affix these instructions adjacent to boiler TO THE CONSUMER Retain these instructions for future reference 970...

Страница 2: ...ler is valid only if the boiler has been installed maintained and operated in accordance with these instructions Surface rust on cast iron sections may be attributed to the manufacturing process as we...

Страница 3: ...the installing contractor to see that all controls are correctly installed and are operating properly when installation is complete including verifying that the limit sensor is fully installed seated...

Страница 4: ...r or smokepipe joints may be signs of condensing flue gases Flue gas condensate is corrosive which requires special consideration and must be addressed immediately Refer to Natural Draft Venting Chimn...

Страница 5: ...5 EMP Installation Service Manual 109529 03 11 19 Figure 1 EMP Water Boiler NOTE This Dimension increases and is controlled by smoke pipe arrangement...

Страница 6: ...MBH 3 AFUE Minimum Chimney Recommendations Direct Vent System GPH MBH 1 Round In Dia Rectangle In x In Height Ft Model Vent Connector Dia Inch EMP84E 0 60 84 74 64 87 6 8 x 8 15 N A N A EMP115E 0 80 1...

Страница 7: ...t Panel 24 for servicing burner 24 for flueway cleaning EMP84E 140E 30 for flueway cleaning EMP182E 36 for flueway cleaning EMP224E b Clearance from Jacket Side Panels 19 for burner swing door if open...

Страница 8: ...nces in space If the result is greater than or equal to 50 ft3 1000 BTU per hour then it is considered an unconfined space If the result is less than 50 ft3 1000 BTU per hour then the space is conside...

Страница 9: ...utomatically during equipment operation D DIRECT VENT CONFIGURATIONS requires 1 Beckett NX Burner 2 Direct Vent Conversion Kit 3 Double Wall Flex Oil Vent Pipe FOVP Horizontal ducts Minimum free area...

Страница 10: ...the deck boards Step 5 Remove skid from underneath the boiler Step 6 Lower pipe handles until front adjustable legs touch floor If necessary place wooden blocks under front legs before lowering to pr...

Страница 11: ...cket holes 2 Perform routine inspection service or cleaning as necessary 2 Packaged Boiler Assembly Trim continued 1 TO OPEN BURNER SWING DOOR see Figures 4A and 4B Step 1 Loosen but do not remove lef...

Страница 12: ...12 EMP Installation Service Manual 109529 03 11 19 Figure 4B Top View Burner Swing Door Mounted to Cast Iron Block Assembly Jacket Removed for Clarity 2 Packaged Boiler Assembly Trim continued...

Страница 13: ...crew first Use an alternating tightening method from right side tap bolt to left side tap bolt to tighten door equally until sealed without applying excessive torque Never tighten left side flange bol...

Страница 14: ...y sealant to the 2 NPT injector threads Insert injector into 2 Figure 5 Return Manifold and Relief Valve Assembly Details NPT upper rear tapping on rear section Thread 2 NPT x 1 1 2 Reducing Elbow ont...

Страница 15: ...in Step a NOTE Based on access for servicing and location of sewer or floor drain when tightening these fittings determine if drain valve is to be located on the left or right side Tighten nipple and...

Страница 16: ...flueway baffle in 3rd pass flueway on right side of boiler hold baffle with word Right readable at the top Slide baffle in flueway until position tab touches fins on right side of 3rd pass flueway To...

Страница 17: ...P182E and EMP224E To install flueway baffle in 2nd pass flueway on left side of boiler hold baffle with word Left readable at the top Slide baffle in flueway until position tab touches fins on right s...

Страница 18: ...constant boiler pressure of 12 PSI WARNING Do not operate boiler below minimum volumetric flow rates B CONNECT SYSTEM SUPPLY AND RETURN PIPING TO BOILER See Figures 9A and 9B Also consult I B R Insta...

Страница 19: ...19 EMP Installation Service Manual 109529 03 11 19 Figure 9A Recommended Water Piping for Circulator Zoned Heating Systems 3Water Boiler Piping continued...

Страница 20: ...20 EMP Installation Service Manual 109529 03 11 19 Figure 9B Recommended Water Piping for Zone Valve Zoned Heating Systems 3Water Boiler Piping continued...

Страница 21: ...ected for integrity as well as for proper draft and condensate control Some jurisdictions require the use of a liner when changing fuel types Some jurisdictions require the use of a liner even when th...

Страница 22: ...nt Pipe Arrangement and Chimney Requirements Figure 11 Proper and Improper Locations of Draft Regulator 4 Natural Draft Venting continued 5 Draft Regulator the draft regulator supplied with the boiler...

Страница 23: ...d must be remedied immediately C DRAFT 1 The natural draft generated through a chimney is dependentonseveralfactorsincluding chimney height temperature of flue gases cross section area of chimney chim...

Страница 24: ...he burner from outdoors providing that the criteria for chimney vent connector and minimum stack temperature outlined in this section can be maintained ONLY AVAILABLE WITH BECKETT BURNER Refer to Sect...

Страница 25: ...inimum clearance to combustible material is 0 4 Maximum wall thickness that FDVS vent termination may be installed through is 12 Figure 13 Vent Terminal Location WARNING This venting system must be in...

Страница 26: ...rate the vent hood tee from the vent hood body and set aside for later use 5 After determining the location of the venting system termination cut the square hole in the wall sized according to L dimen...

Страница 27: ...ipment and NFPA 211 Standard for Chimney Fireplaces Vents and Solid Fuel Burning Appliances latest editions For installations in Canada follow requirements of CSA B139 Installation Code for Oil Burnin...

Страница 28: ...ru four holes in the clamp into the flue outlet collar 7 Apply sealant around the adapter end mated to the flue outlet collar 8 Install supplied 3 8 sampling port plug screw hand tight into the adapte...

Страница 29: ...ipe onto the vent termination inner pipe all the way up to the stop bead Secondly push the opposite end of the inner vent pipe onto the appliance adapter all the way up to the stop bead 12 Tighten the...

Страница 30: ...eter galvanized single wall vent pipe cut off the crimped pipe end below stop bead 6 Insert one end of the vent pipe thru the outside air duct bracket opening and firmly push onto the outside air adap...

Страница 31: ...cross the pivot point and plumb Refer to the vacuum relief valve manufacturer s instructions for details 14 Install remainder of air intake piping to Direct Vent Termination air intake collar securing...

Страница 32: ...it will be influenced by drafts hot or cold water pipes lighting fixtures television rays of the sun or near a fireplace Keep large furniture away from thermostat so there will be free movement of roo...

Страница 33: ...ll operate as long as the thermostat is calling for heat If the thermostat is not satisfied and the operating high limit is reached the circulator will continue to operate and the burner will stop unt...

Страница 34: ...34 EMP Installation Service Manual 109529 03 11 19 Figure 24 Schematic Wiring Diagram Water Boiler 6 Electrical continued...

Страница 35: ...3 8 OD copper tubing Copper tubing shall have a 032 minimum wall thickness WARNING Under no circumstances can copper with sweat style connectors be used NOTICE Some jurisdictions require the use of a...

Страница 36: ...tions on the proper connections for a two pipe system Some manufacturers require the insertion of a bypass plug 3 Under no circumstances is a manual shutoff valve to be located on the return line of a...

Страница 37: ...expansion tank g Allow water to overflow from bucket until discharge from hose is bubble free for 30 seconds h When zone valve is completely purged of air close zone valve or shut off valve Open zone...

Страница 38: ...l g SLIGHTLY OPEN FLAME OBSERVATION PORT COVER on burner swing door enough to insert draft gauge probe later 3 Carlin Burners a Remove nozzle line electrode assembly from burner b Verify the desired n...

Страница 39: ...39 EMP Installation Service Manual 109529 03 11 19 Figure 28 L1 and V1 Head Electrode Positioning and Gun Setting Beckett AFG 8 System Start Up continued...

Страница 40: ...e assembly reverse procedure outlines in steps f thru b k Upon reinstallation of the nozzle line assembly check that head air plate setting number pointer line up with a number on the scale which matc...

Страница 41: ...TING flame present 1 ADJUST DRAFT REGULATOR Natural Draft only for a draft of zero inches water gauge in the canopy see Figure 15 after chimney has reached operating temperature and while burner is ru...

Страница 42: ...nes and filters The R7284 can be placed in a purge routine by pressing and releasing the up arrow button during the Trial For Ignition Pump Prime is shown on the oil primary display along with the tim...

Страница 43: ...ood If not install new cell Close hand valve in oil supply line Failure occurs device enters Recycle Mode Figure 34 Cad Cell Location K CHECK HIGH LIMIT 1 Adjust system thermostat s to highest setting...

Страница 44: ...Recommended setting for Four zone systems 5 Recommended setting for Five zone systems HI Provides highest level of fuel savings E Optional Features NOTE The Program Mode Pro is accessed by turning the...

Страница 45: ...s to desired temperatures 6 Setting the Well Type Elctro Well vs Standard Immersion Well When used to replace older temperature only controls the HyrdroStat can be installed on the existing well The H...

Страница 46: ...EMP dial to select feature dEF c Push the Test Setting Button to Y to reset all features to the default settings d Reset LO TEMP and HI TEMP settings to desired temperatures 9 LED Legend and Test Sett...

Страница 47: ...Smart HydroStat will reduce boiler temperature to conserve fuel The Economy feature is activated using the ECONOMY dial See How Thermal Targeting Works for more information f ECONOMY TARGET When the E...

Страница 48: ...tting clothing that is sufficiently tight around potential entry points for RCF dust 3 Gloves 4 Eye protection such as goggles safety glasses with side shields or full facepiece Take steps to assure a...

Страница 49: ...mpany 4 Make pH or Alkalinity Test After boiler and system have been cleaned and refilled as previously described test the pH of the water in the system This can easily be done by drawing a small samp...

Страница 50: ...er is shut down for an extended period of time 3 To recondition the heating system in the fall season after a prolonged shut down follow the instructions outlined in Section VIII WARNING This boiler c...

Страница 51: ...bustion chamber and smoke box B CLEAN THE COMBUSTION CHAMBER Use a wire or fiber bristle brush to clean the surfaces of the combustion chamber Vacuum all of the loose debris in the bottom of the combu...

Страница 52: ...sult if the boiler is connected to a dirty or inadequate chimney The interior of the chimney flue must be inspected and cleaned before the start of the heating season and should be inspected periodica...

Страница 53: ...amounts will stall the fuel pump Water in the fuel in smaller amounts will cause excessive wear on the pump but more importantly water doesn t burn It chills 8 COLD OIL If the oil temperature approach...

Страница 54: ...oil to burner b Shorted electrodes c Nozzle clogged d Airflow too high e Ignitor module defective f CAD cell defective g Oil valve stuck open or closed Note The Safety Monitoring Circuit SMC is design...

Страница 55: ...l If either LWCO LED lights are illuminated and the control is installed on a standard immersion well this is false reading caused by a loss of continuity between the sensor and the inside of the well...

Страница 56: ...p Active LED will be on at all times when the control is powered Check for 120 VAC on terminals L1 and L2 YES Is the Red LED LOW WATER On YES NO Is the Yellow LED HI TEMP On YES The Control is Sensing...

Страница 57: ...rmally NO The burner will continue to fire when there is a call from the thermostat or external zone Is the External Zone ZC ZR Calling for Heat YES The Control is Operating Normally NO Is the Low Lim...

Страница 58: ...ny Wholesale distributor Should you require assistance in locating a U S Boiler Company Distributor in your area or have questions regarding the availability of U S Boiler Company products or service...

Страница 59: ...54 02 1 1 109554 03 1 109554 04 1 109554 05 1 1B Smoke Box Includes Sealant and Hardware 109555 01 1 1 1 1 1 1C Burner Swing Door Assembly Includes Hinge and Hardware 109556 01 1 1 1 1 109557 01 1 1D...

Страница 60: ...60 EMP Installation Service Manual 109529 03 11 19 Jackets and Trim 13 Service Parts continued...

Страница 61: ...2E Electro Well 1 2 NPT x 3 1 4 109566 01 1 1 1 1 1 2F Harness 109562 01 1 1 1 1 1 2G Burner Recepticle 109570 01 1 1 1 1 1 2H Baffle Kit 109991 01 1 109992 01 1 109561 01 1 1 1 2J Injector Kit 10282...

Страница 62: ...40E EMP182E EMP224E Not Shown Beckett Natural Draft 104506 02 1 104507 02 1 104508 03 1 104509 04 1 104510 05 1 Direct Vent 103896 03 1 103897 04 1 103898 05 1 Carlin Natural Draft 110109 02 1 110110...

Страница 63: ...amp FDVS 6 Half 100235 02 2 2 7 Appliance Clamp FDVS 7 Half 100235 03 2 5D Cover Sleeve Assembly FDVS 5 100236 02 2 2 Cover Sleeve Assembly FDVS 6 100236 03 2 5E Cover Ring Assembly FDVS 5 100237 02 2...

Страница 64: ...64 EMP Installation Service Manual 109529 03 11 19 Beckett AFG Burner 13 Service Parts continued...

Страница 65: ...Clamp Screw 4219 4219 4219 4219 4219 Electrode Insulator Assembly 5780 5780 5780 5780 5780 Spider Spacer Assembly 5503 5503 5503 5503 5503 Escutcheon Plate 3493 3493 3493 5941 5941 Adjusting Plate Ass...

Страница 66: ...66 EMP Installation Service Manual 109529 03 11 19 Beckett NX Burner 13 Service Parts continued...

Страница 67: ...Electrodes Insulator Kit 51811U 10 Fuel Unit Single Stage A2EA6520N621L 2184404U Fuel Unit Two Stage 51975U Mounting Screws 1 4 20 x 7 8 4189 11a Gasket Igniter Baseplate 51942U 11b Gasket Igniter Bas...

Страница 68: ...tion and Operating Instructions for Packaged Heating Burner Units Carlin Elite EZ LF and EZ 66 Oil Burners Form CCT 569A for an exploded view of the burner and a list of spare parts For replacement Ca...

Страница 69: ...eadjusted to settings shown above during burner start up Table 9a Beckett AFG Burner Specifications Chimney Vent Table 9b CARLIN EZ Burner Specifications Chimney Vent Boiler Model Burner Input GPH Bur...

Страница 70: ...1 25 45 B Hago 180 11 5 2nd 23 0 07 0 0 06 0 02 Notes 2 The increased stack temperature with the baffles removed is an approximation based on a constant supply temperature of 180 F and 11 5 CO2 Actual...

Страница 71: ..._____________________________________________ __________________________________________________________________________________________________ _______________________________________________________...

Страница 72: ...72 EMP Installation Service Manual 109529 03 11 19 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...