OPERATION
•
If the parameter
r5=0
and the defrost cycle is not activated the
Overcooling cycle
will start:
the cooling unit runs a cycle with a set point of
r6
parameter for the time
r7.
•
If the parameter
r5=1
the unit will perform an
Overheating cycle
having a operational
temperature of “s
r6
” for a time fo
r7.
3.3.9 Activate/deactivate energy saving in manual mode (if r5 = 0)
Check that the keyboard is unlock.
Touch the DEFROST key
, the setpoint becomes “s
r4
” for a max duration of
HE2
.
3.3.10 Displaying/reset the compressor operational time
Check the keypad is unlocked then press the
DOWN key for 2 sec.
Scroll through the menu’s labels by the UP or DOWN key
:
•
CH1
label: displaying compressor operating hours.
•
CH2
label: displaying second compressor operating hours
•
rCH
label: compressor operating hours reset.
•
nS1
label: compressor star-up time.
To access the label press SET
.
In order to reset the compressor operating hours once selected the
rCH
label, insert the password
“
149”
using the UP or DOWN keys
then confirm touching the SET key
Touch the ON/STAND-BY
key to exit the procedure or do not operate for 60 sec.
3.3.11 Displaying temperature probes
Ensure the keypad is unlocked then touch the DOWN key
for 2 sec.
Scroll through the menu’s labels by the Up or DOWN key
:
•
Pb1:
cabinet temperature probe (if parameter
P4=0,1 or 2);
inlet air temperature probe (if
parameter
P4=3
).
•
Pb2:
Evaporator temperature probe (if parameter
P3=1
or
2
)
•
Pb3:
Auxiliary temperature probe (If
P4=1, 2 or 3
).
•
Pb4:
Calculated product temperature (
CPT; P4=3
)
To access the label press SET
.
Touch the ON/STAND-BY
key to exit the procedure or do not operate for 60 sec.
3.3.12 Setting operational parameters
Touch the SET key
for 4 sec, the monitor will display the label “
PA
”.
Press SET key
and insert the password that will be provided only by the manufacturer or
the authorized service agent.
Press SET key to confirm.
Scroll through the parameters list using the UP or DOWN key
.
For modifying a parameter value, press SET key at the parameter label then adjust the value by
the UP or DOWN key
.
Press SET key to confirm the changing.
20
Use and Operational Manual
20
Содержание UCFZ527-SS31A
Страница 25: ...OPERATION 3 3 14 Electrical connection 22 Use and Operational Manual 22...
Страница 26: ...OPERATION 3 3 15 Default parameters value and description 23 Use and Operational Manual 23...
Страница 27: ...OPERATION 24 Use and Operational Manual 24...
Страница 28: ...OPERATION 25...
Страница 29: ...OPERATION 26 26...
Страница 30: ...OPERATION 27 Use and Operational Manual 27...
Страница 31: ...OPERATION 28 Use and Operational Manual 28...
Страница 54: ...51 FUNCTIONNEMENT 3 3 14 Connexion lectrique 90 Use and Operational Manual...
Страница 55: ...FUNCTIONNEMENT 3 3 15 Valeur et description des param tres par d faut 91 Use and Operational Manual 52...
Страница 56: ...53 FUNCTIONNEMENT 92 Use and Operational Manual...
Страница 57: ...FUNCTIONNEMENT 54...
Страница 58: ...55 FUNCTIONNEMENT...
Страница 59: ...FUNCTIONNEMENT 56...
Страница 60: ...57 FUNCTIONNEMENT...