Remove Fan and Cover

Remove Fan and Cover

CONVECTION COOLING

This unit is equipped with an advanced convection cooling 
system. Convection cooling stabilizes cabinet temperature, 

cools product faster and increases energy efficiency.

Evaporator Fan

The evaporator fan is responsible for circulating warm air 
from the refrigeration zone, past the evaporator and back 
into the refrigerated zone.

The evaporator fan is factory set to have a 1 minute delay 
at the beginning of a cooling cycle. This delay gives the 
evaporator time to cool properly before warm air is passed 
over it. The fan will continue to run for an additional 2 
minutes at the end of a cooling cycle. Fan delay times can 

be modified through the service menu.

Evaporator fan operation is also determined by door switch 
state. If the door switch circuit opens, the fan will stop. 
When the door switch circuit is closed the fan will either 
continue running with the cooling cycle, or if not currently 
cooling, the fan will run for 1 minute to circulate air and 
clear any condensation that may have appeared on glass 
doors and shelves.

Note:

 If the unit is set to sabbath mode, the evaporator 

fan will no longer respond to the state of the door switch.

In order to operate efficiently, the evaporator fan blade 

and vents should be unobstructed and free of any dust 
buildup.

Evaporator Fan Replacement

Should the evaporator fan need to be replaced follow the 
steps below.

1.  Remove any product from the unit.

2.  Remove unit from cabinetry to access rear.

3.  Disconnect power to the unit.

4.  Remove back panel from unit.

5.  Disconnect fan electrical connection at rear of unit.

6.  Remove insulating foam from refrigerant line pass-

through hole as needed to gain clearance for fan plug.

7.  Remove internal shelving.

8.  Remove rear shelf clips, fronts can remain.

9.  Remove thermistor cover.

10.   Remove two evaporator cover screws from top of 

evaporator plate.

11.  Grasp evaporator cover, pull forward and up as bottom 

of cover is installed behind the front edge of the drain 
trough.

12.  While pulling the evaporator cover clear of the unit, it 

may be necessary to use your free hand to manipulate 
the fan plug end through the pass-through hole.

13.  Remove the 4 screws mounting the fan shroud to the 

evaporator plate.

Evaporator Cover

Screws

Air Flow

45

Содержание SUHBV124-SG01A

Страница 1: ...USER GUIDE SERVICE MANUAL 1 Class UHBV124 24 Beverage Center...

Страница 2: ...r Adjust Maintenance Free Standing Kit Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation Airflow and Product Loading Recommended Wine Storage Service Wine...

Страница 3: ...lect products are available worldwide PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings Compliance Documentation and Product Warranty informat...

Страница 4: ...or moderate personal injury property or equipment damage This unit contains R600a Isobutane which is a flammable hydrocarbon It is safe for regular use Do not use sharp objects to expedite defrosting...

Страница 5: ...n place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of re...

Страница 6: ...mperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from heat genera...

Страница 7: ...he unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that has be...

Страница 8: ...the front grille must NOT be obstructed and clearance is required for an electrical connection in the rear CAUTION Unit can NOT be installed behind a closed cabinet door CUTOUT DIMENSIONS PRODUCT DIM...

Страница 9: ...ed according to each unit s electrical specifications requirements Side by Side Installation with Bracket 1 Slide both units out so screws on top of units are easily accessible 2 Remove screws as show...

Страница 10: ...ver holes and attach to unit with two screws removed in step 2 using a T 25 Torx driver Tighten screws fully 4 Gently push unit into position Be careful not to entangle the electrical cord or water li...

Страница 11: ...n opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Readjust the front legs to level the unit after it is...

Страница 12: ...are SHARP and can be easily damaged Removing the grille 1 Disconnect power to the unit 2 Loosen the two screws 1 3 Remove grille 2 from unit Installing the grille 1 Align cabinet and grille holes and...

Страница 13: ...ng Units have a zero clearance for the door to open 90 when installed adjacent to cabinets Stainless Steel models require 2 1 8 54 mm door clearance to accommodate the handle if installed next to a wa...

Страница 14: ...Loosen do not remove top and bottom hinge screws using a Torx T 25 screwdriver 3 Align door squarely with cabinet 4 Make sure gasket is firmly in contact with cabinet all the way around the door no ga...

Страница 15: ...ews on either side Install bottom hinge Install two or three screws depending on model Replace nuts if used Install top hinge and door 1 Remove pivot screw from hinge flip hinge over and install the p...

Страница 16: ...to a cabinet Available at u line com To install the kit 1 Remove grille see GRILLE INSTALLATION section 2 Place shell accessory over front and back of cabinet base aligning holes of shell accessory wi...

Страница 17: ...for more details NOTICE Temperature displayed reflects actual temperature inside unit If the temperature displayed is different than selected the unit is progressing towards the selected temperature...

Страница 18: ...r 5 seconds The display will change units Enable Sabbath Mode Press and hold for 5 seconds and release The oF oC symbol will flash briefly after 5 seconds Interior light and display will go dark and r...

Страница 19: ...d sizes Not all bottles and cans will fit on every shelf and wine rack Larger diameter champagne and Magnum bottles only fit on wine racks when noted on the product specifications When determining cap...

Страница 20: ...wine racks properly position the bottles so the wine remains in contact with the cork which ensures the cork does not become dry U Line recommends arranging wine bottles as shown in the illustration...

Страница 21: ...ess steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possible Integrated Models To clean integrated pan...

Страница 22: ...sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in an open position 2 in 50 mm minimum 4 A...

Страница 23: ...nvironmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric power to the unit before cleaning the condenser NOTICE DO NOT use any type of cleaner on the condens...

Страница 24: ...elease lever up Pull the rack out until it is free of the tracks and the cabinet NOTICE Do not remove the track rails from the cabinet To insert rack in the cabinet 1 Align the left and right rack cha...

Страница 25: ...n the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and milde...

Страница 26: ...ompressor makes a hum or pulsing sound that may be heard when it operates BEFORE CALLING FOR SERVICE TROUBLESHOOTING GUIDE ELECTROCUTION HAZARD Never attempt to repair or perform maintenance on the un...

Страница 27: ...ng the testing period 6 After 24 hours check the temperature of the water If required adjust the temperature control in a small increment see CONTROL OPERATION Causes which affect the internal tempera...

Страница 28: ...e White Black N C 1 6 Evap Cond fan Light Evap temp Zone temp Door switch Compressor FUSE Programming U s e r I n t e r f a c e 42376_C If Applicable POWER CORD ASSEMBLY 220 240 VOLT PLUG LIVE BLACK 1...

Страница 29: ...zed to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial number of the unit it was removed from t...

Страница 30: ...ing for warranty labor Units must be registered prior to warranty submittal Customers may register at www U Line com A proof of purchase is required We also accept the following information to update...

Страница 31: ...DIMENSIONS ARE IN INCHES XX 03 XXX 015 X 1 HOLE 010 004 REMOVE BURRS AND SHARP EDGES TO 015 MAX INTERPRET DIM AND TOL PER ASME Y14 5M 1994 DO NOT SCALE DRAWING THIRD ANGLE PROJECTION THIS DRAWING IN...

Страница 32: ...rovide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original parts we will inform you when the parts o...

Страница 33: ...cian must observe all federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder t...

Страница 34: ...cuum pump and recovery equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the sys...

Страница 35: ...erant is left within the system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing...

Страница 36: ...Install a Schrader Type access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two...

Страница 37: ...erature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near room temperature Very hot Top passes war...

Страница 38: ...aring an anti static wrist strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance m...

Страница 39: ...2547 for assistance NORMAL OPERATING SOUNDS All models incorporate rigid foam insulated cabinets to provide high thermal efficiency and maximum sound reduction for its internal working components Des...

Страница 40: ...Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining cabinetry Check distribution of product in unit Thermistor failure OHM thermistor...

Страница 41: ...e Plunger Switch Replace Main Board Replace Fuse Replace Power Cord Alert Customer Of Power Failure Is the Plunger Switch Operating Properly Inspect Customer UI and Data Cable Connect Test Display Cyc...

Страница 42: ...LED activated with button activation CONTROL FUNCTION GUIDE FUNCTION COMMAND NOTES Defrost Duration Enter menu by pressing for more than 5 seconds Use or to increase reduce defrost duration Press to...

Страница 43: ...E Zone Thermistor If the zone thermistor in the unit fails the unit will continue to cool in a backup mode Self Preservation Mode to preserve the integrity of the contents The unit will otherwise oper...

Страница 44: ...or units defrost every 12 hours of compressor runtime for 45 minutes If you have verified that the unit does not have an ambient air leak utilize the Control Operation Service section and adjust unit...

Страница 45: ...ondensation that may have appeared on glass doors and shelves Note If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In order to operate effi...

Страница 46: ...ator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assure the bottom of the evaporator cover is reinstalled behind the front...

Страница 47: ...d or other natural disasters The product must be installed operated and maintained in accordance with your product s User Guide The remedies described above for each warranty are the only ones that U...

Отзывы: