Troubleshooting - Extended 4
u-line.com
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE •
SERVICE
Other Suspected Main Control Faults
If other components have been ruled out as being faulty
but the unit continues to have operating issues, it is most
likely due to a configuration error. Configuration errors
can be cleared by restoring the unit to its factory default
setting. Factory defaults may be restored through the
service menu.
CAUTION
!
Precautions must be taken while working with
live electrical equipment. Be sure to follow
proper safety procedures while performing tests
on live systems.
CONVECTION COOLING
All 3000 series units are equipped with an advanced
convection cooling system. Convection cooling stabilizes
cabinet temperature, cools product faster and increases
energy efficiency.
Evaporator Fan
The evaporator fan is responsible for circulating warm air
from the refrigeration zone, past the evaporator and back
into the refrigerated zone.
The evaporator fan is factory set to have a 1 minute delay
at the beginning of a cooling cycle. This delay gives the
evaporator time to cool properly before warm air is passed
over it. The fan will continue to run for an additional 2
minutes at the end of a cooling cycle. Fan delay times can
be modified through the service menu.
Evaporator fan operation is also determined by door
switch state. If the door switch circuit opens the fan will
stop. When the door switch circuit is closed the fan will
either continue running with the cooling cycle, or if not
currently cooling, the fan will run for 1 minute to circulate
air and clear any condensation that may have appeared
on glass doors and shelves.
NOTE: If the unit is set to sabbath mode the evaporator
fan will no longer respond to the state of the door switch.
In order to operate efficiently the evaporator fan blade
and vents should be unobstructed and free of any dust
buildup.