Troubleshooting - Extended 2
USER GUIDE
u-line.com
Market/Fresh
10 min.
45 min.
Root
5 min.
90 min.
Pantry
10 min.
45 min.
Deli
10 min.
45 min.
Zone Thermistor
If the zone thermistor fails, the unit will continue to
operate in a timed limp mode which varies by model.
The unit will otherwise operate normally. The error
will be displayed in the error log.
Evaporator Thermistor
If the evaporator thermistor fails, the unit will rely on
a preset defrost time during defrost cycles. The unit
will otherwise operate normally. Evaporator
thermistor errors will be displayed in the error log.
Always assure that all thermistor connections are
clean and dry. Whenever opening a thermistor
connection be sure to apply a fresh dab of die electric
grease.
REED SWITCH
A reed switch is used to monitor door state. When the
door is closed magnetic force pulls the reed to its
contact and closes the circuit which turns the light and
display off. When the door is open the reed pulls away
from the contact and opens the circuit. If the door is
left open for longer than 5 minutes, the switch will
trigger an error code and set an audible warning.
(Switch Closed)
Magnet Away From Switch
)
Door Open
(
Switch Open
(
)