SPECIFICATIONS
Electrical
Input:
120VAC, 60Hz, +/-10%
Isolated Output:
24VDC @150mA
Power Output:
1920W/VA total
1000W/VA max. per zone
1200W/VA max. per side
Minimum Load:
15W
Surge protection:
Surge Suppression for voltage surges up to
6000V and current surges up to 3000A
Load Types:
Incandescent, Tungsten, Magnetic Low-Voltage
Transformer, Advance Mark X Electronic
Fluorescent Dimming Ballast, Neon, Cold
Cathode, and non-dimming loads
Testing/Code Compliance: UL Listed, CSA Certified
FCC Statement:
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device must not cause
harmful interference, and (2) This device must
accept any interference received, including
interference that may cause undesired operation.
Real Time Clock:
Accurate within 15 seconds per week,
with or without power
Leap year compensation
Calculating of Sunrise and Sunset, given
the correct latitude and longitude, to within
15 minutes
Environmental
Operating Temperature:
0
°
C to +40
°
C
Software
Programmer has been specified with sufficient permanent memory for 20
years to hold :
- 32 Scenes
- 64 Time schedules