Qwik Install

 

STEP 1:

 

Prepare the enclosure:  Install DIN rail (if required) to door 

using two Philips head screws. Install just the top mounting bracket to 

the enclosure using two 8mm bolts.

 

NOTE:

 

It takes two people to mount the 

enclosure to a pole. The standard U

-

Bolt mounting accommodates a pole up 

to 

4” 

diameter. Multiple pole straps can 

be used for extra strength. Pole straps 

are available for poles up to 

11” 

diame-

ter or larger.

 

STEP 2:

 

 

Install  the bottom bracket 

and stabilizer bracket to the pole using 

U

-

Bolt and/or Pole Straps. The stabi-

lizer bracket is used as an aid to 

mounting and additional support when 

mounted.

 

STEP 3:

  Lift the enclosure and place it 

on the stabilizer bracket. Connect the 

top bracket to the pole using U

-

Bolt 

and/or Pole Straps.

 

STEP 4:

 

Attach The two 8mm bolts that 

hold the bottom bracket to the enclo-

sure. Make sure all bolts are tight. (8

-

15 

ft lbs)

 

STEP 5:

  Install the three wire feedthru 

cable glands in the holes in the bottom 

of the enclosure. If one or more of the 

cable glands will not be used, just cut a 

short piece of wire and tighten in the 

cable gland.

 

NOTE: 

The bottom plate can be re-

moved from the enclosure if you need 

to add some additional feedthru. (ex; 

conduit connection)

 

STEP 6:

  Install the batteries in the enclosure. There 

must be at least four batteries connected in series to 

create 48V. If eight batteries are used connect first 

four in series and second four in series then parallel 

the two banks. (See wiring diagram). 

 

Note: 

The enclosure has slot features that can be 

used to strap the batteries if desired. Tycon

®  

has vel-

cro straps available. It takes two straps per battery.

 

Содержание UPS-STL48-50

Страница 1: ... lights and power circuits Contact with power lines lights or power circuits may be fatal We rec ommend to install no closer than 20 feet to any power lines Safety For your own protection follow these safety rules Perform as many functions as possible on the ground Do not attempt to install on a rainy windy or snowy day or if there is ice or snow accumulation at the install site or if the site is ...

Страница 2: ...ket to the pole using U Bolt and or Pole Straps STEP 4 Attach The two 8mm bolts that hold the bottom bracket to the enclo sure Make sure all bolts are tight 8 15 ft lbs STEP 5 Install the three wire feedthru cable glands in the holes in the bottom of the enclosure If one or more of the cable glands will not be used just cut a short piece of wire and tighten in the cable gland NOTE The bottom plate...

Страница 3: ...ross one of the batteries in the array STEP 7 Before attaching the battery cables to the batteries first re move the battery cable fuse This will prevent accidental short circuit Connect the battery cables to the batteries Con nect the Temperature probe from the controller to any of the battery terminals The temperature sens ing lug is just a mechanical connection so it doesn t matter which termin...

Страница 4: ...po sition on the large Green connector Connect the Output from the power supply to the PV on the large Green connector WARNING Be sure to make sure the polarity is correct before powering the system or you will damage the controller STEP 11 Connect your AC input wires to the power supply at the screw terminal labeled LNG L Load N Neutral G Ground STEP 12 Connect your equipment to the controller an...

Страница 5: ...elow a set value This value can be set in the user inter face This low voltage disconnect function is needed to preserve the life of the batteries SPECIFICATIONS Subject to change without notice UPS STL48 50 UPS STL48 100 Load Voltage 24V 48V Selectable 24V 48V Selectable Max Load 200W 200W VAC Input 10 115 230VAC user selectable VAC Input Current 12A 115VAC 6A 230VAC Max Battery Capacity 200Ah 40...

Страница 6: ...ds to the controller voltage output This output will discon nect the load if the battery voltage drops below the set voltage and this will protect the battery from over discharge If batteries get completely discharged because the equipment was connected directly to the bat tery you will reduce the battery life Discharged batteries will freeze at very low temperatures 7 ACCESSORIES Tycon also offer...

Страница 7: ...7 ...

Страница 8: ...8 8000050 Rev 3 UPS STL UPSPro Qwik Install Guide ...

Отзывы: