18.1 Repeater User Indications
Refer to Figure 18.
General Indicator Section
Indicator Description
Indication
Colour
Operating Condition
Power Supply On
Green
Illuminates Steady for Mains or Standby power On.
Fire
Red
Flashes on any new fire alarm condition, changing to a steady
indication on operation of Silence Alarms.
Fire Output Active
Red
Illuminates Steady when the Fire Output is active.
General Fault
Yellow
Flashes for any fault condition.
Power Supply Fault
Yellow
Flashes for mains or standby power supply/charge fault on the panel.
System Fault
Yellow
Illuminates Steady to indicate microcontroller failure.
General Test
Yellow
Illuminated when Test Mode is active.
General Disablement
Yellow
Illuminated while any disablement is active.
Communication Fault
Yellow
Flashes for a repeater communication fault.
Sounder Fault/Disabled
Yellow
Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test
Yellow
Illuminates Steady while sounder walk test is active.
Fire Protection
Fault/Disabled
Yellow
Flashes for a fault on the Fire Protection Output. Steady when Fire
Protection Output is disabled.
Fire Output
Fault/Disabled
Yellow
Flashes for a fault on the Fire Output. Steady when Fire Output is
disabled.
Fault Output
Fault/Disabled
Yellow
Flashes for a fault on the Fault Routing Output. Steady when Fault
Routing Output is disabled.
18.2 Repeater User Controls
Refer to Figure 18.
Switch Description
Functionality
Button Availability
Manual Fire Alarm or
Muster
[Configuration option
at Panel]
1] Manual Fire Alarm: Operates all sounders
continuously and lights the Manual Fire Alarm LED
adjacent to the button until the silence button is
operated.
2] Muster: Operates all sounders in the Muster mode
until the silence button is operated.
When controls are unlocked.
[May be disabled if external
muster system is used].
Silence/Resound
Alarms
Following a fire alarm condition, 1st operation stops
the sounders. The General Fire LED and the Zonal
Fire LED will change from flashing to steady. 2nd
operation restarts the previously silenced sounders.
When controls are unlocked.
Reset
Clears the panel display, resets the zones, outputs and
operates the reset relay.
When controls are unlocked
and [if Silence Before Reset
is configured] alarms
silenced.
Silence Buzzer
Press to stop the buzzer sounding in fire or fault
conditions.
When controls are locked or
unlocked.
Delay Override
Overrides the delay when delay is running, turning the
delay off. All delayed outputs will operate immediately.
When the panel is in the fire
condition and the delay is
running.
Test Display
Press to illuminate all LEDs on the display and operate
the buzzer. All indications remain active for approx 5
seconds after button release. Press again while LEDs
are illuminated to toggle the brightness setting
between high & low.
When controls are locked or
unlocked.