EQUIPMENT:
T1200-C
PUBLICATION:
MARINEC-P-A
ISSUE No. & DATE:
3
02/14
© 2014 Thorn Security Ltd
PAGE 17 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
5.2
Features List
Enclosures
Tough welded mild steel enclosures with high quality paint finish.
Removable gland-plate for termination and looming.
Optional door stay available for all panels except T1204A1,
T1204A2, T1204DC.
Temperature-compensated battery
charging
Battery charging voltage is automatically adjusted between
28.25 and 26.72V DC over an ambient temperature range of
-10°C to +55°C.
Battery disconnect
Protects the battery from permanent damage due to deep
discharge by automatically disconnecting it when the battery
voltage falls below 21V.
Mains Failed Indication Delay
The indication of main power failure is delayed by 90 seconds to
allow the power to be switched from ship to shore and vice versa
without generating a false fault indication.
Total power failure warning on the fire
panels
A separate, non-rechargeable 9V battery provides the power for
an audible warning should the primary [ship’s] supply and the
panel’s standby battery fail (or be disconnected).
Class change input
Operates all sounders for up to 5 seconds without giving any
panel indications (this is a land-based feature).
Configurable detection zones
Simple and flexible configuration process utilising the LED
display, allowing detection zones to be configured for any or all
of the following:
•
Latching or non-latching Fire indication.
•
Normal or Intrinsically-Safe zone monitoring.
•
Machinery Space Zones.
Factory configuration: Latching, standard [non-I.S.], no zones
programmed as Machinery Space Zones.
Selectable Zonal or General Alarm
Sounder operation with sounders in alert
or silent in non-alarm zones
Selectable via DIL switches on the motherboard.
The standard sounders on the T1204 panel can be used in
General or Zonal modes. [On T1216-C and T1232-C panels
these sounders always operate in General mode regardless of
DIL switch setting].
The output expansion system provides additional sounder
circuits for General or Zonal use on the T1216-C and T1232-C
panels.
General sounder operation continuous or
pulsed
DIL switch selectable on the motherboard. All sounders operate
continuously or pulsed as selected.
Restart sounders or restart sounder delay
DIL switch selectable on the motherboard. With the panel in the
silence alarms condition, a 2
nd
zone fire condition restarts the
sounder delay or immediately operates all sounders.
[This is
available only when panel is configured to the Crew Alarm
Mode.]