background image

© 2019 Johnson Controls. All rights reserved. JOHNSON CONTROLS, TYCO and KANTECH are trademarks and/or registered trademarks.  
Unauthorized use is strictly prohibited.  
Tel.: 1 (450) 444 2030 • Toll Free: 1-888-222-1560 • 

www.kantech.com

 

DN1776-19

1

1

KT-MOD-INP16 

KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet 

1.

Introduction

The 

KT-MOD-INP16

 is an input module that adds up to 16 zones

to the 

KT-400

 controller. The module supports daisy chaining;

you can interconnect up to 15 KT-MOD-INP16 modules for a total

of 240 external inputs per KT-400. Adding the 16 onboard inputs

of the KT-400 gives a total of 256 inputs per KT-400. Combining

input and output expansion modules gives the flexibility to

connect up to 256 inputs and 256 outputs.

Note 1

: The KT-400 SPI port maximum current draw, when the

12V AUX terminals are not used, is 500 mA.

Note 2

: External power supply (12 VDC, 2 Amps) is required

when the total current draw exceeds 500mA on the SPI Port.

2.

Specifications

Maximum Current Draw: up to 40 mA per module

Supports single end-of-line (5.6 K

Ω) resistor, double end-of-

line resistor and no end-of-line (DRY) zone loops

Supports Normally Closed (NC) and Normally Open (NO)
contacts

The C (Common) terminal is GND

Input change with a debouncing of 500 ms (Slow) or
150 ms (Fast)

Report conditions per input: 

SECURE

 or 

ALARM

 in single

end-of-line and no end-of-line zone loops, and 2 additional
conditions 

TAMPER

 and 

TROUBLE

 in double end-of-line

zone loops

Can be used for contact or elevator input

Cannot be connected to output modules KT-MOD-REL8 and
KT-MOD-OUT16 through SPI OUT, only through its SPI EXP
expansion port

Operating Temperature: -10C to +55C, 0C to 49C for UL
Listed product

Maximum Humidity: 93% (non condensing), 0 to 85% (non
condensing) for UL Listed product

IP Class 3X, IK Rating 04 (when mounted in a Kantech
cabinet). IP and IK rating not evaluated by Underwriters
Laboratories.

3.

Installing the KT-MOD-INP16 Module

3.1. Unpacking

The

 KT-MOD-INP16

 package includes the following parts:

One (1) KT-MOD-INP16 module, 14 cm x 8 cm (5.7 in x 3.25
in)

One (1) SPI cable with 1 SPI connector, 41 cm (16 in)

16x 5.6K Ohms ½ Watt Resistor

Four (4) plastic standoffs

Two (2) installation sheets, English and French

3.2.  Mounting 

The 

KT-MOD-INP16

 can be installed inside a compatible cabinet 

(KT-MOD-CAB or KT-400) or mounted in a dry and secure 

location at less than 1 m (3 ft) from the KT-400. 

1.

Press the four (4) plastic standoffs through the mounting

holes of the cabinet,

2.

Secure the cabinet to the wall in the desired location. Use
appropriate wall anchors when securing the cabinet to
drywall, plaster, concrete, brick or other surfaces.

3.

Press the module into the plastic standoffs to secure the

module to the cabinet.

3.3. SPI Wiring 

Perform the following steps to complete wiring: 

Note 1

: Before beginning to wire the unit, ensure that all power 

(AC transformer and battery) is disconnected from the KT-400. 

Note 2

:

 

If you are combining input and output modules through 

the SPI EXP expansion port of the KT-MOD-INP16, the input 

module must be the 1

st

 module connected to the KT-400 SPI 

Port.  

1.

Connect the 6-pin SPI connector to the KT-400 SPI port or to

the SPI OUT of the previous KT-MOD-INP16 module.

2.

Connect the six SPI wires (blue (BLU), white (WHT), green

(GRN), yellow (YEL), black (BLK) and red (RED)) to the SPI

IN (TB1) terminals.

3.

You can use the SPI EXP of the 1

st

 KT-MOD-INP16 to start a

group of output modules (

KT-MOD-REL8

 and 

KT-MOD-

OUT16 only

).

4.

Connect the 6-pin SPI connector from the SPI OUT to the

next KT-MOD-INP16 module.

5.

Complete all zone wiring to the zone input terminals (Z1-Z16).

Отзывы: