Tyco Kantech KT-MOD-INP16 Скачать руководство пользователя страница 2

© 2019 Johnson Controls. All rights reserved. JOHNSON CONTROLS, TYCO and KANTECH are trademarks and/or registered trademarks.  
Unauthorized use is strictly prohibited.  
Tel.: 1 (450) 444 2030 • Toll Free: 1-888-222-1560 • 

www.kantech.com

 

DN1776-19

1

1

KT-MOD-INP16 

KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet 

3.4.  Check the power jumper JP5 position. Put it on EXT if you 

need external power or INT if no external power is required. 

Note

: In double end-of-line resistor configuration (JP4 ON position), 

only 8 zone inputs (Z1 through Z8) are operational. Z9 through Z16 
are operational only in single and no end-of-line configurations (JP4 
OFF position). This configuration is available from firmware version 
1.03 and later.  

Interconnection is still limited to 15 KT-MOD-INP16 modules for a total 
of 120 external double end-of-line inputs per KT-400.

 

4.

Configurations with Jumpers

There are 4 jumpers available to configure the KT-MOD-INP16.

The jumper settings apply to 

ALL

 inputs at the same time.

DRY (no end-of-line resistor):

 In a simple NC dry contact

configuration, the 

secure

 state is given when a short is detected.

The voltage becomes lower than the 

Level 1

 threshold value

(1.1V).

The 

alarm

 state is given when the input is open. The voltage

becomes higher than the 

Level 2

 threshold value (3.75V). If the

alarm switch is programmed as NO device, the 

alarm

 state will

be given when the input is shorted.

EOL (single end-of-line resistor):

 For NC device, the 

secure

state is given when a single resistor is detected. The voltage

becomes lower than the 

Level 3

 threshold value (2.9V) and

higher than the 

Level 2

 threshold value (2.25V).

The 

alarm

 state is given when the input is open or short. The

voltage becomes higher than the 

Level 4

 threshold value (3.75V)

or lowers than the 

Level 1

 threshold value (1.1V). If the alarm

switch is programmed as NO device, the 

alarm

 state will be given

when a single resistor is detected.

DEOL (double end-of-line resistor):

 Both Alarm and Tamper

switches always operate as NC devices. The 

secure

 state is

given when a single resistor is detected. Corresponding digital

reading is lower than the 

Level 3

 threshold value (2.9V) and

higher than the 

Level 2

 threshold value (2.25V). The 

alarm

 state

is given when double resistors in series are detected.

Corresponding digital reading is lower than the 

Level 4

 threshold

value (3.75V) and higher than the 

Level 3

 threshold value (2.9V).

The 

trouble

 state is given when the input is shorted.

Corresponding digital reading is lower than the 

Level 1

 threshold

value (1.1V). The 

tamper

 state is given when the input is left

open. Corresponding digital reading is higher than the 

Level 4

threshold value (3.75V).

Double End-of-Line resistor functionality not evaluated by

Underwriters Laboratories.

5.

Applying Power

After all wiring is completed, connect the 16 VAC to the KT-400.

Connect the battery leads to the battery, and then apply power to

the AC transformer.

Note

: Do not connect power until all wiring is complete. 

This module provides access point control (5) as per EN50133-1. 

Certified by Telefication under the requirements of EN50133-1 and 

EN50130-5 Class II. 

Отзывы: