TFP332
Page 3 of 4
Storage Type
NFPA
FM Global
(Upright Sprinklers Only)
Sprinkler Type
Standard Coverage
Storage
Response Type
SR
SR
System Type
Wet and Dry
Wet and Dry
Temperature Rating ºF (ºC)
1
155°F (68°C)
1
200°F (93°C)
286°F (141°C)
155°F (68°C)
1
200°F (93°C)
286°F (141°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13
Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13
Refer to FM 2-0 and 8-9
Idle Pallet Storage
Refer to NFPA 13
Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage
Refer to NFPA 13
Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard)
Refer to NFPA 13
Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard)
Refer to NFPA 30
Refer to FM 7-29
Aerosol Storage
(Refer to the Standard)
Refer to NFPA 30B
Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
Refer to NFPA 13
N/A
Notes:
1. Refer to Table C for laboratory listings and approvals.
N/A – Not Applicable
TYPE
TEMPERATURE
BULB
LIQUID
SPRINKLER FINISH
NATURAL BRASS
UPRIGHT
K=16.8 (TY7151)
155°F (68°C)
Red
1, 2, 3, 4
200°F (93°C)
Green
286°F (141°C)
Blue
PENDENT
K=16.8 (TY7251)
155°F (68°C)
Red
1, 2, 4
200°F (93°C)
Green
286°F (141°C)
Blue
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL Listed).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM Approved).
4. Approved by the City of New York under MEA 177-03-E.
TABLE B
MODEL K17-231 UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TABLE C
LABORATORY LISTINGS AND APPROVALS
(Refer To The Design Criteria Section)