Design 

Criteria

UL and C-UL Listing Requirements

The TYCO 16.8 K-factor, Model K17-231 

Sprinklers may be installed in accor-

dance with NFPA 13 standard sprinkler 

position and area/density flow calcu-

lation requirements for light, ordinary, 

or extra hazard occupancies with a 

minimum residual (flowing) pressure of 

7 psi (0,5 bar) in wet or dry pipe sprin-

kler systems, or they may be installed 

in accordance with NFPA 13 standard 

sprinkler position and area/density 

flow calculation requirements for high 

piled storage occupancies (solid piled, 

palletized, rack storage, bin box, and 

shelf storage including but not limited 

to Class I-IV and Group A plastics) with 

a minimum residual (flowing) pressure 

of 7 psi (0,5 bar) for wet or dry pipe 

systems.
The following two examples are typical 

of the types of arrangements permit-

ted by NFPA 13. For all combinations 

of lesser and greater building heights, 

lesser and greater storage heights, 

storage arrangements, commodity 

classifications, and lesser or greater 

required design densities, refer to 

NFPA 13 for specifics.

Example 1:

 NFPA 13 provides ceiling 

only protection (that is, no in-rack 

sprinklers) criteria using open frame 

(that is, no solid shelves) single, double, 

multiple-row, or portable rack storage 

(without the need for in-rack sprinkler 

protection) of cartoned unexpanded 

Group A or B plastics, or, cartoned 

expanded Group A or B plastics, with:
•  a storage height of up to 20 ft  

(6,1 m);

•  a maximum ceiling height of 27 ft 

(8,2 m);

•  a minimum deflector to top of stor-

age clearance of 18 in. (457 mm);

•  a minimum design density of 0.60 

gpm/ft

2

 (24,4 mm/min);

•  a minimum residual (flowing) pres-

sure of 7 psi (0,5 bar);

•  a minimum design area of 2000 ft

2

 

(186 m

2

) for wet systems or 2600 ft

2

 

(242 m

2

) for dry pipe systems

Example 2:

 NFPA 13 provides ceiling 

only protection (that is, no in-rack 

sprinklers) criteria using open frame 

(that is, no solid shelves) single, double, 

multiple-row, or portable rack storage 

(without the need for in-rack sprinkler 

protection) of cartoned unexpanded 

Group A or B plastics, or, cartoned 

expanded Group A or B plastics, with:
•  a storage height of up to 25 ft 

(7,6 m);

•  a maximum ceiling height of 30 ft 

(9,1 m);

•  a minimum deflector to top of stor-

age clearance of 18 in. (457 mm);

•  a minimum design density of 

0.80 gpm/ft

2

 (32,6 mm/min);

•  a minimum residual (flowing) 

pressure of 7 psi (0,5 bar);

•  a minimum design area of 2000 ft

2

 

(186 m

2

) for wet systems or 4500 ft

2

 

(418 m

2

) for dry pipe systems

FM Approval Requirements

The TYCO 16.8 K-factor, Model K17-231 

(TY7151) Upright Sprinklers may be 

installed in accordance with the appli-

cable control mode density/area guide-

lines provided by Factory Mutual. (FM 

guidelines may differ from UL and C-UL 

Listing criteria.)

Item

Description

Sprinkler Identification Number (SIN)

TY7151 

TY7251

TY7151 is a redesignation for C7151, G1888, and S8040
TY7251 is a redesignation for C7251, G1889, and S8041

K-factor, (gpm/psi) (lpm/bar)

16.8 gpm/psi

½

 (241,9 lpm/bar

½

)

Temperature Rating ºF (ºC)

1

155°F (68°C)

1

200°F (93°C)

286°F (141°C)

Thread Size

3/4 in. NPT

Sprinkler Orientation

Upright and Pendent

Maximum Working Pressure, psi (bar)

175 psi (12,1 bar)

Note:

1.  Refer to Table C for laboratory listings and approvals.

*

*

*

UPRIGHT

PENDENT

CROSS SECTION

1

2

3

4

5

6

-

2

Button

Compression

Screw

Bulb

Sealing Assembly

-

6

-

4

5 -

3 -

Frame

1 -

Deflector

2-3/8"

(60,3 mm)

WRENCH

FLAT

Temperature rating is

indicated on deflector.

1/2"

(12,7 mm)

NOMINAL

MAKE-IN

3/4"

NPT

FIGURE 1 

MODEL K17-231 UPRIGHT (TY7151) AND PENDENT (TY7251) SPRINKLERS

TABLE A 

MODEL K17-231 UPRIGHT AND PENDENT SPRINKLER 

TECHNICAL DATA