Tyco K17-231 Скачать руководство пользователя страница 1

Model K17-231 — 16.8 K-factor 

Upright and Pendent Sprinklers 

Standard Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP332

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

ble standards of the National Fire Pro-

tection Association, in addition to the 

standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

Refer to Table A for sprinkler identifica-

tion numbers.

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved 

NYC Approved

Refer to Table C for specific details on labo-

ratory listings and approvals. The approvals 

apply to the service conditions indicated in 

the Design Criteria section.

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Bulb (5 mm) . . . . . . . . . . . . . . . . . . . . . . . . . Glass

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Additional Technical Data

Refer to Table A for additional techni-

cal data.

General 

Description

The TYCO 16.8 K-factor, Model 

 

K17-231, Standard Response, Standard 

Coverage, Upright and Pendent Sprin-

klers (Ref. Figure 1) are automatic sprin-

klers of the frangible bulb type. They 

are standard response spray sprinklers 

which produce a hemispherical water 

distribution pattern below the deflector.
The 16.8 K-factor, K17-231 Sprinklers 

were subjected to full scale, high-piled 

storage, fire tests to qualify their use 

in lieu of 8.0 or 11.2 K-factor standard 

spray sprinklers for the protection of 

high-piled storage.
Higher flow rates can be achieved at 

much lower pressures with the 16.8 

K-factor, K17-231 Sprinklers — making 

their use highly advantageous in high 

density applications, such as the pro-

tection of high-piled storage.
Applications for the 16.8 K-factor, 

Model K17-231 Pendent and Upright 

Sprinklers are expanding beyond the 

current listings/approvals. For infor-

mation regarding research fire tests 

which may be acceptable to an author-

ity having jurisdiction, please contact 

the Technical Services Department.

NOTICE

The 16.8 K-factor, Model K17-231 

Upright and Pendent Sprinklers 

described herein must be installed 

and maintained in compliance with 

this document and with the applica-

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and flow water.