TFP690
Page 3 of 4
Care and
Maintenance
Issue D QUARTZOID 5.6K and 8.0K
Upright and Pendent, Standard
Response, Standard Coverage Sprin-
klers must be maintained and serviced
in accordance with this section.
Before closing a fire protection system
control valve for maintenance work on
the fire protection system that it con-
trols, permission to shut down the
affected fire protection system must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section for more information.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 25), in addi-
tion to the standards of any authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
K-FACTOR
SPRINKLER
TYPE
TEMPERATURE
RATING
BULB
LIQUID COLOR
SPRINKLER FINISH
5
NATURAL
BRASS
CHROME
PLATED
LEAD
COATED
5.6
1/2 in. NPT
UPRIGHT (TY3191)
and
PENDENT (TY3296)
400
°F (204°C)
Black
1, 2, 3
1, 2, 3
1, 2
500
°F (260°C)
Black
1, 2, 3, 4
650
°F (343°C)
Black
3
N/A
8.0
3/4 in. NPT
UPRIGHT (TY4191)
and
PENDENT (TY4292)
400
°F (204°C)
Black
1, 2
1, 2
500
°F (260°C)
Black
Notes:
1. UL Listed
2. C-UL Listed
3. FM Approved
4. LPCB Approved
5. Where Lead Coated sprinklers are noted to be UL and C-UL Listed, the
sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers
N/A – Not Applicable
TABLE A
ISSUE D QUARTZOID UPRIGHT & PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS