TFP690

Page 3 of 4

Care and 

Maintenance

Issue D QUARTZOID 5.6K and 8.0K 

Upright and Pendent, Standard 

Response, Standard Coverage Sprin-

klers must be maintained and serviced 

in accordance with this section.
Before closing a fire protection system 

control valve for maintenance work on 

the fire protection system that it con-

trols, permission to shut down the 

affected fire protection system must 

be obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
The owner must assure that the sprin-

klers are not used for hanging any 

objects and that the sprinklers are only 

cleaned by means of gently dusting 

with a feather duster; otherwise, non-

operation in the event of a fire or inad-

vertent operation may result.

Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers - before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. Refer to the Instal-

lation section for more information.

The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (e.g., NFPA 25), in addi-

tion to the standards of any authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

K-FACTOR

SPRINKLER 

TYPE

TEMPERATURE 

RATING

BULB 

LIQUID COLOR

SPRINKLER FINISH

5

NATURAL 

BRASS

CHROME 

PLATED

LEAD 

COATED

5.6 

1/2 in. NPT

UPRIGHT (TY3191) 

and 

PENDENT (TY3296)

400

°F (204°C)

Black

1, 2, 3

1, 2, 3

1, 2

500

°F (260°C)

Black

1, 2, 3, 4 

650

°F (343°C)

Black

3

N/A

8.0 

3/4 in. NPT

UPRIGHT (TY4191) 

and 

PENDENT (TY4292)

400

°F (204°C)

Black

1, 2

1, 2

500

°F (260°C)

Black

Notes:

1.  UL Listed
2.  C-UL Listed
3.  FM Approved
4.  LPCB Approved
5.  Where Lead Coated sprinklers are noted to be UL and C-UL Listed, the 

sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers

N/A – Not Applicable

TABLE A 

ISSUE D QUARTZOID UPRIGHT & PENDENT SPRINKLERS 

LABORATORY LISTINGS AND APPROVALS