Tyco FSC 80 K-factor Flush Sprinkler Скачать руководство пользователя страница 6

Care and 

Maintenance

The TYCO Model FSC 80 K-factor Flush 

Sprinkler Concrete Sprinklers must be 

maintained and serviced in accordance 

with this section:
Service inspections should be made 

on a regular basis to detect possible 

damage or alterations to the sprinkler 

and escutcheon. Inspections should in-

clude making certain that the escutch-

eon is held fast to the mounting sur-

face. Damaged or altered sprinklers 

are to be replaced immediately to avoid 

personal injury and to prevent use for 

causing personal injury, as well as to 

maintain the sprinkler system in an op-

erative condition.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, obtain permission to shut 

down the affected fire protection sys-

tem from the proper authorities and no-

tify all personnel who may be affected 

by this action.
Sprinklers which are found to be leak-

ing or exhibiting visible signs of corro-

sion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-

age to the sprinklers - before, during, 

and after installation. Sprinklers dam-

aged by dropping, striking, wrench 

twist/slippage, or the like, must be 

replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. (Ref. Installation 

Section.)
Frequent visual inspections are recom-

mended to be initially performed for 

sprinklers installed in potentially corro-

sive atmospheres to verify the integrity 

of the materials of construction as they 

may be affected by the corrosive con-

ditions present for a given installation. 

The owner is responsible for the in-

spection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the approval agency and standards 

of any other authority having jurisdic-

tion. Contact the installing contractor 

or sprinkler manufacturer regarding any 

questions.
Sprinklers are recommended to be in-

spected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product description and Part 

Number (P/N).

Sprinkler Assemblies

Specify: Model FSC 80 K-factor Flush 

Sprinkler Concrete Sprinklers Quick 

Response Standard Coverage, 74°C 

(165°F), with Thread Extension and 

Adapter, with (specify) finish and P/N 

(specify).

White  . . . . . . . . . . . . . . . . . . . . P/N 50-313-4-165
Gray  . . . . . . . . . . . . . . . . . . . . . P/N 50-313-9-165
Concrete Installation Kit (Incl. Installation Cup, 
Cup Insert, and O-Ring)  . . . . . P/N 91-313-1-110

Separately Ordered 

Parts for Sprinkler

Flush Sprinkler Concrete Sprinkler:

White  . . . . . . . . . . . . . . . . . . . . P/N 51-313-4-165
Gray  . . . . . . . . . . . . . . . . . . . . . P/N 51-313-9-165
Extension Thread. . . . . . . . . . . P/N 91-313-1-008
Adapter  . . . . . . . . . . . . . . . . . . P/N 91-313-1-007

Separately Ordered 

Style H Escutcheons  

(85 mm Diameter)

White  . . . . . . . . . . . . . . . . . . . . P/N 56-313-4-010
Gray  . . . . . . . . . . . . . . . . . . . . . P/N 56-313-9-010

Separately Ordered 

Parts Installation Kit

Installation Cup w/O-Ring. . . . P/N 91-313-1-100
Cup Insert. . . . . . . . . . . . . . . . . P/N 91-313-1-004

Separately Ordered 

Sprinkler Wrench

Specify: W-Type 25 Installation Wrench, 

P/N 56-314-1-001.
Specify: W-Type 28 Installation Cup 

Removal Tool, P/N 56-000-4-301.

Copyright © 2012 Tyco Fire Products, LP.  All rights reserved.