Tyco FSC 80 K-factor Flush Sprinkler Скачать руководство пользователя страница 5

Step 11

Step 11.

 Engage FSC Sprinkler using 

W-Type 25 Wrench (Figure 7), and then 

screw  into Adapter. Hand-tighten FSC 

Sprinkler into Adapter until Escutcheon 

is flush with ceiling surface and sprin-

kler is positioned in intended orientation 

(Refer to Figures 1 and 2 for orientation 

details.).

Note:

 The W-Type 25 Wrench will en-

gage the FSC Sprinkler in only one way. 

When the sprinkler is engaged by the 

wrench, the flat on the wrench is par-

allel to the deflector guide pins and at 

installation, indicates the relative sprin-

kler deflector orientation.

Step 10

Step 10.

 Assemble Escutcheon onto 

FSC Sprinkler as shown. Apply sealant 

to external threads of Thread Extension.

NOTICE

Ensure sealant avoids contact with 

guide pins and internal waterway of 

Thread Extension. Failure to do so may 

result in equipment failure.

Step 12

Step 12.

 Ensure sprinkler is securely in 

place then remove W-Type 25 Wrench 

from sprinkler.
Repeat steps 7 through 12 to install re-

maining sprinklers.

Step 9

Step 9.

 Apply sealant to external 

threads on FSC Sprinkler Inlet. With 

hex end of Thread Extension oriented 

toward the sprinkler inlet, screw onto 

sprinkler threads until hex end is flush 

with sprinkler thread shoulder.

NOTICE

Ensure sealant avoids contact with 

guide pins and internal waterway of 

Sprinkler Inlet. Failure to do so may re-

sult in equipment failure.

Step 7

Step 7.

 Insert W-Type 28 Wrench 

(Figure 3) into Installation Cup cav-

ity ensuring it properly engages inter-

nal ribs and is fully seated. Using a 27 

mm hex wrench or a 1/2 inch drive, un-

screw Installation Cup Assembly from 

Sprinkler Fitting and remove from ceil-

ing cavity. Ensure O-Ring, as part of the 

Installation Cup Assembly, has been 

removed.

Note:

 Ceiling finish or coating should 

be applied before proceeding  on to 

sprinkler installation in remaining steps.

Step 8

Step 8.

 Apply sealant (not included 

with sprinkler kit) to external threads of 

Adapter. Screw Adapter into Sprinkler 

Fitting until Adapter shoulder is flush 

with face of fitting.

TFP645