General
Description
The TYCO Model FSC 80 K-factor Flush
Sprinkler Concrete Sprinklers are quick
response spray sprinklers designed for
use in areas such as offices, hospitals,
churches, schools, apartments, and
hotels.
• For applications in poured concrete
ceiling/floor assemblies, a unique
Installation Cup is used to form the
recessed cavity into which the FSC
Sprinkler is installed
• The flush design is made aestheti-
cally appealing by concealing the
deflector and other operating parts
above the link assembly. The FSC
Sprinklers, with heat sensitive sol-
der type release elements, are rated
quick response sprinklers
NOTICE
The TYCO Model FSC 80 K-factor
Flush Sprinkler Concrete Sprinklers
described herein must be installed
and maintained in compliance with this
document and with the applicable stan-
dards CEA 4001 “Sprinkler Systems:
Planning and Installation” or EN12845
“Fixed Firefighting Systems - Automatic
Sprinkler Systems - Design, Installation
and Maintenance”, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
Tyco Fire Protection Products specifi-
cally disclaims any liability for damages
or injury (including death) arising out of
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deflector Assembly . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly . . . . . . . . . . . Beryllium Nickel
with TEFLON
Link Assembly . . . . . . . . . . . . . . . . . . . . . Copper
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deflector Guide Pins . . . . . . . . . . . . . . . Stainless
Steel
Bridge. . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Levers. . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Plastic
Escutcheon . . . . . . . . . . . . . . . . . . . . . . . . . Steel
Installation Cup Assembly. . . . . . . . . . . . . Plastic
Sprinkler Extension Thread. . . . . . . . . . . . . Brass
Thread Adapter . . . . . . . . . . . . . . . . . . . . . . Brass
Design
Criteria
General Criteria
The TYCO Model FSC 80 K-factor
Flush Sprinkler Concrete Sprinklers
are intended to be installed per CEA
4001 “Sprinkler Systems: Planning
and Installation” or EN12845 “
Fixed
Firefighting Systems - Automatic
Sprinkler Systems - Design, Installation
and Maintenance
” where Flush
Sprinklers are permitted. Only escutch-
eons shown in Figure 1 can be utilized
with the Model FSC 80 K-factor Flush
Sprinkler Concrete Sprinklers.
In all cases, CEA 4001 “Sprinkler
Systems: Planning and Installation” or
EN12845 “
Fixed Firefighting Systems -
Automatic Sprinkler Systems - Design,
Installation and Maintenance
” must be
followed to ensure
proper installation.
The FSC Sprinklers can be used in nu-
merous scenarios including installation
in concrete ceilings/floors assemblies.
or caused by manipulation, dismantling,
or misuse of FSC Sprinklers or the use
or attempted use of the FSC Sprinklers
or any component thereof as an instru-
ment unrelated to its intended function
as a fire protection device.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Sprinkler
Identification
Number (SIN)
TY3200
Technical
Data
Approvals
VdS Approved
Flush Sprinkler Concrete is VdS
approved for installation per CEA
4001 “Sprinkler Systems: Planning
and Installation” or EN12845 “Fixed
Firefighting Systems - Automatic
Sprinkler Systems - Design, Installa-
tion and Maintenance”.
Maximum Working Pressure
12,1 bar (175 psi)
Discharge Coefficient
80,6 LPM/bar
1/2
(K=5.6 GPM/psi
1/2)
Temperature Rating
74°C (165°F)
Finishes
Sprinkler: White/Gray
Escutcheon: White/Gray
Model FSC 80 K-factor
Flush Sprinkler Concrete
Quick Response Standard Coverage
Page 1 of 6
OCTOBER 2012
TFP645
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.