Page 4 of 8

UL and C-UL Specific Application 

Listing Requirements for 

Installation under Concrete Tees

Series EC-11 and EC-14 Extended Cov-

erage Upright and Pendent Sprinklers 

(TY5137, TY5237, TY6137 and TY6237) 

have a UL and C-UL Specific Applica-

tion Listing for use under concrete tees 

when installed as follows:

1. 

Stems of the concrete tee con-

struction must be spaced at less 

than 7.5 ft (2,3 m) on center but 

more than 3 ft (0,9 m) on center. The 

depth of the concrete tees must not 

exceed 30 in. (762 mm). The maxi-

mum permitted concrete tee length 

is 32 ft (9,8 m). However, where the 

concrete tee length exceeds 32 ft 

(9,8 m), non-combustible baffles, 

equal in height to the depth of the 

tees, can be installed so that the 

space between the tees does not 

exceed 32 ft (9,8 m) in length.

2. 

The sprinkler deflectors are to be 

located in a horizontal plane at or 

above 1 in. (25,4 mm) below the 

bottom of the concrete tee stems.

3. 

When the sprinkler deflectors are 

located higher than a horizontal 

plane 1 in. (25,4 mm) beneath the 

bottom of the concrete tee stems, 

the obstruction to sprinkler dis-

charge criteria requirements of 

NFPA 13 for extended coverage 

upright and pendent sprinklers 

applies.

HC-1

Linear Spacing

ft

Area Spacing

ft

Ceiling Height

ft

Ceiling Type

K-factor

Style

Response

Min

Max

Min

Max

10

20

100

400

Up to 30

Noncombustible Unobstructed, 

Noncombustible Obstructed, or 

Combustible Unobstructed

11.2 EC  

14.0 EC

Pendent or 

Upright

Quick

10

20

100

400

Up to 30

Noncombustible Unobstructed, 

Noncombustible Obstructed, or 

Combustible Unobstructed

11.2 EC  

14.0 EC

Pendent 

Recessed 

Style 30

10

20

100

400

Up to 30

Combustible Obstructed

11.2 EC  

14.0 EC

Pendent or 

Upright

10

20

100

400

Up to 30

Combustible Obstructed

11.2 EC  

14.0 EC

Pendent 

Recessed 

Style 30

10

20

100

400

Over 30 and 

up to 45

Noncombustible Unobstructed

11.2 EC  

14.0 EC

Upright

HC-2

Linear Spacing

ft

Area Spacing

ft

Ceiling Height

ft

Ceiling Type

K-factor

Style

Response

Min

Max

Min

Max

10

20

100

400

Up to 30

Noncombustible Unobstructed, 

Combustible Unobstructed

11.2 EC

Upright

Quick

10

20

100

400

Up to 30

14.0 EC

Pendent or 

Upright

10

16

100

256

Over 30 and 

up to 45

11.2 EC 14.0 

EC

Upright

HC-3

Linear Spacing

ft

Area Spacing

ft

Ceiling Height

ft

Ceiling Type

K-Factor

Style

Response

Min 

Max

Min

Max

10

16

100

256

Up to 30

Noncombustible Unobstructed, 

Combustible Unobstructed

11.2 EC

Upright

Quick

10

20

100

400

Up to 30

14.0 EC

Pendent or 

Upright

10

16

100

256

Over 30 and 

up to 45

11.2 EC, 

14.0 EC

Upright

NOTES

•  The design for K 11.2 EC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0 

EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar).

•  For flow criteria, refer to FM Loss Prevention Data Sheet 3-26.
•  Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations. 

TABLE C 

SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS

Содержание EC-11 Series

Страница 1: ...s beyond that which occurs when exposed to corrosive atmospheres Although corrosion resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies this testing is not...

Страница 2: ...ed by NFPA 13 for example Unobstructed combustible or noncombustible ceiling con struction with a deflector to ceiling roof deck distance of 1 to 12 in 25 to 300 mm Obstructed non combusti ble ceiling...

Страница 3: ...ory Mutual Research Corporation FM 4 Approved by the City of New York under MEA 177 03 E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and...

Страница 4: ...14 0 EC Pendent or Upright Quick 10 20 100 400 Up to 30 Noncombustible Unobstructed Noncombustible Obstructed or Combustible Unobstructed 11 2 EC 14 0 EC Pendent Recessed Style 30 10 20 100 400 Up to...

Страница 5: ...er or over tightening the Sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 Install the sprinkler with the deflector parallel to the mounting surface Install pendent sprinklers...

Страница 6: ...0 MALLEABLE IRON REDUCING SPRINKLER FITTING FITTING SIDE TOWARDS SPRINKLER FITTING WRENCH RECESS END A WRENCH RECESS WRENCH HEX 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 1 2 1...

Страница 7: ...y the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this doc ument as well as with the...

Страница 8: ...e Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2019 Johnson Controls All rights reserved All specifications and o...

Отзывы: