Series EC-11 and EC-14 Sprinklers, 

11.2 K and 14.0 K Upright and Pendent 

Extended Coverage Light and Ordinary Hazard

Page 1 of 8 

OCTOBER 2018 

TFP220

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

TYCO Series EC-11 and EC-14 

Extended Coverage Upright and 

Pendent Sprinklers are decorative 

glass-bulb sprinklers designed for use 

in light or ordinary hazard occupancies. 

They are intended for use in automatic 

sprinkler systems designed in accor-

dance with standard installation rules, 

such as NFPA 13, for a maximum cov-

erage area of 400 ft

2

 (37,2 m

2

) as com-

pared to the maximum coverage area 

of 130 ft

2

 (12,1 m

2

) for standard cover-

age sprinklers used in ordinary hazard 

occupancies, Series EC-11 and EC-14 

Extended Coverage Sprinklers feature 

a UL and C-UL Listing that permits their 

use with unobstructed or non-combus-

tible obstructed ceiling construction as 

defined and permitted by NFPA 13, as 

well as a specific application listing for 

use under concrete tees.
Series EC-11 and EC-14 Extended Cov-

erage Sprinklers have been fire tested 

to compare their performance to that 

of standard coverage spray sprinklers. 

These tests have shown that the pro-

tection provided is equal to or more 

effective than standard coverage spray 

sprinklers.
Corrosion-resistant coatings, where 

applicable, help extend the life of 

copper alloy sprinklers beyond that 

which occurs when exposed to 

corrosive atmospheres. Although 

corrosion-resistant coated sprinklers 

passed standard corrosion tests of 

the applicable approval agencies, this 

testing is not representative of all pos-

sible corrosive atmospheres. Conse-

quently, it is recommended that the end 

user be consulted with respect to the 

suitability of these corrosion-resistant 

coatings for any given corrosive envi-

ronment. The effects of ambient tem-

perature, concentration of chemicals, 

and gas/chemical velocity should be 

considered, along with the corrosive 

nature of the chemical to which the 

sprinklers will be exposed.

NOTICE

Series EC-11 and EC-14 Extended Cov-

erage Sprinklers described herein must 

be installed and maintained in compli-

ance with this document, as well as 

with the applicable standards of the 

NFPA, in addition to the standards of 

any other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Numbers

TY5137                          Upright, 11 2K
TY5237                        Pendent, 11 2K
TY6137                         Upright, 14 0K
TY6237                       Pendent, 14 0K

TY5137 is a re-designation for C5137, G1894, and S2510

TY5237 is a re-designation for C5237, G1893, and S2511
TY6137 is a re-designation for C6137, G1896, and S2610
TY6237 is a re-designation for C6237, G1895, and S2611

Technical 

Data

Approvals

TYCO Series EC-11 and EC-14 

Extended Coverage Upright and 

Pendent Sprinklers are UL and C-UL 

Listed. Refer to Table A for complete 

sprinkler approval information including 

corrosion-resistant status. The approv-

als apply to the service conditions indi-

cated in the Design Criteria section.
Series EC-11 and EC-14 Extended Cov-

erage Sprinklers

 

are FM Approved. 

Refer to Table A for complete sprinkler 

approval information including corro-

sion-resistant status. The approvals 

apply to the service conditions indi-

cated in the Design Criteria section.

Содержание EC-11 Series

Страница 1: ...s beyond that which occurs when exposed to corrosive atmospheres Although corrosion resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies this testing is not...

Страница 2: ...ed by NFPA 13 for example Unobstructed combustible or noncombustible ceiling con struction with a deflector to ceiling roof deck distance of 1 to 12 in 25 to 300 mm Obstructed non combusti ble ceiling...

Страница 3: ...ory Mutual Research Corporation FM 4 Approved by the City of New York under MEA 177 03 E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and...

Страница 4: ...14 0 EC Pendent or Upright Quick 10 20 100 400 Up to 30 Noncombustible Unobstructed Noncombustible Obstructed or Combustible Unobstructed 11 2 EC 14 0 EC Pendent Recessed Style 30 10 20 100 400 Up to...

Страница 5: ...er or over tightening the Sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 Install the sprinkler with the deflector parallel to the mounting surface Install pendent sprinklers...

Страница 6: ...0 MALLEABLE IRON REDUCING SPRINKLER FITTING FITTING SIDE TOWARDS SPRINKLER FITTING WRENCH RECESS END A WRENCH RECESS WRENCH HEX 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 1 2 1...

Страница 7: ...y the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this doc ument as well as with the...

Страница 8: ...e Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2019 Johnson Controls All rights reserved All specifications and o...

Отзывы: