26
Internet Alarm Communicator Installation Manual
NOTE:
Each Ethernet receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the communicator to operate in Unattended Mode.
Unattended mode is used when a receiver is not available and the unit is required to perform DLS
sessions. Typically used where the customer programs the control panel daily due to access control
and still wants to receive alarms without buying extra hardware (receiver) or software.
NOTE:
When a valid IP address has been programmed, Ethernet receiver 1 is enabled and will
communicate events over the Ethernet channel.
[104] Ethernet Receiver 1 UDP Remote Port
Default (0BF5/3061)
This Section determines the UDP remote port of Ethernet receiver 1. Valid range: 0000 - FFFF.
[105] Ethernet Receiver 1 UDP Local Port
Default (0BF4/3060)
Use this section to set the value of the UDP local outgoing port. Set the value of this port when
your installation is located behind a firewall and must be assigned a particular port number as
determined by your central station system administrator. Valid range: 0000 - FFFF.
[106] Ethernet Receiver 1 Domain Name
Default ( )
Enter the domain name as 32 ASCII characters.
Programming this section is not permitted on a UL/ULC listed system.
Ethernet Receiver 2 Options
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. The account
code is used when transmitting heartbeat signals to the central station receiver. Signals received
from the control panel will use the control panel account number. Valid range: 000000000
1
-
FFFFFFFFFE. Programming all 0 or all F will cause a module configuration Trouble (yellow
LED=12 flashes).
[112] Ethernet Receiver 2 DNIS
Default (000000)
The DNIS is used in addition to the account code to identify the communicator module at the cen-
tral station. Valid range: 000000 - 099999. Value is entered as leading 0 followed by the 5-digit
DNIS. Format is BCD.
NOTE:
Each Ethernet receiver must be programmed with a unique DNIS.
[113] Ethernet Receiver 2 Address
Default (000.000.000.000)
Programming the Ethernet receiver 2 IP address with 000.000.000.000 will disable Ethernet.
Enter the Ethernet receiver 2 IP address. This address will be provided by your central station sys-
tem administrator. Format is 4 fields, each field is a 3-digit decimal. Valid range: 000-255.
NOTE:
When a valid IP address has been programmed, Ethernet receiver 2 is enabled and will
communicate events over the Ethernet channel.
NOTE:
Do not program Ethernet receiver 1 and Ethernet receiver 2 to communicate to same
receiver.
[114] Ethernet Receiver 2 UDP Remote Port
Default (0BF5/3061)
This section is used to program the port number used by Ethernet receiver 2. Set the value of this
port when your installation is located behind a firewall, and must be assigned a particular port
number as determined by your central station system administrator. Valid range: 0000 - FFFF.
NOTE:
Do not program Ethernet receiver 1 and Ethernet receiver 2 port with the same value.