TFP1020

Page 4 of 20

Technical Data

Approvals

UL and C-UL Listed 

FM and NYC under MEA 172-02-E (4 and 

6 inch).

Dry Pipe Valve

The TYCO Model DPV-1 Dry Pipe 

Valves are for vertical installations (flow 

going up), and they are rated for use 

at a maximum service pressure of 250 

psi (17,2 bar). The Valve dimensions are 

shown in Figure 7.
Flanged connections are available and 

drilled per ANSI, ISO, AS, and JIS spec-

ifications (Ref. Table A). The grooved 

outlet connections, as applicable, are 

cut in accordance with standard groove 

specifications for steel pipe. They are 

suitable for use with grooved end pipe 

couplings that are listed or approved 

for fire protection system service. Avail-

able combinations of inlet and outlet 

connections are detailed in the Order-

ing Procedure section. They are also 

noted in the “Available End Connection 

and Sizes” table located on Page 1.
Threaded port connections of valves 

having flanges drilled to ANSI, AS, or 

JIS specifications are NPT threaded 

per ANSI Standard B1.20.1. Threaded 

port connections of valves having 

flanges drilled to ISO are available 

either threaded per ISO 7-1 or NPT 

threaded per ANSI Standard B1.20.1. 

Valves with NPT threaded ports will 

readily accept the trim arrangements 

detailed in Parts 2 and 3 of Figures 4, 

5, and 6.
Components of the DPV-1 Valves are 

shown in Figure 1. The Body and Hand-

hole Cover are ductile iron. The Hand-

hole Cover Gasket is neoprene, and 

the Clapper Facing is EPDM. The Air/

Water Seat Ring is brass, the Clapper 

is bronze or aluminum bronze, and both 

the Clapper Retaining Plate and Latch 

are bronze. The Hinge Pin is aluminum 

bronze, and the fasteners for the Hand-

hole Cover are carbon steel.

Valve Trim

Installation dimensions are given in 

Figure 7, and the Valve Trim and Pre-

Trimmed Valve Assemblies are illus-

trated in Figures 4, 5, and 6. The Valve 

Trim and Pre-Trimmed Valve forms 

a part of the laboratory listings and 

approval of the DPV-1 Valve and is 

necessary for the proper operation of 

the DPV-1 Valve. Each package of trim 

and pre-trimmed includes the follow-

ing items:
•   Water Supply Pressure Gauge
•   System Air Pressure Gauge
•   Air Supply Connections
•   Main Drain Valve
•   Low Body Drain Valve
•   Alarm Test Valve
•   Automatic Drain Valve
•   Drip  Funnel
•   Connections For Optional Quick 

Opening Device (Accelerator)

Also included in the Pre-Trimmed Valve 

Assembly, which can be ordered sepa-

rately for the Valve Trim, includes the 

following items:
•  Model BFV-300 butterfly valve
•  Figure 577 grooved coupling
•  PS10-2 waterflow alarm switch
•  PS40-2 low air pressure alarm switch

Note:

 When the system pressure is 

greater than 175 psi (12,1 bar), provision 

is to be made to replace the standard 

order 300 psi (20,7 bar) Water Pressure 

gauge with a separately ordered 600 

psi (41,4 bar) Water Pressure Gauge.

Air Supply

Table B shows the system air pres-

sure requirements as a function of the 

water supply pressure. The air (or nitro-

gen) pressure in the sprinkler system 

is recommended to be automatically 

maintained by using one of the follow-

ing pressure maintenance devices, as 

appropriate:
•   

Model AMD-1 Air Maintenance 

Device (pressure reducing type).

•   

Model AMD-2 Air Maintenance 

Device (compressor control type).

•   Model AMD-3 Nitrogen Maintenance 

Device (high pressure reducing type). 

The Pressure Relief Valve provided with 

the valve trim is factory set to relieve 

at a pressure of approximately 45 psi  

(3,1 bar). If the normal system air pres-

sure is less than or exceeds 40 psi (2,8 

bar), then the pressure Relief Valve 

must be reset to relieve at a pressure 

that is in accordance with the authority 

having jurisdiction.

Quick Opening Device

As an option, the Model DPV-1 Dry 

Pipe Valve may be equipped with the 

VIZOR Electronic Dry Pipe Valve Accel-

erator (4 and 6 inch sizes) as detailed 

in Technical Data Sheet TFP1105 or 

the Model ACC-1 Mechanical Dry Pipe 

Valve Accelerator (2-1/2, 3, 4, and 6 

inch sizes) as detailed in Technical Data 

Sheet TFP1112.
The VIZOR or the ACC-1 is used to 

reduce the time to valve actuation fol-

lowing the operation of one or more 

automatic sprinklers. In some cases 

the use of a quick opening device 

such as the VIZOR or the ACC-1 may 

be required to meet the requirements of 

the National Fire Protection Association 

to meet water delivery times.

Nominal 

Valve 

Size

Flange Drilling Specification

Nominal Dimensions in Inches and (mm)

ANSI B16.1

1

 

(Class 125)

ISO 7005-2 

(PN16)

2

JIS B 2210 

(10K)

AS 2129 

(Table E)

Dim. 

A

Dim. 

B

Qty. 

N

Dim. 

A

Dim. 

B

Qty. 

N

Dim. 

A

Dim. 

B

Qty. 

N

Dim. 

A

Dim. 

B

Qty. 

N

4 Inch 

(DN100)

7.50 

(190,5)

0.75 

(19,0)

8

7.09 

(180,0)

0.75 

(19,0)

8

6.89 

(175,0)

0.59 

(15,0)

8

7.00 

(178,0)

0.71 

(18,0)

8

6 Inch 

(DN150)

9.50 

(241,3)

0.88 

(22,2)

8

9.45 

(240,0)

0.91 

(23,0)

8

9.45 

(240,0)

0.75 

(19,0)

8

9.25 

(235,0)

0.87 

(22,0)

8

1.  Drilling same as ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150).
2.  Drilling same as BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).

Dim. A

Bolt Circle

Diameter

Dim. B

Bolt Hole

Diameter

Qty. N

Number of

Bolt Holes

TABLE A 

DIMENSIONAL SPECIFICATIONS 

FOR SELECTION OF FLANGE DRILLING

Содержание DPV-1

Страница 1: ...r filled pipe cannot be utilized When set for service the dry pipe sprinkler system is pressur ized with air or nitrogen The loss of pressure through an operated auto matic sprinkler in response to heat from a fire permits the DPV 1 Dry Pipe Valve to open and allow a flow of water into the sprinkler system piping Table B establishes the minimum required system air pressure that includes a safety f...

Страница 2: ...RIPTION REF Clapper Assembly Repair Parts Kit Reset Plunger Parts Kit Includes Items 11 18 Includes Items 6 10 Includes Items 4 7 14 15 18 CH 4 Inch Valve Valves 2 1 2 3 Inch Valves 4 Inch Valve 92 310 2 203 92 310 2 403 2 1 2 3 Inch Valves 4 Inch Valve 92 310 1 204 92 310 1 404 2 1 2 and 3 Inch Valves 1 4 20 UNC x 1 2 Socket Head Cap a Screw 4 Inch Valve NR Not Replaceable CH Common Hardware NO D...

Страница 3: ...FS3452 b or c Grease 1 5 g Flourosilicone NO DESCRIPTION REP PART NR Air Seal O Ring Socket Head Cap Screw NR 3 8 16 UNC x 1 NO DESCRIPTION REP PART Air and Water Water Seal O Ring NR Valve Body NR NO DESCRIPTION REP PART NR Seat NR Not Replaceable CH Common Hardware Clapper Assembly Repair Parts Kit Reset Plunger Parts Kit Includes Items 14 21 Includes Items 9 13 Includes Items 7 10 17 18 21 92 3...

Страница 4: ...he Valve Trim includes the following items Model BFV 300 butterfly valve Figure 577 grooved coupling PS10 2 waterflow alarm switch PS40 2 low air pressure alarm switch Note When the system pressure is greater than 175 psi 12 1 bar provision is to be made to replace the standard order 300 psi 20 7 bar Water Pressure gauge with a separately ordered 600 psi 41 4 bar Water Pressure Gauge Air Supply Ta...

Страница 5: ...ypical flow rate of 1500 GPM matic Drain Valve must be depressed during several of the resetting steps as well as during inspections making certain that the Automatic Drain Valve is open When one or more automatic sprin klers operate in response to a fire air pressure within the system piping is relieved through the open sprin klers When the air pressure is suf ficiently reduced the water pressure...

Страница 6: ...IVOTS TO UNLATCH CLAPPER ASSEMBLY FROM WATER SUPPLY WATERFLOW TO SYSTEM CLAPPER LATCH PIVOTS TO ALLOW CLAPPER ASSEMBLY TO FULLY OPEN 3 4 NPT ALARM PORT OPEN TO ATMOSPHERE RESET KNOB DRAIN FROM SYSTEM COMPLETE DRAIN FROM SYSTEM CLAPPER ASSEMBLY IN SET POSITION PUSH HERE TO RESET VALVE INTERMEDIATE CHAMBER WATER SEAT VALVE WATERWAY CLAPPER ASSEMBLY ALARM PORT AIR SEAT DN40 FOR VALVES WITH ISO THREAD...

Страница 7: ...TO ALARM WATER SUPPLY SHUT OFF CLAPPER LATCH PIVOTS TO UNLATCH CLAPPER ASSEMBLY FROM WATER SUPPLY WATERFLOW TO SYSTEM CLAPPER LATCH PIVOTS TO ALLOW CLAPPER ASSEMBLY TO FULLY OPEN 3 4 NPT ALARM PORT OPEN TO ATMOSPHERE RESET KNOB DRAIN FROM SYSTEM COMPLETE DRAIN FROM SYSTEM CLAPPER ASSEMBLY IN SET POSITION PUSH HERE TO RESET VALVE INTERMEDIATE CHAMBER WATER SEAT VALVE WATERWAY CLAPPER ASSEMBLY ALARM...

Страница 8: ...T CONNECTION TO DRAIN DRIP FUNNEL A B C D H E F G AUTOMATIC DRAIN VALVE ALARM TEST VALVE NORMALLY CLOSED MAIN DRAIN VALVE NORMALLY CLOSED 1 1 4 INCH NPT CONNECTION TO DRAIN DRIP FUNNEL AIR SUPPLY CONTROL VALVE NORMALLY OPEN 1 2 INCH NPT CONNECTION FOR OPTIONAL ACCELERATOR SYSTEM AIR SUPPLY PRESSURE GAUGE 1 1 4 INCH NPT CONNECTION TO DRAIN LOW BODY DRAIN VALVE NORMALLY CLOSED 1 INCH NPT CONNECTION ...

Страница 9: ...omatic Drain Valve 46 048 1 005 3 4 Angle Valve 46 048 1 007 1 1 4 Angle Valve 3 4 90 Elbow CH 1 1 4 90 Elbow CH 1 2 Tee CH 1 4 x 3 CH CH 1 x Close CH CH CH 1 2 x 1 2 x 1 4 CH Reducing Tee DESCRIPTION P N DESCRIPTION P N COMPONENTS INCLUDED ONLY IN PRE TRIMMED VALVE ASSEMBLIES Waterflow Pressure Alarm Switch 25710 Model PS10 2 Low Air Pressure Alarm Switch 25730 Model PS40 2 Model BFV 300 59300G02...

Страница 10: ...ED COUPLING D B C B A NOTES 2 SEE FIGURE 3 FOR VALVE PORT IDENTIFICATION 1 INSTALL TRIM ASSEMBLIES IN ALPHABETICAL ORDER SLOPE ASSEMBLY B DOWN TOWARD BACK OF VALVE TO FACILITATE SUFFICIENT LOW BODY DRAINAGE 4 3 ROUTE 1 4 TUBING TO DRIP FUNNEL AUTOMATIC DRAIN VALVE ALARM TEST VALVE NORMALLY CLOSED MAIN DRAIN VALVE NORMALLY CLOSED 1 1 4 INCH NPT CONNECTION TO DRAIN 3 4 INCH NPT CONNECTION TO DRAIN D...

Страница 11: ... 2 x 2 1 2 1 2 x 3 1 2 x 3 1 2 3 4 x 1 1 2 3 4 x 2 3 4 x 3 1 x 4 2 x 4 1 2 CH CH CH CH CH CH CH CH CH CH CH 1 2 x Close CH 3 4 x Close CH 1 2 x 1 4 Reducing Bushing CH 1 2 Cross CH COMPONENTS INCLUDED ONLY IN PRE TRIMMED VALVE ASSEMBLIES Model BFV 300 Butterfly 59300G040NS Valve 4 DN100 Butterfy Valve GxG DPV 1 Valves Figure 71 Flange Adapter 7140S 4 DN100 Figure 577 Coupling 57740ACP 4 DN100 FxF ...

Страница 12: ...LOPE 3 4 ANGLE VALVE AND 3 4 x 4 1 2 NIPPLE OF ASSEMBLY B INTO DRIP FUNNEL TO FACILITATE SUFFICIENT LOW BODY DRAINAGE NOTES 4 NOTES SEE FIGURE 3 FOR VALVE PORT IDENTIFICATION INSTALL TRIM ASSEMBLIES IN ALPHABETICAL ORDER 2 1 ROUTE 1 4 TUBING TO DRIP FUNNEL 3 AUTOMATIC DRAIN VALVE ALARM TEST VALVE NORMALLY CLOSED MAIN DRAIN VALVE NORMALLY CLOSED 1 1 4 INCH NPT CONNECTION TO DRAIN DRIP FUNNEL DRIP F...

Страница 13: ...CH CH CH CH CH 1 2 x 6 CH CH 3 4 90 Elbow CH 1 2 x 1 4 Reducing CH Bushing 1 2 Cross CH DESCRIPTION P N DESCRIPTION P N DESCRIPTION P N CH 1 2 x Close COMPONENTS INCLUDED ONLY IN PRE TRIMMED VALVE ASSEMBLIES Waterflow Pressure Alarm Switch 25710 Model PS10 2 Low Air Pressure Alarm Switch 25730 Model PS40 2 Model BFV 300 Butterfly 59300G060NS Valve 6 DN150 Butterfy Valve GxG DPV 1 Valves Figure 71 ...

Страница 14: ...m 9 5 8 245 mm 6 INCH DN150 VALVE 24 1 2 620 mm 11 1 2 290 mm 14 3 4 375 mm 15 380 mm 21 7 8 555 6 mm 11 3 8 289 mm 2 1 2 3 INCH DN65 DN80 VALVE 20 7 16 520 mm 14 7 8 380 mm 9 1 4 235 mm 7 1 8 180 mm 16 1 8 409 6 mm 2 1 2 or 3 INCH VALVES 8 3 8 213 mm FIGURE 7 PART 1 OF 2 MODEL DPV 1 DRY PIPE VALVE INSTALLATION DIMENSIONS PRE TRIMMED VALVE ...

Страница 15: ... 6 INCH DN150 VALVE 7 1 4 190 mm 18 3 4 475 mm 4 1 2 115 mm 11 1 2 290 mm 14 3 4 375 mm 15 380 mm 16 406 4 mm FxF FxG or GxG 2 1 2 3 INCH DN65 DN80 VALVE 16 9 16 420 7 mm 6 150 mm 14 7 8 380 mm 9 1 4 235 mm 6 3 4 170 mm 8 200 mm 12 1 4 311 2 mm 2 1 2 or 3 INCH VALVES FIGURE 7 PART 2 OF 2 MODEL DPV 1 DRY PIPE VALVE INSTALLATION DIMENSIONS VALVE AND SEMI ASSEMBLED TRIM ...

Страница 16: ...ed By NFPA 13 must be pro vided on the system piping at the most remote location from the Model DPV 1 Valve Conduit and electrical connections are to be made in accordance with the requirements of the author ity having jurisdiction and or the National Electric Code Before a system hydrostatic test is performed in accordance with NFPA 13 system acceptance test require ments the Clapper Assembly is ...

Страница 17: ...ion should be verified at least once a year as follows Step 1 If water must be prevented from flowing beyond the riser perform the following steps Close the Main Control Valve Open the Main Drain Valve Open the Main Control Valve one turn beyond the position at which water just begins to flow from the Main Drain Valve Close the Main Drain Valve Step 2 Open the system s Inspector s Test Connection ...

Страница 18: ...4 Inch DPV 1 Semi Assembled Galvanized Trim P N 52 309 2 001 Specify 6 Inch DPV 1 Semi Assembled Galvanized Trim P N 52 309 2 002 Optional Accelerator VIZOR Electronic Dry Pipe Accelerator with Trim Details provided in TFP1105 Specify VIZOR Electronic Dry Pipe Accelerator for use with the 4 or 6 inch TYCO Model DPV 1 Dry Pipe Valve trim P N 52 312 3 001 Model ACC 1 Mechanical Accelerator Details p...

Страница 19: ... 50 88 9 mm Outside Dia Groove P N 52 309 1 922 Part Numbers For Other 4 Inch DN100 Dry Pipe Valves Valves with NPT Ports FxG ISO Flange x 4 50 114 3 mm Outside Dia Groove P N 52 309 1 253 FxG AS Flange x 4 50 114 3 mm Outside Dia Groove P N 52 309 1 613 FxG JIS Flange x 4 50 114 3 mm Outside Dia Groove P N 52 309 1 813 FxF ISO Flange x ISO Flange P N 52 309 1 133 FxF AS Flange x AS Flange P N 52 ...

Страница 20: ...GLOBAL HEADQUARTERS 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 TFP1020 Page 20 of 20 Copyright 2016 Tyco Fire Products LP All rights reserved ...

Отзывы: