Model CV-1FR Grooved-End 

Riser Check Valves 

2 Inch to 12 Inch (DN50 to DN300)

Page 1 of 4 

AUGUST 2018 

TFP950

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

General 

Description

The  TYCO Model CV-1FR Grooved-

End Riser Check Valve is a compact 

and rugged swing-type unit that allows 

water flow in one direction and pre-

vents flow in the opposite direction. 

A resilient elastomer seal facing on 

the spring-loaded clapper ensures a 

leak-tight seal and non-sticking opera-

tion. The Model CV-1FR Riser Check 

Valves are designed to minimize water 

hammer caused by flow reversal.
The Model CV-1FR Riser Check Valve 

is furnished with grooved ends and 

can be installed using GRINNELL

 

Grooved Couplings or GRINNELL 

Figure 71 Flange Adapters. The Model 

CV-1FR Riser Check Valves have been 

designed with a removable cover for 

ease of field maintenance. These valves 

can be installed horizontally (with cover 

in the upward position) or vertically with 

the flow in the upward direction. Refer 

to Figure 6.
To facilitate their use in wet-type auto-

matic sprinkler system risers, the 

Model CV-1FR Riser Check Valves are 

provided with threaded outlets for pres-

sure gauges and a drain connection. 

They provide a more compact and eco-

nomical alternative to an alarm check 

valve where a water motor alarm is not 

required. Provisions must be made for 

a local alarm using an approved flow 

switch (not included).
The Model CV-1FR Riser Check Valve 

is also Listed for use in conjunction 

with the TYCO DV-5 Deluge Valve in 

Preaction Systems under air pressure 

without the use of prime water.
The Model CV-1FR Riser Check Valves 

are a redesign for the Central Figure 

590FR and GRINNELL Figure 590FR.

NOTICE

The Model CV-1FR Riser Check Valve 

described herein must be installed 

and maintained in compliance with 

this  document and with the applicable 

standards of the NATIONAL FIRE PRO-

TECTION ASSOCIATION, in addition to 

the standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of this device.
Never remove any piping component 

nor correct or modify any piping defi-

ciencies without first de-pressurizing 

and draining the system. Failure to do 

so may result in serious personal injury, 

property damage, and/or impaired 

device performance.
The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition. 

Contact the installing contractor or 

manufacturer with any questions.

Technical 

Data

Approvals 

UL, C-UL Listed  

FM Approved

Sizes

2 in. to 12 in. (DN50 to DN300)

Maximum Working Pressure 

300 psi (20,7 bar)

Valve Assembly Finish 

Red, non-lead paint

Installation

The Model CV-1FR Riser Check Valves 

are to be installed in accordance with 

this section:
1. The arrow cast on the Body must 

point in the direction of the flow.

2. Valves installed vertically must 

be positioned with the flow in the 

upward direction.

3. Valves installed horizontally must be 

positioned with the Cover facing up. 

Refer to Figure 6.

4. Grooved-end pipe couplings used 

with the Model CV-1FR Riser Check 

Valve must be installed in accordance 

with manufacturer’s instructions.

NOTE: Valves should be installed a 

reasonable distance downstream from 

pumps, elbows, expanders, reducers, 

or other similar devices to extend the 

valve life. Standard piping practices 

call for a minimum of five times the pipe 

diameter for general use.