Tyco AMD-3 Скачать руководство пользователя страница 3

TFP1241

Page 3 of 4

Operating  

Procedure

Place the TYCO Model AMD-3 Auto-

matic Nitrogen Maintenance Device 

in operation in accordance with this 

section.

Step 1.

 Determine the pressure that 

meets the minimum requirements of 

the system to pressurize.

Step 2.

 Close the control valve in the 

air supply trim to the system.

Step 3.

 Turn the Two-Stage Pressure 

Regulator adjusting handle counter-

clockwise until the adjusting spring 

pressure is fully released.

Step 4.

 Standing to the side of the 

nitrogen cylinder opposite from the 

Pressure Regulator, slowly crack open 

the Cylinder Control Valve until the cyl-

inder pressure is indicated on the High 

Pressure Gauge and then fully open 

the Cylinder Control Valve to seal its 

packing.

Step 5.

 Slowly turn the Two-Stage 

Pressure Regulator handle clockwise 

until the Outlet Pressure Gauge indi-

cates the required pressure established 

in Step 1.

Step 6.

 Open the By-Pass Valve in the 

Model AMD-3 Device.

Step 7.

 Open the control valve in the air 

supply trim to the system.

Step 8.

 After the system pressure sta-

bilizes, note the value on the system 

pressure gauge and compare it with the 

requirement. Adjust the Pressure Regu-

lator, as required (counter-clockwise to 

decrease and clockwise to increase). 

One-half turn of the stem changes the 

outlet pressure by approximately 8 psi.

Step 9.

 If the system pressure must be 

decreased, first re-adjust the Pressure 

Regulator, then momentarily open a 

connection to the system to reduce the 

pressure to below the required value. 

Allow the system pressure to automati-

cally stabilize.

Step 10.

 Close the By-Pass Valve in the 

Model AMD-3 Device.

NOTICE

Following a sprinkler operation, in order 

to prevent a delay in the release of the 

automatic control valve, the By-Pass 

Valve must be closed when the fire pro-

tection system is in service.

Step 11.

 Check all supply pressure 

connections for leaks.

Care and  

Maintenance

The TYCO Model AMD-3 Automatic 

Nitrogen Maintenance Device must 

be maintained and serviced in accor-

dance with this section, in addition to 

any specific requirements of the NFPA. 

Any impairment must be immediately 

corrected.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
It is recommended that a spare supply 

of nitrogen be kept on hand.
Make no attempt to field-repair or 

replace any component of the Pres-

sure Regulator.
Inspections should be made more 

frequently, after the system is initially 

placed in service, to develop a guide-

line as to the required schedule for 

nitrogen cylinder replacement. Graph-

ing the Inlet Gauge pressure noted 

during each inspection will assist in 

this evaluation.
After placing a fire protection system 

in service, notify the proper authorities 

and advise those responsible for moni-

toring proprietary and/or central station 

alarms.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (e.g., NFPA 25), in addi-

tion to the standards of any authorities 

having jurisdiction. Contact the install-

ing contractor or product  manufacturer 

with any questions.
Automatic sprinkler systems should be 

inspected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national code.

INSPECTION PROCEDURE

The Model AMD-3 Automatic Nitrogen 

Maintenance Device must be inspected 

quarterly in accordance with the follow-

ing instructions.

Step 1.

 Verify that the control valve 

in the air supply trim to the system is 

open.

Step 2.

 Verify that the nitrogen Cylinder 

Control Valve is open.

Step 3.

 Verify that the By-Pass Valve 

is closed.

NOTICE

Following a sprinkler operation, in order 

to prevent a delay in the release of the 

automatic control valve, the By-Pass 

Valve must be closed when the fire pro-

tection system is in service.

Step 4.

 Verify that the system pressure 

gauge indicates the same value as the 

previously established requirement. If 

not, re-adjust per Step 8 of the Operat-

ing Procedure section.

Step 5.

 Verify that the Inlet Pressure 

Gauge of the Pressure Regulator 

indicates sufficient nitrogen cylinder 

pressure. It is recommended that the 

nitrogen cylinder be replaced whenever 

its pressure falls to 200 psi or below.

60

50

40

30

20

10

0

-60

-50

-40

-30

SYSTEM PRESSURE, PSIG

*

BASED ON A DEWPOINT OF -60°F AT ATMOSPHERIC PRESSURE.

NITROGEN, °F

DEWPOINT OF SUPPL

Y

GRAPH A 

MAXIMUM DEWPOINT OF SUPPLY NITROGEN AS A 

FUNCTION OF SYSTEM PRESSURE*

Содержание AMD-3

Страница 1: ...ion Failure to do so may impair the perfor mance of these devices The owner is responsible for main taining their fire protection system and devices in proper operating con dition Contact the installing contrac tor or product manufacturer with any questions Technical Data Approvals UL and C UL Listed FM Approved NYC Approved under MEA 206 02 E Maximum Inlet Nitrogen Supply Pressure 3000 psi 200 ba...

Страница 2: ...in the air supply trim of TYCO dry pipe valves preaction valves and dry pilot trim Step 5 Following the steps outlined in the caution below install the nitrogen cylinder CAUTION The following instructions regarding the nitrogen cylinder must be strictly fol lowed Failure to do so may result in personal injury or property damage Step A Secure the cylinder to a wall or post ensuring it will not tip ...

Страница 3: ...ssion to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this action It is recommended that a spare supply of nitrogen be kept on hand Make no attempt to field repair or replace any component of the Pres sure Regulator Inspections should be made more frequently after the system is initially placed in service to develop a gui...

Страница 4: ...t and dust with a clean cloth If damaged threads oil or grease are present replace the cylinder Step C Inspect the Pressure Regulator inlet for dirt dust damaged threads oil or grease Remove dirt and dust with a clean cloth If damaged threads oil or grease are present have the pressure regulator serviced by an authorized agent of the Victor Equip ment Company Step D With the cylinder securely in p...

Отзывы: