EQUIPMENT:
PUBLICATION:
ISSUE No.
&
DATE:
MAIN MENU DISPLAY
ACTIONS
‘Address Program’
Read/Writes the address of the connected addressable device
Reads the stored address map of used addresses
‘Analogue Values’
Displays the analogue values of the addressable device
‘Measure Temp.’
Measures temperature in degrees C and F (only available on detectors which have a
temperature sensing element)
‘Measure CO Level’
For CO detectors only. Gives values for CO levels in the measuring environment.
Normal value is zero PPM (parts-per-million)
‘Test All’
Performs:
a self test if the detector has such a facility
remote indicator output
functional base interface output
‘Dirtiness’
Indicates the contamination level of the optical chamber expressed as a percentage,
where 100% is the fault level
‘Device Type ID’
Displays the device type identification value
‘Digital Inputs’
Displays the status of the digital inputs in addressable devices
‘Digital Outputs’
Allows the user to set the digital outputs of the addressable device
‘Customer Code’
Not normally used, but it should be set to the same as the customer code in the device
Low Battery
Indicates Low Battery by using a flashing symbol in the bottom right of the LCD display
CPU Reset
Switch is accessed through a small hole at the rear of the unit near the label
LCD Backlight
The display can be temporarily illuminated by pressing any two buttons simultaneously
Table 1: Functional Reference table