Tyco 801AP MX Скачать руководство пользователя страница 3

801AP

17A-05-AP

4

 8/07

© 2007 Tyco Safety Products

PAGE 3 of 10

EQUIPMENT:

PUBLICATION:

ISSUE No. 

&

 DATE:

The Service Tool requires a 6-digit password to be entered.
The password is different for each service tool and will be
issued by the respective branch office.

The password uses only the digits 1 to 4, and may be entered
by pressing the corresponding buttons F1 to F4; eg, button F1
to enter 1, button F2 to enter 2, etc. 

The user has 3 attempts to enter the correct code. On the 4th
attempt
 the following screen is displayed: 

The user must telephone the branch office to get the correct
6-digit password at this point. 

WARNING:

FAILURE TO ENTER THE CORRECT 

PASSWORD AT THE FOURTH ATTEMPT 

WILL RESULT IN THE SERVICE TOOL 

SWITCHING OFF AND ALLOWING ONLY ONE 

ATTEMPT ON SUBSEQUENT POWERING UP 

OF THE UNIT.

The password has an expiry time associated with it.

The hours left indicates the actual usage (switched on) time
remaining.

CAUTION:

ONCE THE HOURS LEFT REACHES ZERO, 

THE SERVICE TOOL BECOMES 

INOPERABLE AND MUST BE RETURNED TO 

THE BRANCH OFFICE.

When there is less than 50 hours, the expiry time appears. The
screen displays the expiry time in the form of ‘Hours Left’: 

On successful entry of the password, the following screen is

displayed: 

This is the start of the main menu options, which are
discussed further in para. 3.5. 

Phone Base
Password:

Hours Left: 46
Password:

(example)

<--  Select  -->
ADDRESS PROGRAM

3.3

CONNECTING TO A DEVICE 

Detectors are inserted as shown in Fig. 3. Use the marking on
the service tool (above F1 button) to align the detector. Place
detector in position 1 to engage and then twist clockwise to
position 2 to lock. 

Ancillaries are connected to the ‘AUX’ socket using the
ancillary connection lead connector lead as shown in Fig. 4. 

Note:

1) It is good practice to connect only a detector or

ancillary at any one time. However, the Service
Tool is equipped with a port interlock feature.
When the ancillary lead is connected to the ‘Aux’
socket, communication with the detector will be
disabled. When the ancillary lead is removed,
the detector will be able to communicate. 

Fig. 3

Connecting a detector 

POSITION 2

POSITION 1

MARKING

Fig. 4

Connecting to an ancillary 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание 801AP MX

Страница 1: ...e Tool to ancillary connector lead 110 or 230V ac adaptor plus lead 4 x rechargeable AA size Nickel Metal Hydride batteries The 801AP is designed to be used as a desktop unit clipped to a trouser belt...

Страница 2: ...ment cover whilst removing it b Insert the batteries ensuring correct polarity as shown inside the battery compartment c Replace the battery compartment cover and screw down CAUTION ENSURE ONLY NICKEL...

Страница 3: ...BE RETURNED TO THE BRANCH OFFICE When there is less than 50 hours the expiry time appears The screen displays the expiry time in the form of Hours Left On successful entry of the password the followi...

Страница 4: ...rows on the top line of the display The bottom line of the main menu displays the option The top line position of text is always shown in relation to the F1 F4 buttons above In the Main Menu F1 scroll...

Страница 5: ...e previous screen If Write is selected then the following message will appear for 2 seconds This is followed by Having programmed an address the Service Tool moves to the next sequential unused addres...

Страница 6: ...eported on three alternating displays b Select MEASURE CO LEVEL Self Test is available on the following types of detectors MX Ionisation MX Optical Heat including 814P Optical sensing element only MX...

Страница 7: ...ve the cursor to the eigth bit on the far right and toggle this bit 1 The LED should illuminate red on all models Menu 11100011L 227 Menu Tog Set 00000000L 0 CUSTOMER CODE CAUTION THIS MENU OPTION CHA...

Страница 8: ...ified by the C tick mark on the product identification label on the underside of the tool See Fig 10 When using with Intrinsically Safe 800Ex devices the Service Tool must be used in a non hazardous s...

Страница 9: ...utput functional base interface output Dirtiness Indicates the contamination level of the optical chamber expressed as a percentage where 100 is the fault level Device Type ID Displays the device type...

Страница 10: ...lpoint EX n Baseefa CP830Exn 132 DIN Indoor Europe DIN820 133 DIN Outdoor Europe DIN830 134 Mini Input Monitored Aus NZ MIM801 138 Table 2 Type Values JM an 24th August 2007 DESCRIPTION MARKET MODEL T...

Отзывы: